NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

NOTE:

  The minimum vertical rise (exhaust vent) is 10 feet (3.1 M) and 

the maximum vertical rise is 35 feet (10.7 M). These dimensions are 

measured from the starting collars of the unit to the end of the vent pipe.

The fireplace and fireplace chimney must be clean and in good working 

order and constructed of non-combustible materials. Inspect chimney 

cleanouts for proper fit and seal.

Make sure that both liners will pass through existing damper area. 

Remove or lock damper to allow the passage of the flexible liners. If 

the damper will not allow the passage of both liners, DO NOT PROCEED 

FURTHER.  (If fireplace is masonry) Consult a local mason for removal 

of the damper without risk of structural damage or leakage (if the fire-

place is factory built) The appliance may NOT be installed into the fireplace.

        

WARNING

Direct-Vent Fireplace Insert Vent Requirements - Use liner 

listed to UL181 (Factory-made Air Ducts And Air Connec-

tors) or UL1777 (Chimney Liners) for the AIR INTAKE.  Use 

liner listed to UL1777 ONLY for the EXHAUST.

Do not substitute the heat-rated flex liner (UL1777) for 

the exhaust with any other type liner or a fire may result 

causing property damage, personal injury or loss of life.

Vertical Venting

The vent pipes must be connected to the proper collars on the unit and 

the exhaust vent pipe must be connected to the termination cap or the 

unit will not operate. 

The combustion air intake pipe can be connected to the termination cap 

(see 

Figure 7b

)

 or it can terminate inside the chimney 

(see 

Figure 7a

)

.  

If combustion air intake pipe is terminated inside the chimney and not 

connected to the actual termination cap the bottom opening of the chim-

ney (chimney throat) must be sealed around the vent pipes.  Use a non 

combustible seal-off plate (i.e. 22 gage sheet steel) or unfaced fiberglass 

insulation (8 lb per square foot density minimum) to seal around the vent 

pipes.  Whichever “seal off” method is used must effectively seal the area 

to prevent room air passage to the chimney of the fireplace.  The insulation 

may give off an odor during the first hour of operation.

Air Inlet Liner (for combustion air) When 

terminating the air inlet liner at this point, a 

positive flue connection is required (to ensure 

combustion air is drawn down the chimney 

only).

Exhaust 3" (75mm) UL 

1777. A full length liner 

is required from the 

exhaust outlet on appli-

ance to center collar of 

termination cap.

Positive Flue Con-

nection (sealing 

fireplace throat 

using a noncombus-

tible seal-off plate 

or insulation).

The outside air inlet does not 

require a full reline (if intake 

liner is terminated in chimney 

and a positive flue connection 

is achieved as specified).

Air Inlet

Exhaust

Air Inlet

Existing Fireplace Flue

(chimney)

Masonry and Factory Built Fireplaces

Figure 7a - Terminating Air Inlet in Chimney 

NOTE: Terminating the air intake liner as shown here may not be al-

lowed by some local codes.  Check with the authority having jurisdiction 

for your area.

Vertical Cap

Termination 

Connector

Exhaust

Intake

Combustion Air Intake

The existing fireplace chimneys 

may take various contours 

which the flexible liners will 

accommodate. However, keep 

the flexible liner as STRAIGHT 

as possible, avoid unnecessary 

bending.

Liner Requirements:

Vertical Height Min. = 10 ft. (3.1 M)

Vertical height Max. = 35 ft. (10.7 M)

Note: Measured from flue collar on 

unit to the end of the vent pipe or liner

Use 3" (76 mm) diameter listed gas 

vent liner (UL1777 ONLY) for the 

EXHAUST

Use 3" (76 mm) diameter listed 

liner (UL 181 or UL1777) for the 

AIR INTAKE.

The flexible vent pipe 

must NOT be allowed to 

sag behind  insert or in 

fireplace flue.

Figure 7b

Summary of Contents for DRI3030TENC

Page 1: ...cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure...

Page 2: ...ADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre...

Page 3: ...o Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio Mantenga la ropa mobiliario gasolina y otros l quidos inflamable...

Page 4: ...eplace Dimensions 13 Clearances to Combustibles 14 Insert Leveling 14 Fan Control Module Switch 15 USING THIS MANUAL Please read and carefully follow all of the instructions found in this manual Pleas...

Page 5: ...avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po le installez une barri re de s curit cett...

Page 6: ...rcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor de control en el panel de control del artefacto verifique que el interruptor opera el artefacto encendi...

Page 7: ...eil Figure A Choisissezlalanguequiestprincipalementparl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 2 Rep rezlat l commandeetnettoyez lasoigneuse ment pour liminer...

Page 8: ...eart or lung disease or anemia those under the influence of alcohol and those at high altitudes Turn off gas and electrical power to the appliance and allow it to cool before cleaning or servicing the...

Page 9: ...ver use solid fuels such as wood paper cardboard coal or any flammable liquids etc in this appliance Plated surfaces must be cleaned with glass cleaner and a clean soft cloth before firing the first t...

Page 10: ...ral gas or propane Is NOT for use with solid fuels Is approved for sitting rooms and or bedrooms This appliance is suitable for installation into masonry or factory built fireplaces Fireplace Requirem...

Page 11: ...a nationally recognized testing and certification laboratory to ANSI American National Standard Institute gas appliance safety standards This appliance has been tested and certified to ANSI Z21 88 CSA...

Page 12: ...sion kit see Page 33 for ordering information This appliance comes from the factory equipped to burn natural gas at a specified elevation Only IHP conversion kits can be used to convert from NG to LP...

Page 13: ...A 31 1 2 800mm Front Opening Width B 19 1 2 495mm Height C 18 457mm Rear Width D 16 406mm Fireplace Depth Top View Left Side View Right Side View Front View A B C D Figure 3 Minimum Fireplace Cavity...

Page 14: ...ve the leg to the desired height and then tighten the screws Repeat these steps for each adjusting leg Facing and Mantel Clearances See Figure 4 CLEARANCES TO COMBUSTIBLES DRI3030TENC Facing and Mante...

Page 15: ...The vent should terminatewithalisteddirect ventterminationcap Thechimneyshouldbe sealed around the cap to prevent air and rain from entering the chimney Adhere to the vent manufacturer s instructions...

Page 16: ...e sealed around the vent pipes Use a non combustible seal off plate i e 22 gage sheet steel or unfaced fiberglass insulation 8 lb per square foot density minimum to seal around the vent pipes Whicheve...

Page 17: ...moyen d isolant incombustible une fois la conduite de gaz en place The installer must mechanically attach the marking supplied with the gas fireplace insert to the inside of the firebox of the firepla...

Page 18: ...rackets from the firebox using a 5 32 allen wrench seeFigure11 Retainthescrewsforstep4 anddiscardthebrackets as they will not be needed 3 Install the rear liner panel by inserting the tabs on the bott...

Page 19: ...ound panels so the edge of the surround panel fits just behind the rounded edge of the trim 8 Install three spring clips found in parts bag in firebox in each piece of trim by inserting them between t...

Page 20: ...d check the pressure Again close the tap gently but securely after completing the check Check the taps for gas leaks with a gas leak test solution retighten if necessary If the pressure is not suffici...

Page 21: ...or firebox panels If soot begins to form after burning the air shutter should be opened gradually until the sooting condition stops Gas quality and gas pressure may vary which can affect the burning c...

Page 22: ...e and is properly sealed Operating Instructions See Page 36 for operating instructions IMPORTANTNOTE Whenopeningthelowerdoorontheface while the insert is burning pull at the far left or far right vent...

Page 23: ...e that it is ready to synchronize with the Remote transmitter Install 3 AAA type batteries in the Remote transmitter battery bay located on the base of the Remote With the batteries already installed...

Page 24: ...e flame is turned off The Up Arrow Key will increase the flame height each time it is pressed If the Up Arrow Key is pressed while the system is on but the flame is off the flame will come on in the h...

Page 25: ...a yellow orange color Adjusting the appliance to cause the flames to turn orange sooner may result in poor combustion sooting and a hazardous situation See Figure 26 showing proper flame appearance W...

Page 26: ...TURE N C NORMALLY CLOSED N O NORMALLY OPEN FEMALE DISCONNECT MALE DISCONNECT STUD CONNECTION REMOTE RECEIVER PILOT ON AUTO SWITCH FAN CONTROL MODULE POWER ADAPTOR BOX 6 WHT 5 BLUE 11 YLW 10 ORG 13 BLK...

Page 27: ...flow of ventilation air or use vents other than those approved for use with this appliance o Check that the chimney and its outlet are open and free of soot block age or debris The venting system sho...

Page 28: ...Code Part 1 CSA C22 1 latest edition See Operating Options for burner ON OFF switch information Glass Door Cleaning and Maintenance Cleaning Do not remove or clean the glass door when hot When cool t...

Page 29: ...and lifting up slightly and then out away from the unit 3 Lay the facade face down on a soft surface that will not scratch the paint 4 Using a 3 8 socket remove the six nuts holding the left 1 and rig...

Page 30: ...reaching the appliance Loose wires to the valve or ignition module Pilot flame is not engulf ing the sensor Obstructed vent system Check the gas supply and gas shutoff valves Checkcontrolcompartmentfo...

Page 31: ...n Burner 36 NG 32 000 BTU 29 H5964 Orifice Main Burner 53 LP 27 000 BTU 31 H8491 Pilot Assembly Convertible NG or LP 32 H8509 Gas Control Valve Auto Hi Lo Regulator NG if LP also requires H8858 LP Reg...

Page 32: ...E DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE 38 Facade REPLACEMENT PARTS DRI3030TENC 14 36 25 33 34 21 22 23 13 31 29 32 1 10 9 17 8 16 7 6 15 5 4 37 2 26 27 11 31 29 32 1 10 9 8 17 2 11 27 26 4 5 36 15...

Page 33: ...Reflective Black Porcelain Panel Kit required accessory Cat No Model Description H8855 RDV BLK PCLPNL Black Porcelain Panels Black Porcelain Surround Trim Kits Cat No Model Description H5143 GFT2941...

Page 34: ...RATING 120 VAC 60 HZ LESS THAN 2 AMPS CHIMNEY USE 3 76 MM GAS VENT FLEX CHIMNEY LINER LISTED TO UL 1777 OR ULC S635 THIS APPLIANCE MUST BE PROPERLY CONNECTED TO A VENTING SYSTEM IN ACCORDANCE WITH THE...

Page 35: ...e appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch...

Page 36: ...36 NOTES...

Page 37: ...or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damage...

Page 38: ...e recommend that you record the following important information about your appliance Please contact your IHP dealer for any questions or concerns REPLACEMENT PARTS See Page 31 for a complete replaceme...

Reviews: