Superior SSDVPF-CNE-B Installation Instructions Manual Download Page 16

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

16

v

 SV4.5VF

Firestop / spacer

u

SV4.5SU

Support Strap

8 ft. (2.4 M)

Maximum

u

SV4.5SP

Support Plate

Ceiling Framing

u

Secured 

to Vent with 

Appropriate 

Fasteners

1” (25.4 mm) 

Minimum 

Clearance to

Combustibles

v

When using 

secure Flex, use 

Firestop/Spacer 

SF4.5VF

Framing Dimensions for Roof

Inches (millimeters)

Pitch

C

D

0/12

10-1/2 in.

(267 mm)

10-1/2 in.

(267 mm)

6/12

10-1/2 in.

(267 mm)

12 in.

(305 mm)

12/12

10-1/2 in.

(267 mm)

17-3/4 in.

(451 mm)

Figure 24

 - Roof Framing

C

D

Figure 25

Storm

Collar

Figure 26

Flashing

7-5/8”

(194 mm)

4-13/16 

(122 mm)

(206 mm)

If the vent system extends more than 5 feet 

(1.5  m) above the roof flashing, stabilizers may 

be necessary. Additional screws may be used 

at section joints for added stability. Guide wires 

may be attached to the joint for additional sup-

port on multiple joint configurations.

G.

 

Continue installation of horizontal / inclined 

sections -

 Continue with the installation of the 

straight vent sections in horizontal / inclined run 

as described in 

Step C.

 Install support straps 

every 5 feet (1.52 m) along horizontal / inclined 

vent runs using conventional plumber’s tape. 

See Page 19, Figure 32. 

 

It is very important 

that the horizontal / inclined run be maintained 

in a straight (no dips) and recommended to 

be in a slightly elevated plane, in a direction 

away from the fireplace of 1/4" rise per foot (20 

mm per meter) which is ideal,

 

though rise per 

foot run ratios that are smaller are acceptable 

all the way down to at or near level.  

F. Change vent direction to horizontal / inclined 

run -

 At transition from or to a horizontal / in-

clined run, install the SV4.5E45 and SV4.5E90 

elbows in the same manner as the straight vent 

sections. The elbows feature a twist section to 

allow them to be routed about the center axis 

of their initial collar section to align with the 

required direction of the next vent run element. 

Twist elbow sections in a clockwise direction 

only so as to avoid the possibility of unlocking 

any of the previously connected vent sections 

(see Figure 23).

Use  a  carpenter’s  level  to  measure  from  a 

constant surface and adjust the support straps 

as necessary. 

It is important to maintain the required clear-

ances to combustibles: 1" (25 mm) at all sides 

for all vertical runs; and 3" (76 mm) at the top, 

1" (25 mm) at sides, and 1" (25 mm) at the 

bottom for all horizontal / inclined runs.

H.

 

Frame roof opening -

 Identify location for 

vent at the roof. Cut and/or frame opening per 

Roof Framing Chart and Figure 24.

Figure 23

Swivel Joint

(360° swivel)

SV4.5E45

45° Elbow)

Swivel Joint

(360° swivel)

SV4.5E90

90° Elbow)

SV4.5FA or

SV4.5FB Flashing

and SV4.5SC 

Storm Collar

SV4.5CGV-1

Termination

8-1/8"

K. Install the vertical termination - 

The final 

Step involves installation of the SV4.5CGV-1 

Vertical Termination.  Extend the vent sections 

to  the  height  as  shown  in  the  "Vertical  vent 

termination section" (Page 6, Figure 4B).  The 

SV4.5CGV-1 Vertical Termination (Figure 26) 

can be installed  in the exact same fashion as 

any  other 

Secure  Vent™

  section.  Align  the 

termination  over  the  end  of  the  previously 

installed section, adjusting the radial alignment 

until the four locking dimples of the termination 

are aligned with the inlets of the four incline 

channels of the last vent section.  Push the ter-

mination down until it fully engages, then twist 

the termination clockwise running the dimples 

down and along the incline channels until they 

are seated at the end of the channels.

I.

 

Install the roof flashing - 

Extend the vent 

sections through the roof structure. Install the 

roof flashing over the vent section and position 

such that the vent column rises vertically (use 

carpenters level - see Figure 25). Nail along 

perimeter to secure flashing or adjust roofing 

to overlap the flashing edges at top and sides 

only and trim where necessary. Seal the top 

and both sides of the flashing with waterproof 

caulking.

J. Install the storm collar -

 Install the storm 

collar, supplied with the flashing, over the vent / 

flashing joint. See Figure 25.  Loosen the storm 

collar screw. Slide collar down until it meets 

the top of the flashing. Tighten the adjusting 

screw.    Apply  non-combustible  caulking  or 

mastic around the circumference of the joint 

to provide a water tight seal.

Figure 22

Summary of Contents for SSDVPF-CNE-B

Page 1: ...de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur s par...

Page 2: ...e installed the electrical power must be provided at the time of appliance in stallation The Electronic appliances have an electronic intermittent pilot ignition system External electrical power is re...

Page 3: ...y be required due to excessive lint from carpeting bed ding material etcetera It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean Remarque...

Page 4: ...e reduced by either Using gas that has been derated by the gas company Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the USA National F...

Page 5: ...rer s instructions and the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 in the United States or the StandardforInstallationinMobileHomes CAN CSA Z240 MH Series in Canada C...

Page 6: ...54 ANSI Z223 1 Roof Pitch Feet Meters Flat to 6 12 1 0 0 3 6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10 12 to 11 12 3 25 0 99 11 12 to 12 12 4 0 1 22 12...

Page 7: ...cm for appliances 10 000 BTU hr 3kW 12 in 30 cm for appliances 10 000 BTU hr 3kW and 100 000 BTU hr 30kW 36 inches 91 cm for appliances 100 000 BTU hr 30kW 6 in 15 2 cm for appliances 10 000 BTU hr 3...

Page 8: ...owing exception If the optional radiant panels are installed the non combustible material may cover any portion of the top radiant panel or the air gaps surrounding the top radiant panel down to the t...

Page 9: ...plates and remove the cardboard from beneath each plate be careful not to damage the white gasket See Figure 10 NOTE INSTALLATION DIAGRAMS AND INSTRUCTIONSSHOWTHEFRONTOFTHE APPLIANCEASTHESIDEWHICHHAS...

Page 10: ...108 679 11 3 8 267 289 7 178 5 1 8 130 12 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Lou...

Page 11: ...uance without notice Appliance has a factory installed vent seal cap see Figures 15 and 16 on Page 13 in each flue outlet EFFICIENCIES SSDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louv...

Page 12: ...torand1 2inchshutoff valve see Figure 47 on Page 27 See Massachusetts Requirements on Page 4 foradditionalrequirementsfor installations in the state of Massachusetts in the USA The gas supply line sho...

Page 13: ...1 in Canada Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier D gagementconformeauxcodesd installationlocauxetauxexigences du foumisseunde gaz...

Page 14: ...0 0 3 5 4 5 7 3 0 0 2 0 0 2 5 6 4 5 7 8 3 0 0 0 0 1 1 5 9 4 5 2 1 4 1 0 2 0 0 3 1 5 5 2 4 1 0 0 0 1 2 5 5 5 5 2 6 4 0 1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9...

Page 15: ...4 5LA may be used to provide the installer with an option in installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or...

Page 16: ...ections see Figure 23 Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary It is important to maintain the required clear ancestocombustibles 1 25mm at...

Page 17: ...ori zontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio Forevery1footof V verti cal you are allowed 5 feet of H horizontal run up to a...

Page 18: ...4 2 0 610 1 0 305 10 3 048 4 1 219 2 0 610 15 4 572 6 1 829 3 0 914 20 6 096 8 2 438 4 1 219 V V1 H H1 40feet 12 2m Max H 8 feet 2 438 meters Max H H1 20 feet 6 096 meters Max Example If 20 feet total...

Page 19: ...geandsealboththe inner and outer pipe elements with the same procedure Sealant and securing screws are not required Note An elbow may also be attached to the appliance collar Attach in the same manner...

Page 20: ...ey are in the same area as a hot termination To prevent contact with hot surfaces we recommend the use of a Termination Guard See Page 33 This can be purchased at your local dealer SV4 5HT 2 Terminati...

Page 21: ...hes mm Termination Kit Only 6 to 9 1 4 152 to 235 TerminationKitand 6In Vent Section SV4 5L6 10 3 4 to 14 273 to 356 Termination Kit and 12 in Vent Section SV4 5L12 16 3 4 to 20 426 to 508 Termination...

Page 22: ...5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF Note See Table 9 as an aid in venting component selection for a particular range of exterior...

Page 23: ...meters Max H H1 H2 20 feet 6 096 meters Max Example If 20 feet total H H1 H2 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio F...

Page 24: ...nner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pull a...

Page 25: ...es 43 and 44 b Optional Wall Switch Wall Thermostat OrRemoteControlReceiver Installsnap bushing provided in Electrical Outlet Kit See Figure 44 into control switch knock out in side panel see Figures...

Page 26: ...x Wiring when using unit mounted relay module BK W G C A V 0 2 1 Igniter Connector Leave the OFF ON switch which is integral with the gas valve in the ON position Optional Control Switches Wall Switch...

Page 27: ...that will allow the shut off valve to be easily attached by hand to the gas flex line Using pipe dressing materials appropriate for the gas type securely affix the shut off valve to this determined pi...

Page 28: ...al tongues of flame on the burner Make sure all ports are open and producing flame evenly across the burner If any ports are blocked or partially blocked clean out the ports With the gas line installe...

Page 29: ...ers as it is being installed c Asafinalcheckforcorrectlogsetplacement check that the four outer notches on the underside of the log set fit over the burner tines as indicated in Figure 53 Burner Grate...

Page 30: ...ld be increased If air shutter is open too far Flame will be blue Air shutter gap should be decreased Step 9 INSTALLATION AND REMOVAL OF GLASS DOOR Only doors certified with the appliance shall be use...

Page 31: ...lly clockwise Propane fully counter clockwise Settings are shown for each burner Air Shutter Adjusting Rod Air Shutter Adjusting Arms Orifice Increase Shutter Opening In This Direction Decrease Shutte...

Page 32: ...ur liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisis...

Page 33: ...flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 2 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 2 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Co...

Page 34: ...12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 25 H1988 CTSA 33 Ch...

Page 35: ...th the re quirements of the CAN CSA B149 1 Installation code Laconversiondevra treeffectu e conform ment aux recommanda tions des autorit s provinciales ayant juridiction et conform ment aux exigences...

Page 36: ...rimary air opening setting NOTE Each model has two burners and 2 Orifices Pilot Orifice Pilot Assembly Igniter Assembly Retaining Clip Flare Nut Note If the igniter is damaged a replacement kit is ava...

Page 37: ...S NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER BURNER ORIFICE Step 10 Reassemble the remaining compo nents by reversing the procedures outlined in the preceding steps Step 11 Attach the conversion...

Page 38: ...38 NOTES...

Page 39: ...39 39 NOTES...

Page 40: ...earth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor...

Reviews: