If possible, you should choose a location where 

the chimney will pass through the house without 

cutting floor or roof joists (see fireplace dimen-

sions 

Page 9).

Usually, no additional floor support is needed 

for the fireplace.  The adequacy of the floor 

can be checked by first estimating the weight 

of the fireplace system.  Weights are given 

on 

Page 22

.   Note the floor construction and 

consult your local building code to determine 

if additional support is needed. 

The WCT6820WS fireplace may be installed 

directly on the floor or on a raised base (for 

proper guidelines, refer to “Hearth Extension 

Requirements”) and a minimum of 6’8” (2 m) 

measured from the base of the appliance to the 

ceiling is required.

When selecting the location, the chimney outlet 

position and the direction of the wind are impor-

tant factor affecting the chimney performance. 

To allow a maximum draft and to reduce wind 

turbulence, the chimney must:

•  Penetrate the highest part of the roof.

•  Be installed as far as possible of roof offsets, 

trees or any other obstructions that may 

cause wind turbulence and back drafts in 

the chimney.

•  The least amount of offsets (elbows) pos-

sible. 

NOTE: A maximum of 2 offsets is 

allowed.

GLASS CARE

Glass Replacement

The glass used for the WCT6820WS fireplace 

is a high temperature ceramic glass (1,400° F / 

760° C).  If the glass breaks, it must be replaced 

with an identical ceramic glass. Tempered glass 

or ordinary glass will not withstand the high 

temperatures of the WCT6820WS fireplace.  

Replacement glass should be purchased from a 

IHP dealer (see “Replacement Parts”, 

Page 22)

.  

DO NOT OPERATE THE UNIT WITH CRACKED 

OR BROKEN GLASS. 

Glass Cleaning

The WCT6820WS fireplace is designed to keep 

the glass clean under normal operating condi-

tions. If the WCT6820WS fireplace is operated 

continuously with the combustion air controls 

closed, the glass will tend to get dirty unless 

the fuel, firebox and glass are maintained at 

hot temperatures (see “Refueling For Best 

Performance”).  To clean the glass, there are a 

number of specially designed cleaners.  Your IHP 

dealer can recommend a suitable cleaner which 

is available in your area.  Regular household 

glass cleaners will not clean creosote.  Do not 

use abrasives such as steel pads, steel wool 

or oven cleaner as they will scratch the glass.

DO NOT USE CHEMICAL GLASS CLEANERS 

ON PAINTED SURFACES AS IT MAY CAUSE 

THE PAINT TO PEEL.
CAUTION : DO NOT ALLOW WINDOW CLEANER 

TO GET IN CONTACT WITH DOOR GASKET OR 

PAINT ON FACADE OR DOOR.  ONCE CLOSED, 

CONTACT OF GLASS CLEANER WITH THE 

FIREPLACE FACADE CAN PROVOKE PAINT 

PEELING OFF.

Gasket

Length Dimensions

Part No.

Steel Door

Around 

Glass

69

(1753)

1 x 3/16

(25 x 4.8)

PR-SR1685D

On Door 

Frame

73

(1854)

5/8 dia.

(15.9)

PR-SR1823G 

Cast Door

Around 

Glass

69

(1753)

1 x 5/16

(25 x 4.8)

PR-SR1823H

On Door 

Frame

73

(1854)

5/8 dia.

(15.9)

PR-SR1823G 

 

        Inches (millimeters)

FIREPLACE INSTALLATION

Locating The WCT6820WS Fireplace

The best location to install your fireplace is 

determined by considering the location of 

windows, doors, and the traffic flow in the room 

where the fireplace is located, allowing space 

in front of the unit for the hearth extension and 

the mantel, and taking into consideration the 

location of the hot air ducts (optional), outside 

air kit and chimney.  

Gasket Replacement

Remove the door from the unit (see 

Page 7)

 

and lay it on a clean unabrasive surface. To 

replace the gasket, first remove all of the old 

gasket and gasket cement.  Make sure that the 

surface is totally clean before applying new 

cement (a high temperature silicone caulking 

rated at 500° F [260° C], is suitable) or adhesion 

problems may result.  Apply gasket cement to 

the gasket channel and install the new gasket.  

This replacement part is available from your IHP 

dealer in the following dimensions:

Marginal Location

Wind Direction

Location

Not

Recommended

Outside Air Intake

Facing the Wind

Location

Not 

Recommended

Location Recommended

Figure 30

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

18

*

Available from Security Chimneys™ 

Summary of Contents for WCT6820

Page 1: ...of glass doors Install this fireplace in a square and plumb condition using shims as necessary at sides and or bottom Install the fireplace only as described in these instructions This installation ma...

Page 2: ...s ensure that the air inlet to the fireplace is free from debris and any other obstructions that can block the entrance of air WARNING Neither the manufacturer nor the seller warrants smoke free opera...

Page 3: ...del ASHT S 2100 HT6000 HT6103 or AC manufactured by Security Chimneys Inter national only including Chimney lengths Elbows where necessary Associated components as per these installation instructions...

Page 4: ...ing 10 to 20 minutes after reloading depending on the heat and on the moisture content of the wood Onceyouhavereachedthedesiredtemperature the air boost can be closed and the primary air set to a medi...

Page 5: ...e Monitor Recommended Carbon Monoxide Poisoning Early signs of carbonmonoxidepoisoningaresimilartotheflu withheadaches dizzinessand ornausea Ifyou have these signs obtain fresh air immediately Somepeo...

Page 6: ...o 11 20 NOTE The use of a firewood moisture meter is rec ommended to ensure the firewood contains less than 20 moisture Seasoning Guide Softwoods 6 months to 18 months Hardwoods 12 months to 24 months...

Page 7: ...supplied will be necessary for this adjustment Checking Door Seal A one inch strip of paper may be used to perform a test of the integrity of the door seal Close the door on the paper in at least eigh...

Page 8: ...cover the entire width of the fireplace The combustible floor in front of the fireplace must be covered with a non combustible ma terial tile marble stone etc See Figure 7 Cold climate INSTALLATIONS...

Page 9: ...nstallation instructions Product designs materials dimensions specifications colors and prices are subject to change or discontinuance without notice Allframingdimensionscalculatedfor 1 2 dry wall at...

Page 10: ...tside Walls Of Chase Solid Continuous Surface Outside Base Insulation Thermal Barrier 8 Level 7 2 1 m Min 6 8 2 m Min 8 2 4 m Level 42 1067mm 2 x 3 Min 51mm x 76mm Rock Board or Other Noncombustible F...

Page 11: ...replace Blower The fireplace comes equipped with a heat acti vated blower It is located in the bottom of the fireplace towards the back It uses 120V and must be connected to the main electrical circui...

Page 12: ...diameter flexible pipe for the complete run up to thirty 30 feet and a 6 diameter pipe for a run of up to forty 40 feet The duct system must be installed respecting the following 1 Removetheplatesclo...

Page 13: ...11 When offsets are used the pipe may not penetrate a ceiling or floor unless it is running vertical no 30 offsets Outside Intake Screw Opening Facing Down Wall Aluminum Tape Plastic Cover Insulation...

Page 14: ...ofs place the flashing under the upper shingles and on top of the lower shingles Nail the flashing to the roof using roofing nails 6 Place the spacers and the storm collar over the flashing and tighte...

Page 15: ...a plumb bob to line up the center of the hole Cut a hole for the chimney in the ceiling floor Frame this hole as described previously refer to section Chimney Instal lation Instructions 5 From below...

Page 16: ...22 mm 6 1 8 156 mm 11 280 mm 14 1 8 359 mm 16 7 8 429 mm 18 7 16 468 mm 23 584 mm 26 3 16 665 mm B 27 11 16 703 mm 33 1 2 851 mm 50 7 8 1292 mm 62 1 2 1588 mm 72 5 8 1845 mm 78 7 16 1992 mm 95 3 4 243...

Page 17: ...bustible wall with the chimney at a 30 or 45 angle an angled firestop or wall radiation shield must be installed Only one is required NOTE 45 angle for Canada only RSMI45 In cold climate locations cli...

Page 18: ...are maintained at hot temperatures see Refueling For Best Performance To clean the glass there are a numberofspeciallydesignedcleaners YourIHP dealercanrecommendasuitablecleanerwhich is available in y...

Page 19: ...ns provided with the support CHIMNEY MODEL MAXIMUM HEIGHT OF SUPPORTED CHIMNEY Offset Support Roof Support ASHT HT6103 6 dia 28 feet 8 54 m 29 feet 8 84 m S 2100 HT6000 6 dia 18 feet 5 49 m 20 feet 6...

Page 20: ...cation Temporarily install the ASHT elbow on the top of the fireplace and using a level mark with an oval the location where the flue liner will enter the masonry chimney 2 In the middle of the oval d...

Page 21: ...bow 90 8 dia 7B26ZE90 H8948 Elbow 45 8 dia 7B26ZE45 H8949 Telescopic length 8 dia 15 to 26 7B26ZLA H8950 Adjustable length 8 dia 2 5 7B26ZL2A H8951 Length two 2 feet 8KL2 H8954 Length one 1 feet 8KL1...

Page 22: ...R2324 Log retainer bar PR SR2323 Door rod and lock PR SR2118 Steel door glass gasket PR SR1685D Cast iron door glass gasket PR SR1823H Steel and cast Iron door gasket PR SR1823G Touch up Paint Aerosol...

Page 23: ...ess Steel Chimney 6 I D and 8 O D Double Wall Stainl Steel Listed to CAN UCL S604 and UL 103HT Description Part Cat No Lengths and Misc Chimney Components 8 length 6 Dia 6L8 6L8 12 length 6 Dia 6L12 6...

Page 24: ...8 Length 6 Dia 6LL48 6LL48 Adjustable Length 7 to 11 6 Dia 6L7A 6L7A Split Base Tee 6 Dia 6LT 6LT Tee Cap 6 Dia 6TCS 6TCS Twist Lock Tee Cap 6 Dia 6LTC 6LTC Elbow 30 6 Dia 6LE30 6LE30 Elbow 45 6 Dia 6...

Page 25: ...ormal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with abnormal burning...

Page 26: ...ct your IHP dealer for any questions or concerns Replacement parts See Page 22 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered...

Reviews: