FIREPLACE INSTALLATION 

Continued

HEARTH EXTENSION

A hearth extension projecting a minimum of 20" in front of and a 

minimum of 12" beyond each side of fireplace opening is required 

to protect combustible floor construction in front of fireplace. Fabri-

cate a hearth extension using a material which meets the following 

specifications: a layer of noncombustible, inorganic material having a 

thermal conductivity of k=0.84 BTU IN/FT, HR. F (or less) at 1" thick. 

For example, if the material selected has a k factor of 0.25, such as 

glass fiber, the following formula would apply:
 

0.25 x 1.0" = 0.30" thickness required

 0.84
Thermal conductivity "k" of materials can be obtained from manufac-

turer or supplier of noncombustible material. If hearth extension is 

to be covered, use noncombustible material such as tile, slate, brick, 

concrete, metal, glass, marble, stone, etc. Provide a means to prevent 

hearth extension from shifting and seal gap between fireplace frame 

and hearth extension with a noncombustible material (see Figure 6). 

 WARNING: Hearth extension is to be installed only 

as shown in Figure 6.

Figure 6 - Hearth Extension

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front Raised 

Hearth

Fireplace Front Elevated

Ember Protector

Ember Protector

Seal Gap

Hearth 

Extension

MANTELS

A mantel may be installed if desired (see Figure 7). Woodwork such as 

wood trims, mantels or any other combustible material projecting from 

front face must not be placed within 12" (36" Models) or 18" (42/50" 

Models) of fireplace opening. Combustible materials above 12" (36" 

Models) or 18" (42/50" Models) and projecting more than 1 

1

/

2

" from 

fireplace must not be placed less than 15" (36" Models) or 21" (42/50" 

Models) from the top opening of the fireplace (NFPA 211, Section - 

Clearance from Combustible Material).
Mantels or any other combustible material also may come up to side 

edge of black metal face of fireplace as long as projections from front 

face fall within limit shown in Figure 7.

Figure 7 - Mantel Clearances to Combustible Material

12 

1

/

4

(312 mm)Ref.

6" (153 mm)

Ref.

15" (381 mm) Min.

(36" Models)

21" (534 mm) Min.

(42/50" Models)

12" (305 mm) Min.

(36" Models)

18" (458 mm) Min.

(42/50" Models)

1

1

/

2

" (39 mm) 

Max.

3" (77 mm)

Nom.

33°

Combustible 

Material

Safe Zone for 

Projection of 

Combustible 

Materials

Fireplace Opening

Upper Section 

of Fireplace

FIREBOX

SAFE ZONE

Top View of Fireplace

1

/

2

" (115 mm)

3

/

4

" (197 mm)

36" Models

11 

1

/

2

" (293 mm)

(42/50" Models)

Min. to 

Perpendicular 

Side Wall 

12" (305 mm)

36" Models

18" (458 mm) 

42/50" Models

33°

Combustible 

Material Must 

Not Overlap 

Front Face

3" (77 mm) Max.

Summary of Contents for WRT4536

Page 1: ...84 standards or for use with a vent free gas log heater approved to ANSI Z21 11 2 standard FOR CANADA The authority having jurisdiction such asthemunicipalbuildingdepartment firedepartment etc should...

Page 2: ...any other appliance Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies Do not place clothing or other flammable materials on or near the app...

Page 3: ...thazard IMPORTANT See appendix A page 27 for additional information regarding draft requirements smoking causes and troubleshooting WARNING BURNINGIMPROPERFUEL I E CHAR COAL CAN RESULT IN CARBON MONOX...

Page 4: ...12 305 mm EACH SIDE MINIMUM 12 305 mm TOPERPENDICULAR SIDEWALL COMBUSTIBLE WALL BOARD NO COMBUSTIBLE MATERIAL ON FACE HEARTH EXTENSION 60 X 20 1524 mm x 508 mm OUTSIDE AIR 29 737 mm 22 1 2 572 mm 14...

Page 5: ...ACH SIDE MINIMUM 18 458 mm TOPERPENDICULAR SIDEWALL COMBUSTIBLE WALL BOARD NO COMBUSTIBLE MATERIAL ON FACE HEARTH EXTENSION 66 X 20 1677 mm x 508 mm OUTSIDE AIR 22 3 4 578 mm 30 1 2 775 mm 15 3 4 400...

Page 6: ...TERIAL ON FACE HEARTH EXTENSION 74 X 20 1880 mm x 508 mm OUTSIDE AIR 50 HEARTH 33 1 8 842 mm 23 1 4 591 mm 50 1270 mm 38 1 2 978 mm 28 1 2 724 mm 17 5 8 448 mm 4 3 8 112 mm 19 1 4 489 mm 24 610 mm 1 2...

Page 7: ...ight of termination assembly at level of the flue gas outlet see Figure 15 page 12 FRAMING 1 Frame opening for fireplace using dimensions shown in Figures 4 and 5 2 If fireplace is to be installed dir...

Page 8: ...Protector Fireplace Front Raised Hearth Fireplace Front Elevated Ember Protector Ember Protector Seal Gap Hearth Extension MANTELS A mantel may be installed if desired see Figure 7 Woodwork such as w...

Page 9: ...endently as the chimney is installed When connect ing chimney directly to the fireplace the inner flue pipe section must be installed first with the lanced side up The outer pipe section can then be i...

Page 10: ...t be secured with two screws on the outer pipe only see Figure 10 Do not penetrate the inner stainless Figure 11 Ceiling Support Pipe 12S 12DM CAUTION THE STRUCTURAL INTEGRITY OF THE MANUFACTUREDHOMEF...

Page 11: ...e FST10 is required to avoid intrusion by insu lation and recommended to negotiate a joist Firestop Thimble FST10 Figure 14a Firestop Thimble PENETRATING ROOF To maintain a 1 36 Models or 2 42 50 Mode...

Page 12: ...used between the flashing and the roof The flashing must be secured to the roof using 8 x 3 4 screws and then sealed with roof coating to prevent leakage through the screw holes A roof coating must al...

Page 13: ...termination to another We suggest that terminations be separated at least 24 center to center and stacked at a vertical height difference of 18 see Figure 19 Note If a decorative shroud is to be inst...

Page 14: ...nd place flash ing over chase 4 Secure flashing through sides with 8 penny nails or sheet rock screws 5 Place galvanized sleeve through hole in flashing and around last section of chimney see Figure 2...

Page 15: ...lvanized steel over chimney outlet see Figure 29 6 Attach storm collar where chimney pierces opening in flash ing Caulk where storm collar touches outer chimney pipe see Figure 29 NONCHASE INSTALLATIO...

Page 16: ...ermine which is which match up the pattern on the rear panel with the left and right sides before installing the rear panel Make sure panel is center before continuing 5 Install the right and left ref...

Page 17: ...gure 34 Gas Line Access Side Firebrick Finished Side Brick with Access Hole Outside of Fireplace Gas Line Conduit Insulation Gas Conduit Cover 1 2 Dowel Remove Knockout Gas line hook up should be done...

Page 18: ...doors completely folded insert bottom pivot pin into pivot hole located near bottom corner of front face opening and swing door to vertical position making sure top pins slide into door track Door is...

Page 19: ...ustion air and maintain safe temperatures in firebox IMPORTANT The glass must be allowed to warm slowly and evenly The tempered glass will withstand a gradual temperature rise to 550 F which is more t...

Page 20: ...laces us com 126601 01_J 20 PARTS 1 21 20 5 6 7 10 9 11 12 13 16 17 15 14 8 24 23 3 25 18 2 22 19 4 MODEL CATALOG NO WRT4536WS F0626 WRT4536WH F0627 WRT4542WS F0628 WRT4542WH F0629 WRT4550WS F0630 WRT...

Page 21: ...Pan 1 8 Top Insulation 1 9 Fireplace Top Assembly 36 1 Fireplace Top Assembly 42 1 Fireplace Top Assembly 50 1 10 J6997 Standoff 4 11 Fireplace Surround Assembly 1 12 J4362 Clearance Spacer 6 13 J532...

Page 22: ...the fireplace is placed in a permanent location WARNING LIFTING HAZARD SINGLE PERSON LIFT COULD CAUSE INJURY USE ASSISTANCE WHEN MOVING OR LIFTING PARTS MODEL CATALOG NO WRT4536WS F0626 WRT4536WH F062...

Page 23: ...ite 1 7 J4466 Retainer Assy Ref Corner 2 1 F3278 45 series White Stacked Refractory Set 50 1 2 Refractory Hearth 50 Stk White 1 3 Refractory Rt 50 Stk White 1 4 Refractory Lt 50 Stk White 1 5 Refracto...

Page 24: ...tion Hi Temp Double Wall Pipe Snap Lock F0954 18 12HT 18 Section Hi Temp Double Wall Pipe Snap Lock F0955 24 12HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0956 36 12HT 36 Section Hi Temp Double...

Page 25: ...and combustibles must not touch pipe Consult manual for clearance requirements Ensure proper connection WARNING HOT Fire Risk Insulation and combustibles must not touch pipe Consult manual for cleara...

Page 26: ...s fireplace may be used if installed in accordance with the instructions by its manufacturer A locally fabricated shroud may be used with IHP Shroud Leg Spacer Kit SLK in accor dance with instructions...

Page 27: ...nditions inadequate chimney heights adversewindconditionsand orunusualenvironmental factors or conditions beyond our control take into account all variables within the installation and install the app...

Page 28: ...ance The best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of...

Page 29: ...__________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 30: ...__________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 31: ...be subject to normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with a...

Page 32: ...6601 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult yo...

Reviews: