background image

15

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Installation Instructions

901140-00, 01/2021

Innovative Hearth Products
DRT63ST-B Power-Vent Direct-Vent Fireplaces

Proper Sizing of Gas Line

Properly size and route the gas supply line 

from the supply regulator to the area where the 

appliance is to be installed per requirements 

outlined in the National Fuel Gas Code, NFPA 

54 - latest edition (USA) or CAN/CGA-B149.1 

- latest edition (Canada). 

IMPORTANT: It is critical that a licensed 

installer perform this step strictly per 

NFPA.

Never use galvanized or plastic pipe.  Refer 

to 

Table 6

 for proper sizing of the gas sup-

ply line, if black iron pipe is being used. Gas 

lines must be routed, constructed and made 

of materials that are in strict accordance with 

local codes and regulations.   We recommend 

that a qualified individual such as a plumber or 

gas fitter be hired to correctly size and route 

the gas supply line to the appliance. Installing 

a gas supply line from the fuel supply to the 

appliance involves numerous considerations of 

materials, protection, sizing, locations, controls, 

pressure, sediment, and more. Certainly no one 

unfamiliar and unqualified should attempt sizing 

or installing gas piping.

NOTE:

•  All appliances are factory-equipped with 

a flexible gas line connector and 1/2 inch 

shutoff valve (see 

Figure 37

 on 

Page 26

)

.

• See 

Massachusetts Requirements

 on 

Page 

7

 for additional requirements for installations 

in the state of Massachusetts in the USA.

•  The gas supply line should not be connected 

to the appliance until 

Step 6

 (

Page 26

)

.

•  A pipe joint compound rated for gas should 

be used on the threaded joints.

 

Be very careful 

that the pipe compound does not get inside 

the pipe.

•  It is recommended to install a sediment trap 

in the supply line as close as possible to the 

appliance (see 

Figure 37

 on 

Page 26

)

.  

•  Check with local building official for local 

code requirements (i.e. are below grade 

penetrations of the gas line allowed?, etc).

Schedule  40, Black Iron Pipe

Inside Diameter (Inches)

Schedule  40 Pipe

Length (feet)

Natural

Gas

0-10

1/2

10-40

1/2

40-100

1/2

100-150

3/4

150-200

3/4

Table 6

Figure 14 - INDOOR /  OUTDOOR

Right Side Front Corner 

(Valve Side) of Fireplace Framing

19-1/2" 

(495 mm)

7”

(178 mm)

1-1/2”

(38 mm)

Figure 13 - INDOOR / INDOOR

7”

(178 mm)

Right Side Front Corner 

(Valve Side) of Fireplace Framing

19-1/2" 

(495 mm)

Right Side Front 

Corner Of Fire-

place Framing

Step 2. ROUTE GAS LINE

 NOTICE: For indoor/outdoor installations, 

the CONTROL SIDE of the fireplace must 

be installed on the INDOOR side.

Route a 1/2" (13 mm) gas line along the inside 

of the right side framing as shown in

 Figures 13 

and 14

.  Gas lines must be routed, constructed 

and made of materials that are in strict accor-

dance with local codes and regulations.

All appliances are factory-equipped with a 

flexible gas line connector and 1/2 inch shutoff 

valve

 (see Step 6 on Page 26).

The incoming gas line should be piped into 

the valve compartment and connected in one 

of the two methods as shown in 

Figure 37

  on  

Page  26

.

Step 3. INSTALL VENT SYSTEM

General Information

These instructions should be used as a guide-

line and do not supersede local codes in any 

way. Install venting according to local codes, 

these instructions, the current National Fuel 

Gas Code (ANSI-Z223.1) in the USA or the 

current standards of CAN/CGA-B149.1 and 

-B149.2 in Canada. 
These fireplaces are designed, tested and 

listed for operation and installation with, 

and only with, Secure Vent

®

  (SV4.5) Direct-

Vent System Components, manufactured by 

Security Chimneys International.  These ap-

proved vent system components are labeled 

for identification.  DO NOT use any other 

manufacturer's vent components with these 

appliances. 

Ensure clearances are in accordance with 

local installation codes and the requirements 

of the gas supplier.

Dégagement conforme aux codes d’installa-

tion locaux et aux exigences du foumis-

seunde gaz.

Use only approved venting components.  See 

Approved Vent Components

 on 

Page 4

.

These fireplaces must be vented directly 

to the outside.

The vent system may not service multiple 

appliances, and must never be connected to a 

flue serving a solid fuel burning appliance. The  

vent pipe is tested to be run inside an enclosed 

wall (such as a chase). There is no requirement 

for inspection openings in the enclosing wall at 

any of the joints in the vent pipe. 

Venting System

With the appliance secured in framing, de-

termine vent routing and identify the exterior 

termination location. The following sections 

describe horizontal (exterior wall) vent applica-

tions. 

 A list of approved venting components 

is shown on 

Page 35

.

Summary of Contents for DRT63ST

Page 1: ...mm diatement de b timent Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des...

Page 2: ...NT DE TOUCHER LA VITRE EL VIDRIO CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque...

Page 3: ...toca Mantenga a los ni os alejados de la chimenea en funcionamiento Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidri...

Page 4: ...and d installerunebarri rephysiquesi des personnes risques habitent lamaison Pouremp cherl acc s un foyer ou un po le installez une barri re de s curit cette mesureemp cheralestoutpetits les jeunes en...

Page 5: ...t cran ou protecteur retir pour permettre l entretien de l appareil doit tre remis en place avant de mettre l appareil en marche WARNING Improper installation or use of thisappliancecancauseserious in...

Page 6: ...WC 2 61 kPa Table 2 Gas Supply Pressure Requirements Inlet and manifold gas supply pressure require ments for these appliances are listed in Tables 2 and 3 Manifold Gas Supply Pressure all models Fuel...

Page 7: ...of combustible materials used to construct a utility shelf in this fashion is shown in Figure 7 on Page 11 Be aware that this is a heat producing ap pliance Objects placed above the unit are exposed...

Page 8: ...Termination Combustible 18 457 mm VENT TERMINATION CLEARANCES These instructions should be used as a guideline and do not supersede local codes in any way Install venting according to local codes the...

Page 9: ...50 000 Btu h 15 kW 12 300 mm for fireplaces 50 000 Btu h 15 kW 6 150 mm for fireplaces 10 000 Btu h 3 kW 12 300 mm for fireplaces 10 000 Btu h 3 kW K Clearance to a mechanical air supply inlet 36 910...

Page 10: ...e fireplace and may butt against the front face of the fireplace see Figures 5 and 6 Also note the following Combustible material may project beyond the sides of the fireplace opening as long as it is...

Page 11: ...r on the underside of the mantel 7 178 2 51 4 102 6 152 8 203 10 254 12 305 9 229 13 330 17 432 15 381 11 279 Side View Inches millimeters Mantel Depth Minimum Distance to Unprotected Side Wall Top of...

Page 12: ...e in direct contact with the nailing flanges and may be located closer than 1 2 inch from screw heads and the firebox wrapper in areas adjacent to the nailing flanges Frame the opening to the exact di...

Page 13: ...e base to top framing member Dimension C is from fireplace base to centerline of horizontal vent pipe Minimum vent framing Adaptor plus 4 ft vertical vent and one 90 degree elbow For other venting con...

Page 14: ...ner 7 1 2 Outer Adaptor Probe assembly cat no H8313 required to transition from fireplace vent collar to vent pipe 50 1 2 1283 29 5 8 753 12 3 8 314 5 1 8 130 41 1 2 1054 33 3 4 857 34 3 4 883 13 1 8...

Page 15: ...m 7 178 mm 1 1 2 38 mm Figure 13 INDOOR INDOOR 7 178 mm Right Side Front Corner Valve Side of Fireplace Framing 19 1 2 495 mm Right Side Front Corner Of Fire place Framing Step 2 ROUTE GAS LINE NOTICE...

Page 16: ...w NOTE 87L00 and F4502 are required if using flex vent and is not provided in kit Please see Page 35 and Figure 16A Vent Restrictor The adaptor probe assembly for this appli ance has a pre installed v...

Page 17: ...7 4 5 2 6 9 3 0 1 0 0 0 1 1 1 0 8 4 0 4 1 1 0 0 0 1 1 1 2 9 4 1 4 1 0 1 0 0 1 2 1 5 9 9 4 5 2 6 1 4 0 0 0 1 0 1 1 1 4 0 5 2 4 1 0 0 1 0 1 2 1 5 1 1 5 5 2 6 2 4 0 0 0 0 1 1 1 1 5 0 2 5 5 7 3 3 4 0 2 0...

Page 18: ...mponent against the previ ous section until it fully engages then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels This...

Page 19: ...Minimum Vent Run Horizontal 10 ft Exterior Wall Power Vent Termination Probe Adaptor required Probe Adaptor required Fireplace Floor Maximum Horizontal Venting 110 ft Up to 6 Elbows Firestop Spacer Ex...

Page 20: ...Install support straps every 3 feet 1914 mm along horizontal inclined vent runs using conventional plumber s tape See Figure 21 on Page 19 HORIZONTAL OUTSIDE WALL TERMINATION SYSTEM See Figures 21 and...

Page 21: ...including theuseofsiliconecaulkingwhererequired To help minimize water infiltration it isrecom mended that the Firestop Spacer SV4 5HF be installed on the exterior side of the wall Power Vent Termina...

Page 22: ...over to the grooves of the collar that extend approximately 1 from the end and to the flat surface approximately 1 3 8 from the end Apply ONLY MIL PAC BLACK HIGH TEMPERATURE SEALANT P N 10K81 to the o...

Page 23: ...e electrical wiring refer to Figure 27 Standard Instruction For use when access to the termination is difficult because of height or other reasons Locate a locally procured electrical junction box wit...

Page 24: ...en the strain relief on the termination shown in Figure 30 Pull the pigtail in and shorten it to fit within the junction box cover Route 14 gauge AWG grounded Romex wiring not provided from fireplace...

Page 25: ...tall ing the glass door frame Donotattempttosubstitutethe materials used on this door or replace cracked or broken glass with any materials other than those provided by the appliance manufacturer The...

Page 26: ...ing connection then retest as described above C When the gas lines are tested and leak free be sure to rinse off the leak testing solution D Reinstall the access plate making certain the gasket has no...

Page 27: ...el and glass door assembly from one side of fireplace See Page 30 9 2 Locate materials log set bag of glowing embers and bags of volcanic stone NOTE LOGS ARE FRAGILE Handle with care to prevent breaka...

Page 28: ...3rd Grate Finger Control Side 2nd Grate Finger Non Control Side Main Grate Support Log C 4th Grate Finger Control Side 5 Place Log H on left grate crossbar and Log C Slide Log H up crossbar until it c...

Page 29: ...see Figure 49 1st Grate Finger 2nd Grate Finger 3rd Grate Finger Log D Figure 49 12 Place Log F on top of Logs D and A see Figure 50 Log F Log A Log D Figure 50 13 Place Log I on top of Log D and in c...

Page 30: ...er f Install the new approved factory barrier with flatsideofbarriertowardfirebox ifappropriate 2 Remove the modesty panel from the top flange of the glass door by firmly pulling up on it with both ha...

Page 31: ...ter is not covered under the warranty Burner Air Shutter Adjustment Procedure Step 11 BURNER ADJUSTMENTS Flame Appearance and Sooting Proper flame appearance is a flame that is blue at the base and be...

Page 32: ...e Finished Wall Materials Wall Stud Top of Door Frame FIREPLACE side view Top of Appliance Spacers Insulation is NOT ALLOWED in clearance zones around vent components Keep this area free from combusti...

Page 33: ...ront lip of each Mounting Bracket and then align the holes Step 5 Slide the openings in the bottom edge of the Safety Guard over the Spring Nut Clips Step 6 Align the holes in the top of the Outdoor B...

Page 34: ...ment pour liminer la poussi re et les traces degraisseoud huile Collezl tiquettesurlebo tier de la t l commande Figure B Choisissez la langue qui est principalement parl e dans la r sidence du propri...

Page 35: ...al 3 1 1 spacing 10 pack H2247 SV4 5VF Firestop Spacer Vertical 1 1 1 spacing 10 pack The following flashings come packaged with a storm collar H5816 750 247M SV4 5 TWSK Through Wall Shield Kit used t...

Page 36: ...053M 98K03 SF 12 12 ft 3 66 m compressed flex see 750052M H2248 SF4 5HF 10 Firestop Spacer Horizontal flex 3 1 1 spacing 10 Pack H2249 SF4 5VF 10 Firestop Spacer Vertical flex 1 1 1 spacing 10 Pack 91...

Page 37: ...eunes enfants ou les adultes peuvent subir des br lures s ils viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison...

Page 38: ...a If you have these signs obtain fresh air immediately Turn off the gas supply to the appliance and have it serviced by a qualified professional as it may not be operating correctly Some people are mo...

Page 39: ...d for residential application Direct vent appliances operate with the com bustion chamber completely isolated from the indoor environment All air for combustion is brought in from the outside and exha...

Page 40: ...hot surfaces AVERTISSEMENT Lesjeunesenfantsdevraient tresurveill s troitementlorsqu ilssetrou ventdanslam mepi cequel appareil Lestoutpetits lesjeunesenfants ou les adultes peuvent subir des br lures...

Page 41: ...nce main burner turns on A single beep from the Receiver will confirm reception of the command Turn OFF the Appliance Press the ON OFF Key on the Transmitter The Transmitter LCD display will only show...

Page 42: ...s func tion press the MODE and UP keys at the same time Todeactivatethisfunction presstheMODE and UP keys at the same time Manual Bypass of the Remote System If the batteries of the Receiver or Transm...

Page 43: ...fe combustion Inspect Wiring Refer to wiring diagram on Page 25 CAUTION Label all wires prior to disconnec tion when servicing controls Wiring errors cancauseimproperanddangerousoperation Verify prope...

Page 44: ...of the door held away from the fireplace see Figure 68 c Lower the bottom of the door assembly onto the bottom door track engaging and centering it in the base channel and then gently swing the door...

Page 45: ...ENCE INFORMATION Model Number_________________________________________________________ Serial Number_________________________________________________________ Date Installed ___________________________...

Page 46: ...ag of Volcanic Stone Outdoor Kit Wheninstallingthisapplianceinanindoor out door configuration this outdoor kit is required to be installed on the outdoor side Outdoor Kit Cat No Model Description F223...

Page 47: ...e 9 Slide the switch on the receiver to REMOTE 10 Press ON OFF button on transmitter to ON 11 Set thermostat on remote control to desired setting 12 If the appliance will not operate follow the instru...

Page 48: ...ssez l tape suivante 8 Mettez l appareil sous tension 9 Placez l interrupteur du r cepteur en position REMOTE 10 Appuyez sur le bouton ON OFF pour s lectionner ON 11 Ajustez le thermostat sur la t l c...

Page 49: ...NOTE Excessive condensation can cause corrosion of caps pipe and fittings excessive condensation can be caused by long lateral runs too many elbows and or exterior portions of the system being exposed...

Page 50: ...ce Check gas supply and gas shutoff valves call a service technician if required B Air in gas line Call a service technician C Loose wires to valve Check control compartment for any obvious loose wiri...

Page 51: ...Hose From The Blower To The Pressure Switch Are the Hose Connections Loose Is The Hose Cracked Replace Pressure Switch Replace Control Module Yes Yes Is The Lead To The Spark Electrode Attached Or Ar...

Page 52: ...7 AC DC Power Adaptor H8006 1 38 Transmitter Kit H7275 1 39 Ground Wire H7278 1 Power Vent Module H7367 1 45 Pilot Bracket F3659 1 Item No Description Cat No Qty a Ceramic Panel Kit Architectural Ston...

Page 53: ...ration 901140 00 01 2021 Innovative Hearth Products DRT63ST B Power Vent Direct Vent Fireplaces REPLACEMENT PARTS ILLUSTRATION Numbers correspond to Replacement Parts List on previous page 22 14 3 2 4...

Page 54: ...8 2 6 H7370 Ring Terminal 10 2 7 H7384 Insulated 1 4 Male Terminal 4 8 H7371 Hose Clamp 11 32 2 15 H7372 Base Assembly Power Vent 1 16 H7378 Kicker Assembly 1 POWER VENT REPLACEMENT PARTS Item Part Nu...

Page 55: ..._____________________________________ ______________________________________________________ ______________________________________________________ ____________________________________________________...

Page 56: ..._____________________________________ ______________________________________________________ ______________________________________________________ ____________________________________________________...

Page 57: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard...

Page 58: ...erial number Date fireplace was Installed Type of gas fireplace uses Dealer name Printed in U S A 2014 Innovative Hearth Products P N 901140 00 Rev NC 01 2021 1769 East Lawrence Street Russellville AL...

Reviews: