background image

9

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

TYPICAL INSTALLATION SEQUENCE

The typical sequence of installation is outlined 

below.    However,  each  installation  is  unique 

and  may  result  in  variations  to  the  steps 

described. 

See the page numbers references in the follow-

ing steps for detailed procedures.

Step 1.   (

Page  9)

  Construct  the  appliance 

framing. Position the appliance within 

the  framing  and  secure  with  nailing 

flanges.

Step 2.   (

Page 12)

 Route gas supply line to ap-

pliance location.

Step 3.   (

Page 13)

 Install the vent system and 

exterior termination.  

Step 4.   (

Page 26)

  Field Wiring  – Install the 

OFF/ON  burner  control  switch  and 

bring  in  electrical  service  line  for 

forced air-circulating blower (optional 

equipment). 

Step 5.   (

Page  27)

  Install  blower  kit  (optional 

equipment).

Step 6.   (

Page 28)

 Make connection to gas sup-

ply.

Step 7.    (

Page 29)

 Verify appliance operation. 

Step 8.   (

Page 29)

  Install the logs, decorative 

volcanic stone and glowing embers.

Step 9.   (

Page  31)

  Install  glass  door  assem-

blies.

Step 10.  (

Page  31)

  Adjust  burner  primary  air 

shutter to achieve proper flame appear-

ance.

Step 11.  (

Page 32)

  Install the decorative trim 

and hoods.

Step 12.  

(Page 33)

 Attach Safety in Operation 

Warnings.

Step 1. FRAMING

Frame these appliances as illustrated in 

Figures 

11 or 12.  

All framing details must allow for a 

minimum  clearance  to  combustible  framing 

members as shown in 

Table 5 

on

 Page 8

.

If the appliance is to be elevated above floor 

level,  a  solid  continuous  platform  must  be 

constructed below the appliance. 

Headers  may  be  in  direct  contact  with  the 

appliance  top  spacers  but  must  not  be  sup-

ported by them or notched to fit around them.  

All construction above the appliance must be 

self-supporting, DO NOT use the appliance for 

structural support. 

Side Nailing Flanges

The  fireplace  should  be  secured  to  the  fram-

ing  at  the  side(s)  of  the  appliance  using  the 

factory-provided  nailing  flanges.  Install  the  8 

nailing flanges as shown in 

Figure 10

 using the 

existing screws. Position the fireplace within 

the framing. When required, the tabs may be 

bent 90 degrees by hand or with the assistance 

of a hammer. Use  wood screws to secure the 

nailing flanges to the framing. 

See Table 5 on 

Page  8

  for  clearances  of  framing  members 

to cabinet parts. The nailing flange itself can 

directly contact framing.

Floor Nailing Tabs - Secure the fireplace to the 

floor as shown in  

Figure 10. 

Figure 10 - 

Nailing Flanges

Remove these screws and use them 

when installing nailing flanges.

Nailing Flanges

Turn nailing tabs down and secure to floor with 

8d nails or other appropriate fasteners on both 

sides of appliance which do not have viewing 

glass panels.

SDVST Shown (SDVPF - No nailing 

flanges on end with glass panel)

DETAILED INSTALLATION STEPS

The appliance is shipped with all gas controls 

and components installed and pre-wired. 

1.  Remove the shipping carton.  Remove the 

shipping  pad,  exposing  the  front  glass 

door.

2.  Open  the  two  latches  (located  under  the 

firebox floor) securing the glass door. Re-

move the door by tilting it outward at the 

bottom and lifting it up. Set the door aside 

protecting it from inadvertent damage. 

See 

Removing Glass Panels 

on

 Page 31.

2. Remove the top louvered panel and locate 

the pressure relief plates.

3. Lift the pressure relief plates and remove 

the cardboard from beneath each plate (be 

careful not to damage the white gasket). 

See 

Figure 9

.

*   NOTE:  INSTALLATION  DIAGRAMS  AND 

INSTRUCTIONS SHOW THE FRONT OF THE 

APPLIANCE AS THE SIDE WHICH HAS VALVE 

ACCESS, EXCEPT WHERE NOTED.

       WARNING 

Failure  to  position  the  parts  in 

accordance with these diagrams 

or failure to use only parts specifi-

cally approved with this appliance 

may result in property damage or 

personal injury.

       AVERTISSEMENT 

Risque  de  dommages  ou  de 

blessures  si  les  pièces  ne  sont 

pas  installées  conformément  à 

ces schémas et ou si des pièces 

autres que celles spécifiquement 

approuvées avec cet appareil sont 

utilisées.

Figure 9

 

REMOVE

CARDBOARD

BEFORE USING

REMOVE

CARDBOARD

BEFORE USING

Pressure Relief Plates

Remove Cardboard Before 

Using Appliance

Summary of Contents for SDVPF-N-B

Page 1: ...sing property damage personal injury or death vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrica...

Page 2: ...with piezo ignition system If any optional accessories that will require electrical power are to be installed the electrical power must be provided at the time of appliance in stallation These vented...

Page 3: ...en marche Note Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent c...

Page 4: ...n and in the USA the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition or in Canada the CAN CSA B149 1 latest edition NOTE Flame appearance will diminish 4 per thousand feet NOTE Each model ha...

Page 5: ...pareil ne peut tre converti d autres gaz sauf si une trousse de conversion est utilis e CAUTION Ensure that the cross mem bers are not cut or weakened during installation The structural integrity of t...

Page 6: ...s For Vents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch Feet Meters Flat to 6 12 1 0 0 3 6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10...

Page 7: ...Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 6 in 15cm for appliances 10 000 Btuh 3kW 12 in 30cm for appliances 10 000 Btuh 3kW and 100 0...

Page 8: ...mantels vary according to the depth of the mantel See Figure 6 Mantels constructed of non combustible materials may be installed at any height above the appliance opening however do not allow anythin...

Page 9: ...flanges as shown in Figure 10 using the existing screws Position the fireplace within the framing When required the tabs may be bent 90 degrees by hand or with the assistance of a hammer Use wood scr...

Page 10: ...2 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Louvered Control Compartment Door Left Side...

Page 11: ...ral Propane Gas BTU Input 37 500 MV Low 30 000 Co axial DV Vent Size 4 1 2 Inner 7 1 2 Outer EFFICIENCIES SDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louvered Control Compartment Door...

Page 12: ...ts for installations in the state of Massachusetts in the USA The gas supply line should Not be connected to the appliance until Step 6 Page 28 Apipejointcompoundratedforgasshouldbe used on the thread...

Page 13: ...learances are in accordance with local installation codes and the requirements of the gas supplier D gagementconformeauxcodesd installationlocauxetauxexigences du foumisseunde gaz Use only approved ve...

Page 14: ...4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2 0 4 5 7 9 5 2 1 8 1 0 0 0 2 3 2 0 1 5 8 2...

Page 15: ...to the ceiling joists Route the vent sections through the framed opening and secure the firestop spacer with appropriate fasteners at each corner Remember to maintain 1 25 mm clear ance between verti...

Page 16: ...the vent E Support the vertical vent run sections Note Properventingsupportisveryimportant The weight of the vent must not be supported by the fireplace in any degree Support the vertical portion of t...

Page 17: ...ertical vent termination section Page 6 Figures 3A and 3B The SV4 5CGV 1 Vertical Termination Figure 27 can be installed in the exact same fashionasanyotherSecureVentsection Align the termination over...

Page 18: ...table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet VERTICAL VENT FIGURES TABLES Notes Secure Vent rigid...

Page 19: ...very 1 foot of V vertical you are allowed 5 feet of H H1 horizontal run up to a maximum total horizontal run of 20 feet Example If 20 feet total H H1 horizontal vent run is needed then 4 feet minimum...

Page 20: ...the component clockwise runningthedimplesdownandalong the incline channels until they seat at the end of thechannels TheunitizeddesignoftheSecure Ventcomponentswillengageandsealboththe inner and oute...

Page 21: ...riodoftime following the use of the fireplace Young children should be carefully supervised when they are in the same area as a hot termination To prevent contact with hot surfaces we recommend the us...

Page 22: ...degree elbows are used SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible floor or ceil ing SV4 5HF Secure Vent SF4 5HF Secure Flex fir...

Page 23: ...rizontal run up to a maximum horizontal run of 20 feet V H H 1 Table G H H1 Maximum V Minimum feet meter feet meter 3 0 914 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 21...

Page 24: ...eof exterior wall thicknesses vWall Firestop Spacer SV4 5HF Square termination SV4 5HT 2 shown V H2 H1 H v Wall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uWhen using Secure Flex use Fir...

Page 25: ...e inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pul...

Page 26: ...ing the gas valve control knob or connect wires to optional wall thermostat wall switch or remote control to operate unit 1 If any of the original wire as supplied must be replaced 1 it must be replac...

Page 27: ...ply wire to the top outlet sblackpigtailleadandtotheswitch s black lead Connect the white supply wire to the neutral terminal of the outlet box CAUTIONS Remove the carton support from the control comp...

Page 28: ...ge 12 to a point within the control compartment that will allow the shut off valve to be easily attached by hand to the gas flex line Using pipe dressing materials appropriate for the gas type securel...

Page 29: ...appliance will not require such purging Inspect the pilot flame Millivolt Appliance Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of oran...

Page 30: ...ea on both sides of the log set The glowing embers may touch one another but should not overlap each other FRONT OF FIREPLACE REAR BURNER FRONT BURNER Outer Log Notch Location FIREBOX SUBFLOOR Outer L...

Page 31: ...re n est pas en place est craqu ou bris Top Flange on Glass Door Bottom Vee flange Glass Door Glass Door Latch Glass Door Firebox Floor INSTALLING OR REMOVING GLASS DOOR Figure 55 Note When installing...

Page 32: ...aming Step 11 Hood Installation All of these appliances must have hoods installed prior to operating see Figure 58 Slide the hood into the slots on the lower edge of the cabinet top see Figure 58 Fini...

Page 33: ...sadhesivasmultiling es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeelinterruptor ope...

Page 34: ...SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 12 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 12 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Collar 6 per box 8 H2246 SV4 5HF Firestop Spacer Hor...

Page 35: ...ent roof support collar assembly roof flashing and storm collar 19 56L75 SFVT45 Vertical Termination for flex 6 12 to 12 12 with flex adapter section of rigid vent roof support collar assembly roof fl...

Page 36: ...2 12 Pitch 25 92L09 SV FSTFE Firestop Thimble SV Flat with Extension 25 92L10 SV FST1E Firestop Thimble SV 1 12 Pitch with Extension 25 92L11 SV FST2E Firestop Thimble SV 2 12 Pitch with Extension 26...

Page 37: ...or dance with the manufacturer s instructions and all applicable codes and requirementsoftheauthorityhavingjurisdiction Iftheinformationinthese instructionisnotfollowedexactly afire explosionorproduct...

Page 38: ...Page 29 Step 11 Attach manometer to the manifold side pressure test fitting and verify manifold pressure reads 3 5 inches water column 0 87 kPa for natural gas and 10 0 inches water column 2 49 kPa f...

Page 39: ...39 NOTES...

Page 40: ...earth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor...

Reviews: