background image

11

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Chimney Connector Systems and Clearances 

from Combustible Walls for Residential Heat-

ing Appliances (NFPA 211) - 

Refer to 

Figure 9

System A.

 Minimum 3.5 in. (90 mm) thick brick masonry wall framed 

into combustible wall with a minimum of 12 in. (305 mm) brick sepa-

ration from clay liner to combustibles. Fireclay liner (ASTM C 315, 

Standard Specification for Clay Flue Linings, or equivalent), minimum 

5/8 in. (16 mm) wall thickness, shall run from outer surface of brick 

wall to, but not beyond, the inner surface of chimney flue liner and 

shall be firmly cemented in place.
Clearance: 12 in. (305 mm)

System B

. Solid-insulated, listed factory-built chimney length of the 

same inside diameter as the chimney connector and having 1 in. (25.4 

mm) or more of insulation with a minimum 9 in. (229 mm) air space 

between the outer wall of the chimney length and combustibles.
The inner end of the chimney length shall be flush with the inside of 

the masonry chimney flue and shall be sealed to the flue and to the 

brick masonry penetration with non-water-soluble refractory cement. 

Supports shall be securely fastened to wall surfaces on all sides.
Fasteners between supports and the chimney length shall not penetrate 

the chimney liner.
Clearance: 9 in. (229 mm)

System C.

 Sheet steel chimney connector, minimum 24 gage [0.024 

in. (0.61 mm)] in thickness, with a ventilated thimble, minimum 24 

gage [0.024 in. (0.61 mm)] in thickness, having two 1 in. (25.4 mm) 

air channels, separated from combustibles by a minimum of 6 in. (152 

mm) of glass fiber insulation. Opening shall be covered, and thimble 

supported with a sheet steel support, minimum 24 gage [0.024 in. 

(0.61 mm)] in thickness.
Supports shall be securely fastened to wall surfaces on all sides and 

shall be sized to fit and hold chimney section. Fasteners used to secure 

chimney section shall not penetrate chimney flue liner.
Clearance: 6 in. (152 mm)  

System D.

 Solid-insulated, listed factory-built chimney length with an 

inside diameter 2 in. (51 mm) larger than the chimney connector and 

having 1 in. (25.4 mm) or more of insulation, serving as a pass-through 

for a single wall sheet steel chimney connector of minimum 24 gage 

[0.024 in. (0.61 mm)] thickness, with a minimum 2 in. (51 mm) air 

space between the  outer wall of chimney section and combustibles. 

Minimum length of chimney section shall be 12 in. (305 mm). Chimney 

section concentric with and spaced 1 in. (25.4 mm) away from con-

nector by means of sheet steel support plates on both ends of chimney 

section. Opening shall be covered, and chimney section supported on 

both sides with sheet steel supports of minimum 24 gage [0.024 in. 

(0.61 mm)] thickness.
Supports shall be securely fastened to wall surfaces on all sides and 

shall be sized to fit and hold chimney section. Fasteners used to secure 

chimney section shall not penetrate chimney flue liner.
Clearance: 2 in. (51 mm)

Additional requirements:

1. Insulation material used as part of wall pass-through system shall be of 

noncombustible material and shall have a thermal conductivity of 1.0 

Btu-in./hr-ft

2

 - ºF (4.88 kg-cal/hr-m

2

 - ºC) or less.

2. All clearances and thicknesses are minimums; larger clearances and 

thicknesses shall be permitted.

3. Any material used to close up an opening for the connector shall be of 

noncombustible material.

4. A connector to a masonry chimney, except for System B, shall extend 

in one continuous piece through the wall pass-through system and the 

chimney wall to the inner face of the flue liner, but not beyond.

Factory Built 

Chimney Length 

Air Space – 9 in. 

(228.6mm) Min. 

Chimney Length 

Flush with 

Inside of Flue 

Min. Clearance 

9 in. (229mm) 

Chimney 

Connector 

Use Chimney 

Mfrs. Parts to 

Attach 

Connector 

Solid-Insulated 

Listed Factory-

Built Chimney 

Length

Sheet Steel Supports

Sheet Steel Supports

Sheet Steel Supports

Minimum Chimney Clearance from Masonry to Sheet Steel 

Supports & Combustibles – 2 in. (51mm) 

Nonsoluble 

Refractory  

Cement

Minimum chimney clearance to sheet

steel supportrs and combustibles

2 in. (51mm)

Chimney 

Connector 

2 Air Channels, Each 1 

in. (25.4 mm) 

2 Ventilated Air 

Channels, Each 

1 in. (25.4 mm) 

Construction of 

Sheet Steel 

Minimum chimney clearance to sheet steel 

supports and combustibles 2 in. (51mm) 

Sheet Steel 

Supports 

Chimney 

Connector 

Chimney 

Section

Air Space – 2 in. 

(51mm) Min. 

Chimney connector  

Chimney length

1 in. (25.4 mm) 

air space to 

        chimney length

Min. Clearance  

2 in. (51 mm) 

Minimum

12 in. (305mm)

to combustibles

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Minimum chimney clearance to brick

and combustibles 2 in. (51mm)

Minimum clearance

12 in. (305mm)

of brick

Chimney

Chimney

flue

Chimney

flue

Chimney

flue

connector

Fire clay

liner

Figure 9 - 

Chimney Connector Systems and Clearances from Combustible Walls

System A

System B

System C

System D

Summary of Contents for WXS2016

Page 1: ...aire la demande Num ro de la pi ce 900917 01 This appliance must be properly installed and operated in order to prevent the pos sibility of a house fire Please read this entire installation and operat...

Page 2: ...ation 3 Testing Information 4 Draft Requirements 4 Selecting the Proper Venting System 4 Negative Pressure Warning 5 Clearances to Combustibles 6 7 Floor Protection 6 Chimney and Connector 6 Component...

Page 3: ...h your local building department for requirements in your area 13 Inspectyourchimneyatleastonceamonthduringtheburn ing season to check for soot and creosote accumulations Any accumulations over 1 8 th...

Page 4: ...cleaning Overfiring of a stove is a condition where excessive temperatures are reached beyond the design capabilities of the appliance The damage that occurs from overfiring is not covered under the m...

Page 5: ...d by many common household appliances which exhaust air from the home such as a furnace heat pump air conditioner clothes dryer exhaust fans fireplaces and other fuel burning appliances Also the combu...

Page 6: ...ed for mobile homes but connector pipe may be double wall single wall or single wall with shield as listed above This appliance may be vented into a code approved masonry chimney with flue liner WARNI...

Page 7: ...19 1 2 9 5 8 8 6 15 37 5 8 46 3 4 34 7 8 16 0 84 57 1 2 305 232 495 245 200 152 381 956 1188 886 406 0 2134 1461 CANADA inches millimeters PIPE INSTALLATION A 3 B 1 C 3 D 1 E 8 F 1 G 3 H 2 I 6 J 2 K 7...

Page 8: ...ions only 1 4 Diagrams illustrations and photographs are not to scale consult installa tion instructions Product designs materials dimensions specifications colors and prices are subject to change or...

Page 9: ...all metal chimney at least 6 in diameter or to a masonry chimney with a flue passage of at least 48 square inches It is required that a chimney connector pipe not extend further than the inner wall of...

Page 10: ...______________________________________ ______________________________________________________ ______________________________________________________ ___________________________________________________...

Page 11: ...n shall be 12 in 305 mm Chimney section concentric with and spaced 1 in 25 4 mm away from con nector by means of sheet steel support plates on both ends of chimney section Opening shall be covered and...

Page 12: ...register must not be installed more than ten 10 feet 3050 mm above the base of the stove c The fresh air must come from outside the house The air intake must not draw air from the attic from the base...

Page 13: ...ll install the baffle blanket It will be installed with the 11 dimension from the front to rear of the firebox Install by lifting it into place between the front and rear baffle Place the blanket over...

Page 14: ...5 F 10 F 9 F 8 A 4 F 6 D 1 F 2 F 3 D 7 F 11F 12A 13F 14F 15G 16E Figure 15 Side Cut A Way View of Firebox Baffle Blanket Front Baffle Board Rear Baffle Board Firebox Brick Baffle Insulation Parts Figu...

Page 15: ...able from all IHP dealers Opening Door Lift handle and pull to open door Closing Door Hold handle lifted swing door closed then push handle down to engage latch Handle Door OPERATING HINTS 1 Burn only...

Page 16: ...ing appliance it is important to become familiar with how the damper control affects heat output and the overall temperature of the appliance A stove thermom eter can be a helpful tool to help ensure...

Page 17: ...chieve heat output rates that exceed heater design specifica tions can result in permanent damage to the heater Figure 22 Figure 23 OK 4 4 8 Standard Cord of Wood What does Well Seasoned mean When a t...

Page 18: ...need to have sufficient temperatures inside the firebox for thorough combustion The best method for determining if you have sufficient temperatures is to watch the brick lining in your firebox When yo...

Page 19: ...he stove is burned with the blower opening unobstructed Figure 24 The optional blower is controlled by a Dial a Temp see Figure 24 It contains an On Off line switch with variable speed control from lo...

Page 20: ...on ing are similar to the flu with headaches dizziness and or nausea If you have these signs obtain fresh air immediately Some people are more affected by carbon monoxide than others including pregnan...

Page 21: ...a chimney fire THIS WOOD HEATER NEEDS PERIODIC INSPECTION AND REPAIR FOR PROPER OPERATION IT IS AGAINST FEDERAL REGULATIONS TO OPERATE THIS WOOD HEATER IN A MANNER INCONSISTENT WITH OPERATING INSTRUC...

Page 22: ...ior to cleaning glass A commercial glass cleaner designed for stoves is recommended Do not use abrasivecleaners Donotcleanwithanymaterials which may scratch or otherwise damage the glass Scratches on...

Page 23: ...2 3 See Poor Draft section above and Cleaning Glass on Pages 4 and 22 SMOKES WHEN 1 If smoke is entering the room check to make sure your baffle boards are properly installed DOOR IS OPEN 2 Check the...

Page 24: ...Draft Rod Knob 9 F4088 Ash Lip Kit includes hardware 1 4 5 11 6 3 12 13 14 15 16 16 16 16 17 16 21 19 20 16 17 16 19 16 16 17 18 16 22 7 10 9 8 2 Item Cat Description 10 F4101 Pedestal Assembly 11 H5...

Page 25: ...ND UZI UZI Outside Air Ducting Kit includes 4 insulated flex x 10 long AND F4062 OUTAIRKIT ES Outside Air Panel and Air Channel Kit includes rear pedestal panel and side and front air channels MISC H8...

Page 26: ...anufactured By INNOVATIVE HEARTH PRODUCTS 1502 14th St NW Auburn WA 98001 USA PREVENT HOUSE FIRES Installanduseonlyinaccordancewithmanufac turer sinstallationandoperatinginstructionsand your local bui...

Page 27: ...cessive temperatures and may cause damage to the Product or may cause it to function improperly IHP stoves and inserts are approved for burning dry seasoned wood only c damages caused by failing to pr...

Page 28: ...give the following information 1 The model number of the appliance 2 The Serial Number of the appliance 3 The part number 4 The description of the part 5 The quantity required 6 The installation date...

Reviews: