background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

25

D. Install Firestop / Spacers at ceilings and walls 

When Secure Flex penetrates a wall or ceiling, 

a firestop / spacer is required: use the SF4.5 VF 

firestop / spacer for ceilings and the SF4.5 HF 

firestop / spacer for walls. See the appropriate 

sections and 

Figure

s shown throughout the vent-

ing section for their installation requirements. 

NOTE:  Outer pipe is pulled away to show 

the detail of the inner pipe.

APPLY  ONLY  MIL-PAC  BLACK 

HIGH  TEMPERATURE  SEALANT 

(Cat. No. 10K81) to the outside 

surface  of  both  collars  of  the 

adapter (be especially careful to 

fill the grooves of the outer collar 

to be covered by the flexible pipe) 

and slide flexible pipe over inner 

and outer adapter collars.

1-3/4 inch (44 mm) flexible 

pipe and adaptor outer collar 

overlap

Adapter (SV4.5RF)

Attach adaptor to appliance 

Collar, or secure vent sections

Flex Vent

Gear Clamps

Securing Screw 

- 3 places, 120° apart 

(equally spaced) just 

below gear clamp

1-3/4  in.  (44  mm)  flexible 

pipe and adaptor inner collar 

overlap

Securing Screw - 3 places, 

equally  spaced,  just  below 

gear clamp.

Figure 42

VERTICAL OR HORIZONTAL VENTING USING 

SECuRE FLEX

 KITS AND COMPONENTS

Secure  Flex™  venting  kits  and  components 

may be used in any venting application in place 

of  rigid  Secure  Vent™  (SV4.5)  direct-vent 

components.  All restrictions, clearances and 

allowances that pertain to the rigid piping apply 

to the flexible venting.  

Secure Flex

 kits may 

not be modified; also, under no circumstances 

may separate sections of flex pipe be joined 

together

Using  adapter  (SV4.5RF),  Secure  Flex  kits 

may be added to the end of a vent run made 

up of rigid Secure Vent (SV4.5) vent sections 

provided that doing so does not violate any of 

the venting length, height, routing, horizontal 

to  vertical  ratio  requirements  or  clearance 

considerations detailed in this manual.

Secure  Flex  kits  come  with  an  adapter  that 

can be fitted to the inclined channel end of the 

last Secure Vent (SV4.5) vent section in a rigid 

system in the exact same fashion as any other 

Secure Vent section.

Align  the  dimpled  end  of  the  adapter  over 

the  previously  installed  section  or  appliance 

collar, adjusting the radial alignment until the 

four locking dimples of the adapter are aligned 

with the inlets of the four incline channels of 

the  last  vent  section  or  collar.    Push  on  the 

adapter  until  it  fully  engages,  then  twist  the 

adapter clockwise running the dimples down 

and along the incline channels until they seat 

at the end of the channels.

Attach the flexible vent to the adapter as fol-

lows 

(see also Figure 42):

A. Install the Inner Flex Pipe - 

1. Install the small  gear clamp loosely around 

the inner flexible vent pipe, push it back out 

of the way.

2. Apply a bead of Mill-Pac Black (700° F) high 

temperature sealant - Catalog No. 10K81 

to  the  inner  adapter  collar,  approximately 

1/2 inch from the end.

3. Pull and extend the inner flexible vent pipe. 

4.  Slide the inner flex pipe over the adapter col-

lar. Ensure the flexible vent pipe completely 

engages the adapter collar to a distance of 1 

3/4 inches from the end, and that it is free  

from damage or tears. 

5. Slide  the  gear  clamp  down  and  tighten  it 

fully to secure the flexible vent to the adapter 

inner collar approximately 3/4 inch from the 

end of the flex.

6.  Install  three  screws,  120  degrees  apart, 

through the flexible vent pipe and into the 

adapter collar just below the gear clamp to 

provide additional security to the connec-

tion.

B. Install the Outer Flex Pipe - 

1. Install the large gear clamp loosely around 

the outer flexible vent pipe, push it back out 

of the way. 

2. Apply a bead of Mill-Pac Black (700° F, high 

temperature sealant - Catalog No. 10K81) 

to the outer adapter collar; to the grooves 

of the collar which extend approximately 1 

inch from the end and to the flat surface, 

approximately 1 3/8 inches from the end. 

3. Pull and extend outer flexible vent pipe. 

4. Slide the outer flex pipe over the adapter col-

lar. Ensure the flexible vent pipe completely 

engages the adapter collar to a distance of 

1³⁄₄ inches from the end, and that it is free 

from damage or tears. 

5. Slide  the  gear  clamp  down  and  tighten  it 

fully to secure the flexible vent to the adapter 

outer collar approximately 3/4 inch from the 

end of the flex.

6. Install  three  screws,  120  degrees  apart, 

through the flexible vent pipe and into the 

adapter collar just below the gear clamp to 

provide additional security to the connec-

tion.

C. Route Flex Vent -   

Ensure that the flex vent is properly routed to 

provide the required clearance. Do not allow the 

flexible vent to bend in a radius tighter than 5" 

(127 mm). Refer to 

Figure 43

. Space out the 

internal flex vent spacers evenly - approximately 

every 6 inches - and avoid kinking of inner pipe. 

Support horizontal sections of flex with metal 

straps at 2 foot (0.61 m) intervals. 

E. Attach Flex Vent to Termination -  

Secure  Flex  components  can  be  purchased 

separately and attached to bulk lengths of Se-

cure Flex flexible tubing cut to size at the job 

site.   Secure the flexible vent to the Secure Flex 

terminations in the same manner (see

 Figure 

42) 

as it was attached to the adapter.

Note:

 

Secure Flex vent must be attached to Se-

cure Flex terminations only. DO NOT substitute 

Secure Vent terminations or the Secure Vent 

adapter for Secure Flex components. The collars 

of Secure Flex terminations and adapters have a 

different diameter than that used with the Secure 

Vent pipe.  Additionally, Secure Flex components 

have an extended length center tube for use in 

attaching the flexible vent.

Flexible Vent 

Section

5” (127 mm)

Radius

Minimum

Figure 43

Summary of Contents for SDVPF-N-B

Page 1: ...sing property damage personal injury or death vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrica...

Page 2: ...with piezo ignition system If any optional accessories that will require electrical power are to be installed the electrical power must be provided at the time of appliance in stallation These vented...

Page 3: ...en marche Note Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent c...

Page 4: ...n and in the USA the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition or in Canada the CAN CSA B149 1 latest edition NOTE Flame appearance will diminish 4 per thousand feet NOTE Each model ha...

Page 5: ...pareil ne peut tre converti d autres gaz sauf si une trousse de conversion est utilis e CAUTION Ensure that the cross mem bers are not cut or weakened during installation The structural integrity of t...

Page 6: ...s For Vents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch Feet Meters Flat to 6 12 1 0 0 3 6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10...

Page 7: ...Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 6 in 15cm for appliances 10 000 Btuh 3kW 12 in 30cm for appliances 10 000 Btuh 3kW and 100 0...

Page 8: ...mantels vary according to the depth of the mantel See Figure 6 Mantels constructed of non combustible materials may be installed at any height above the appliance opening however do not allow anythin...

Page 9: ...flanges as shown in Figure 10 using the existing screws Position the fireplace within the framing When required the tabs may be bent 90 degrees by hand or with the assistance of a hammer Use wood scr...

Page 10: ...2 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Louvered Control Compartment Door Left Side...

Page 11: ...ral Propane Gas BTU Input 37 500 MV Low 30 000 Co axial DV Vent Size 4 1 2 Inner 7 1 2 Outer EFFICIENCIES SDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louvered Control Compartment Door...

Page 12: ...ts for installations in the state of Massachusetts in the USA The gas supply line should Not be connected to the appliance until Step 6 Page 28 Apipejointcompoundratedforgasshouldbe used on the thread...

Page 13: ...learances are in accordance with local installation codes and the requirements of the gas supplier D gagementconformeauxcodesd installationlocauxetauxexigences du foumisseunde gaz Use only approved ve...

Page 14: ...4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2 0 4 5 7 9 5 2 1 8 1 0 0 0 2 3 2 0 1 5 8 2...

Page 15: ...to the ceiling joists Route the vent sections through the framed opening and secure the firestop spacer with appropriate fasteners at each corner Remember to maintain 1 25 mm clear ance between verti...

Page 16: ...the vent E Support the vertical vent run sections Note Properventingsupportisveryimportant The weight of the vent must not be supported by the fireplace in any degree Support the vertical portion of t...

Page 17: ...ertical vent termination section Page 6 Figures 3A and 3B The SV4 5CGV 1 Vertical Termination Figure 27 can be installed in the exact same fashionasanyotherSecureVentsection Align the termination over...

Page 18: ...table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet VERTICAL VENT FIGURES TABLES Notes Secure Vent rigid...

Page 19: ...very 1 foot of V vertical you are allowed 5 feet of H H1 horizontal run up to a maximum total horizontal run of 20 feet Example If 20 feet total H H1 horizontal vent run is needed then 4 feet minimum...

Page 20: ...the component clockwise runningthedimplesdownandalong the incline channels until they seat at the end of thechannels TheunitizeddesignoftheSecure Ventcomponentswillengageandsealboththe inner and oute...

Page 21: ...riodoftime following the use of the fireplace Young children should be carefully supervised when they are in the same area as a hot termination To prevent contact with hot surfaces we recommend the us...

Page 22: ...degree elbows are used SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible floor or ceil ing SV4 5HF Secure Vent SF4 5HF Secure Flex fir...

Page 23: ...rizontal run up to a maximum horizontal run of 20 feet V H H 1 Table G H H1 Maximum V Minimum feet meter feet meter 3 0 914 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 21...

Page 24: ...eof exterior wall thicknesses vWall Firestop Spacer SV4 5HF Square termination SV4 5HT 2 shown V H2 H1 H v Wall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uWhen using Secure Flex use Fir...

Page 25: ...e inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pul...

Page 26: ...ing the gas valve control knob or connect wires to optional wall thermostat wall switch or remote control to operate unit 1 If any of the original wire as supplied must be replaced 1 it must be replac...

Page 27: ...ply wire to the top outlet sblackpigtailleadandtotheswitch s black lead Connect the white supply wire to the neutral terminal of the outlet box CAUTIONS Remove the carton support from the control comp...

Page 28: ...ge 12 to a point within the control compartment that will allow the shut off valve to be easily attached by hand to the gas flex line Using pipe dressing materials appropriate for the gas type securel...

Page 29: ...appliance will not require such purging Inspect the pilot flame Millivolt Appliance Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of oran...

Page 30: ...ea on both sides of the log set The glowing embers may touch one another but should not overlap each other FRONT OF FIREPLACE REAR BURNER FRONT BURNER Outer Log Notch Location FIREBOX SUBFLOOR Outer L...

Page 31: ...re n est pas en place est craqu ou bris Top Flange on Glass Door Bottom Vee flange Glass Door Glass Door Latch Glass Door Firebox Floor INSTALLING OR REMOVING GLASS DOOR Figure 55 Note When installing...

Page 32: ...aming Step 11 Hood Installation All of these appliances must have hoods installed prior to operating see Figure 58 Slide the hood into the slots on the lower edge of the cabinet top see Figure 58 Fini...

Page 33: ...sadhesivasmultiling es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeelinterruptor ope...

Page 34: ...SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 12 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 12 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Collar 6 per box 8 H2246 SV4 5HF Firestop Spacer Hor...

Page 35: ...ent roof support collar assembly roof flashing and storm collar 19 56L75 SFVT45 Vertical Termination for flex 6 12 to 12 12 with flex adapter section of rigid vent roof support collar assembly roof fl...

Page 36: ...2 12 Pitch 25 92L09 SV FSTFE Firestop Thimble SV Flat with Extension 25 92L10 SV FST1E Firestop Thimble SV 1 12 Pitch with Extension 25 92L11 SV FST2E Firestop Thimble SV 2 12 Pitch with Extension 26...

Page 37: ...or dance with the manufacturer s instructions and all applicable codes and requirementsoftheauthorityhavingjurisdiction Iftheinformationinthese instructionisnotfollowedexactly afire explosionorproduct...

Page 38: ...Page 29 Step 11 Attach manometer to the manifold side pressure test fitting and verify manifold pressure reads 3 5 inches water column 0 87 kPa for natural gas and 10 0 inches water column 2 49 kPa f...

Page 39: ...39 NOTES...

Page 40: ...earth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor...

Reviews: