General Information
900285-00 05/2015
Innovative Hearth Products
Superior
TM
DRT/C3000 Series Direct-Vent Gas Fireplaces
9
BTU Input
Table 1: Input Rate (BTU/HR), Gas Valves
Models
Natural Gas
Propane Gas
High Rate
Low Rate
High Rate
Low Rate
33” Models
14,000
10,500
13,000
9,500
35” Models
16,000
11,000
15,000
11,000
40” Models
20,000
14,000
19,000
14,000†
45” Models
21,500
13,500
21,500
13,500
† 12,000 in Superior Contemporary Models
Table 2: Thermal Efficiency (%)
Model
Millivolt
Electronic
AFUE *
P4 **
AFUE *
P4 **
33” Models
65
60
65
63
35” Models
66
61
66
63
40” Models
66
61
66
63
45” Models
67
61
67
63
* AFUE is a measurement of the US Department of Energy, ** P4 (EnerGuide) is a measurement of the Canadian Office of Energy Efficiency.
Efficiencies are based on Normal input operation.
Gas Pressure
Table 3: Inlet Gas Supply Pressure
Fuel
Minimum
Maximum
Natural Gas
5” WC / (1.25 kPa)
10.5” WC / (2.61 kPa)
Propane
11.0” WC / (2.74 kPa)
13.0” WC / (3.23 kPa)
Table 4: Manifold Gas Supply Pressure
Fuel
Traditional Model Pressure
Contemporary Model Pressure
Natural Gas
3.5” WC / (0.87 kPa)
3.8” WC/ (0.95 kPa)
Propane
10.0” WC / (2.49 kPa)
9.8” WC (2.44 kPa)
Test gauge connections are provided on the front of the millivolt and electronic gas control valve (identified IN for the
inlet and OUT for the manifold side). The control valves have a 3/8” (10 mm) NPT thread inlet and outlet side of the
valve (
Figure 1
and
Figure 2
).
Figure 1: Millivolt Gas Valve
Figure 2: Electronic Gas Valves
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step down
regulators to reduce the pressure to safe levels.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures
in excess of
1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during
any pressure testing of the gas supply piping system at test pressures
equal to or less than
1/2 psi (3.5 kPa).