background image

15

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

TROUBLESHOOTING THE ELECTRONIC IGNITION SYSTEM

N

ote:

 Before troubleshooting, be sure that the appliance main line gas shut-off valve, the gas control valve and the wall switch are in

the “ON” position.

Important: “ON/OFF” switch must be “OFF” before performing continuity test. Adjust multimeter to the ohm setting when performing continuity tests.

Important:

 Valve system troubleshooting should only be accomplished by a qualified service technician.

Confirm 24Vac output from transformer (red and blue leads). If no, then replace
transformer.

Note:

 Before replacing transformer check wiring for loose connections or broken wires

and repair as needed. Turn off power before replacing transformer.

Disconnect the two black wires from the two red wires attached to the limit switch and
transformer (label wires for correct reattachment). Test “ON/OFF” wall switch for
continuity with a multimeter. If continuity is not indicated, switch is defective and must
be replaced.

Note: 

Before replacing “ON/OFF” switch be sure to check switch wiring for loose

connections or broken wires and repair as needed.

Reset the limit switch button.  If still not working

isolate the limit switch in the same manner

as the “ON/OFF” switch (label wires for correct reattachment) and test for continuity with
a multimeter. If continuity is not indicated, switch is defective and must be replaced.

If reading is not 24V at “TH” and “TR” terminals on ignition control, replace ignition
control module.

Check for availability of gas at control. Check that manual valve upstream of gas control
and manual valve on gas control are in the full “ON” position. Check for plugged pilot
orifice or plugged pilot tubing. Also check pilot key adjustment at gas control valve.

Confirm 24Vac at gas valve terminals “C” and “P” of the gas valve. If yes, valve is OK. If
no voltage, check the wiring. If wiring tests OK, check ignition control module.

Confirm 24Vac at “PV” and “PV/MV” on ignition control module. If no, replace the ignition
control.

Check if pilot line and pilot orifice are plugged. Clean or replace as necessary. Adjust pilot
flame if necessary.

Confirm that the igniter is sparking at the pilot assembly when the “ON/OFF” switch is
activated. If not, undertake the following steps:

With “ON/OFF” switch “OFF,” remove wire at “TR” terminal at the ignition control module.
Disconnect the electrode wire “IGN” at the ignition control. Connect one end of a jumper
wire to the metal blade of a small screwdriver. Attach the other end of the jumper wire to
any metal part of the chassis. Reconnect the “TR” terminal. Position end of metal blade
approximately

 

¹⁄₈

" (3 mm) from the “IGN” terminal. Activate the “ON/OFF” switch.

Sparking should occur between the “IGN” terminal and screwdriver blade. If sparking
does occur, the ignition control module is OK, but either the electrode wire of the igniter
is faulty and the pilot and electrode assembly should be replaced.

Electrode tip needs to be realigned to correct location.

 

³⁄₃₂

" to 

¹⁄₈

" (2 – 3 mm) gap between

electrode tip and pilot hood is desired.

Pilot and electrode igniter must be properly aligned so that the pilot flame impinges the
top

 

³⁄₄

" (19 mm) of the electrode igniter. The electrode igniter must be pushed all the way

into the pilot bracket. Adjust pilot flame if necessary.

Check main burner orifice(s) for stoppage. Clean or replace.

Check for 24 volts at gas operator terminals “M” and “C.” If there is a 24V reading and the
burner does not come on, the valve operator is defective and the gas valve must be
replaced.

Adjust pilot flame and/or check location of electrode igniter.

SYMPTOM

CORRECTIVE ACTION

1.

No spark and no pilot gas.

2.

Spark but no pilot gas
(no solenoid valve click).

3.

Spark but no pilot gas
(solenoid valve click).

4.

Pilot gas available, but
pilot does not light
(solenoid click).

5.

Pilot burning but main
burners will not come on.

Note: 

Wait at least 90

seconds after pilot lights
before doing the checkout
for possible causes.

6.

Burners come “ON” but go
“OFF.”

A.

Faulty transformer.

B.

“ON/OFF” switch defective.

C.

Limit switch defective.

D.

Ignition control module defective.

A.

No gas supplied to pilot valve.

B.

Faulty gas valve.

C.

Ignition control module defective.

A.

Gas supply to pilot restricted.

A.

Ignition control or igniter
defective.

B.

Sparking, but not at proper
location.

A.

Low pilot flame or improper
alignment of electrode igniter in
pilot flame.

B.

Burner orifice(s) plugged.

C.

Gas valve defective.

A.

Low pilot flame or electrode
igniter not correctly positioned.

POSSIBLE CAUSES

Summary of Contents for GHC-6500 SERIES

Page 1: ...tout autre appareil POUR VOTRE S CURIT Que faire si vous sentez une odeur de gaz Ne pas tenter d allumer d appareil Netouchez aucuninterrupteur Nepasvousservir des t l phones se trouvant dans le bati...

Page 2: ...absence of local codes installation must be in accordance with the National Electrical Code NFPA 70 latest edition In Canada thecurrentCSAC22 1CanadianElectricCode DO NOT ATTEMPT TO ALTER OR MODIFY T...

Page 3: ...ES USE CAUTION AROUND THE APPLIANCE TO AVOID BURNS OR CLOTHING IGNITION YOUNG CHILDREN SHOULD BE CARE FULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE WARNING DO NOT PLACE CLOTHING OR...

Page 4: ...near the gas valve in the control compartment 4 Always keep the appliance area clear and free from combustible materials gasoline and other flammable liquids 5 Remember Millivolt appliances have a co...

Page 5: ...ck on Adjustment To adjust the flame position the air shutter to the nominal setting Figure 10 Allow the burner to operate for at least 30 minutes Observe the flame continuously If it appears weak or...

Page 6: ...Accomplishing Person Procedure Inspecting Cleaning Burner Logs and Controls Check Flame Patterns and Flame Height Inspecting Cleaning Pilot and Burner Checking Vent System Appliance Checkout Replacin...

Page 7: ...l valve If a higher than normal temperature is sensed due to a blocked vent or prolonged downdraft the limit switch will open and cause the burner to shut off The pilot flame should be steady not lift...

Page 8: ...D CAREFULLY THEY WILL STAND UP INDEFINITELY TO EX TREMETEMPERATURES HOWEVER THEY AREVERYFRAGILEANDARESUSCEPTIBLE TO CRUSHING AND OR BREAKAGE IF HANDLED ROUGHLY Figure 14 GHC GRD 6500 LOG PLACEMENT A B...

Page 9: ...e for refer ence purposes only This information is also provided on schematics attached directly to the appliance on a pullout panel located within the control compartment CAUTION LABEL ALL WIRES PRIO...

Page 10: ...e safety information above on this page If you do not smell gas go to the next step 7 Push in gas control knob slightly and turn counterclockwise to PILOT 8 Push in control knob all the way and hold i...

Page 11: ...ely call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS ELECTRONIC 1 For com...

Page 12: ...ement on generator Be sure wire connections from generator at gas valve terminals are tight and generator is fully inserted into the pilot bracket One of the wall switch wires may be grounded Remove w...

Page 13: ...niter is sparking at the pilot assembly when the ON OFF switch is activated If not undertake the following steps With ON OFF switch OFF remove wire at TR terminal at the ignition control module Discon...

Page 14: ...ed wall switch Horizontal Trim Installation There are two 2 optional horizontal trim kits Models 41HTK PB 41HTK SPB available for use with the GHC Series appliance The 41 HTK SPB kit s trim is solid p...

Page 15: ...M 3 1 1 1 0 6 3 M 3 1 1 e t f e L p o T g o L 1 0 2 3 M 3 1 1 1 0 2 3 M 3 1 1 f t h g i R p o T g o L 1 0 3 3 M 3 1 1 1 0 3 3 M 3 1 1 8 8 3 K S D F B S t i K p o t S r o o D 2 4 6 8 3 0 1 2 4 6 8 3 0...

Page 16: ...18 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE REPLACEMENT PARTS MILLIVOLT 10 6 22 24 26 21 20 25 23 2 1 1 3 8 5 4 9 GRD 6500 GHC 6500 26 25 11 12 12 7b 7e 7a 7d 7f 7c...

Page 17: ...d n a l a r u t a N 0 0 5 6 D R G e n a p o r P d n a l a r u t a N o N t r a P y t Q o N t r a P y t Q 1 k c a l B r e v u o L r a B B 7 1 9 6 9 B L 5 2 p o T r a B B 6 0 9 6 9 B L 1 3 r e w o L r e...

Page 18: ...ke changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information 1110 We...

Reviews: