background image

Installation 

900636-01, 01/2017

Innovative Hearth Products
DRT4200 Series Direct-Vent Gas Fireplaces

31

6.  Install the firestop/spacer at the ceiling

—When using Secure Vent

®

, use SV4.5VF firestop/spacer at ceiling 

joists; when using Secure Flex

®

, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, 

the firestop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the 

firestop/spacer must be installed on the top side of the joist. Route the vent sections through the framed opening 

and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Maintain 1” (26 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running 

vertical chimney sections.

7.  Support the vertical run sections

—On the vertical run, support the venting system every 8 ft (2.4 m) above the 

fireplace vent outlet with field provided support straps (Plumber’s tape). Attach the straps to the vent pipe and 

secure to the framing members with nails or screws 

(

Figure 21, Page 26

)

.

8.  Change vent direction

—At transition from or to a horizontal/inclined run, install SV4.5E45 or SV4.5E90 elbows 

in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed 

about the center axis of their initial collar section to align with the required direction of the next vent run element. 

Twist elbow sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously 

connected vent sections 

(

Figure 17

)

.

9.  Continue installation of horizontal/inclined sections

—Continue with the installation of the straight vent 

sections in horizontal/inclined run. Install support straps every 5 ft. (1.52 m) along horizontal/inclined vent 

runs using conventional plumber’s tape 

(

Figure 25

)

. Maintain the horizontal/inclined run in a straight (no dips), 

slightly elevated plane. The recommended incline is approximately 1/4” per 1 ft (20 mm per 1 m) horizontal, in 

a direction away from the fireplace. 

Smaller rise per foot run ratios are acceptable all the way to at or near 

level.

 Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary. 

Maintain the required clearances to combustibles

 (

Page 30

)

.

10. Assemble the vent run to the exterior wall

—If not previously measured, locate the center of the vent at the 

exterior wall. Prepare the opening. Assemble the vent system until the terminus of the last section is within 

7” (178 mm) to 11-1/4” (286 mm) inboard of the exterior surface to which the SV4.5HT termination is to be 

attached 

(

Figure 26

)

. If the terminus of the last section is not within this distance, use the telescopic vent section 

SV4.5LA, as the last vent section. 

Table 20

 lists the additional venting components needed (in addition to the 

termination and adaptor) for a range of wall thicknesses.

11. Attach the termination adaptor

—Attach the adaptor (SV4.5RCH, provided with the termination) to the vent 

section or telescoping vent section, elbow or fireplace collar 

(

Figure 26

)

.

12. Install the firestop/spacer at the exterior wall

—When using the square termination, install SV4.5HF (Secure 

Vent), SF4.5HF (Secure Flex) Firestop/Spacer over the opening at the exterior side of the framing, long side up, 

with the 3” spacer clearance at the top 

(

Figure 26

)

 and nail into place. 

NOTE: 

The firestop/spacer may also be installed over the opening at the interior side of the framing.

13. Install the termination (

SV4.5HT-2

)

—From outside the exterior wall, slide the collars of the termination onto the 

adaptor (the outer over the outer and the inner inside the inner) until the termination seats against the exterior 

wall surface to which it will be attached. Orient the housing of the termination with the arrow pointed upwards. 

Secure the termination to the exterior wall. The horizontal termination must not be recessed into the exterior wall 

or siding by more than the 1-1/4” (32 mm) 

(

Figure 27

)

.

NOTE: 

If the venting exits the building below grade, or close to grade, see 

Installation Accessories on 

Page 47

 

for available snorkel terminations. The termination must be above grade and above the expected level of 

snow accumulation.

NOTE: 

The vent termination is hot while in operation and for a period of time following the use of the fireplace. 

To prevent contact with hot surfaces, use a horizontal termination guard; available for purchase at your local 

dealer.

The horizontal terminations have been designed to perform in a wide range of weather conditions. Our 

terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, 

do not place the termination where water from 

eaves and adjoining rooflines may create a heavy flow of cascading water onto the termination cap

. If the cap 

must be placed where the possibility of cascading water exists, it is the responsibility of the builder to direct the 

water away from the termination cap by using gutters or other means.
Take care to carefully follow the installation instructions for the termination, including the use of silicone caulking 

where required.

Summary of Contents for DRT4200 Series

Page 1: ...sseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installationetl entretiendoivent treassur spar...

Page 2: ...VITRE EL VIDRIO CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas...

Page 3: ...oca Mantenga a los ni os alejados de la chimenea en funcionamiento Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio...

Page 4: ...Requirements 12 Location 12 Vent Termination Clearances 13 Minimum Clearances to Combustibles 15 Wall Finishes Surrounds Mantels 16 Installation Preparation 16 Installation Installation Sequence 17 C...

Page 5: ...t subir des br lures s ils viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou u...

Page 6: ...ls is dangerous Improper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning CARBON MONOXIDE POISONING Early signs of carbon...

Page 7: ...combinations of fuels will degrade the performance of this system and may be dangerous Provide adequate clearances around air openings and adequate accessibility clearance for service and proper opera...

Page 8: ...e inspection par un technicien professionnel avant d tre utilis et au moins une fois l an par la suite Des nettoyages plus fr quents peuvent tre n cessaires si les tapis la literie et cetera produisen...

Page 9: ...ased on Normal input operation Gas Pressure Table 3 Inlet Gas Supply Pressure Fuel Minimum Maximum Natural Gas 5 WC 1 25 kPa 10 5 WC 2 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 4 Manifold...

Page 10: ...very 1 000 ft of altitude IN CANADA CAN CGA 2 17 M91 HIGH ALTITUDE THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER S AUTHORIZED REPRESENTATIVE IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACT...

Page 11: ...loor on which fireplace rests if floor is above ground level Gas line holes and other openings should be caulked or stuffed with unfaced fiberglass insulation NOTE Do not use loose or blown in insulat...

Page 12: ...se direct vent fireplaces are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace Utility shelves like these are commonly used for locating television s...

Page 13: ...12 6 0 ft 1 83 m 16 12 to 18 12 7 0 ft 2 13 m 18 12 to 20 12 7 5 ft 2 29 m 20 12 to 21 12 8 0 ft 2 44 m 12 X Roof pitch is X 12 2 ft minimum 2 ft minimum Lowest discharge opening H H minimum height f...

Page 14: ...orner 6 152 mm minimum 6 152 mm minimum H Clearance to each inside of center line extended above meter regulator assembly 36 910 mm within a height of 15 ft above the meter regulator assembly 36 910 m...

Page 15: ...iance shall be installed on a metal or wood panel extending the full width and depth of the appliance Hearth Extension A hearth extension is not required with this fireplace If a hearth extension is u...

Page 16: ...and retain the front of the carton used to protect the fireplace during construction 2 Remove the shipping pad exposing the front glass door 3 Remove the glass door Pages 57 58 NOTE Place the glass do...

Page 17: ...Fireplace Operation Page 41 Remote Control 15 Initialize the Remote Control System for the First Time Page 40 Finishing 16 Optional Install the Firebox Liners Page 42 17 Install the Logs Volcanic Ston...

Page 18: ...xible venting When using flexible venting refer to the kit requirements for framing specifications Vent Framing Top Vent with One 90 Elbow NOTE Dimension D is the required framing depth when the finis...

Page 19: ...of Gas Line Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code NFPA 54 la...

Page 20: ...Step 4 Fireboard standoff can be secured to the capture screw holes 4 Determining Vent Setup in the Combination Venting Unit Combination venting units are shipped with rear venting setup nearly ready...

Page 21: ...framing 1 2 and 5 8 framing depths 2 Secure the fireplace to the side framing members using the unit s nailing flanges one top and bottom on each side of the fireplace front Figure 10 Use 8d nails or...

Page 22: ...rictor is held in place by friction Vent Restrictor with Horizontal Terminations When horizontally terminating a vent system with a vertical vent run up to 4 ft through an exterior wall no vent restri...

Page 23: ...ption to install in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or will not build up to the required length The SV4 5LA Te...

Page 24: ...465 38 75 0 0 0 0 10 10 69 5 75 0 0 0 2 0 2 475 5 39 625 0 1 0 0 10 11 73 5 6 125 1 0 0 2 0 3 480 40 1 1 0 0 10 12 79 5 6 625 0 1 0 2 0 3 492 41 1 0 1 0 10 12 81 6 75 0 0 0 1 1 2 499 5 41 625 0 0 0 1...

Page 25: ...s specified in ANSI Z223 1 In Canada the current CAN CGA B149 1 installation code by major building codes Always consult your local codes for specific requirements A general guide to follow is the gas...

Page 26: ...living space above the ceiling level the firestop spacer must be installed on the bottom side of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the top side o...

Page 27: ...ry Seal the top and both sides of the flashing with waterproof caulking 11 Install the storm collar Install the storm collar supplied with the flashing over the vent flashing joint Figure 22 Loosen th...

Page 28: ...NOT join separate sections of concentric flexible vent pipe Figure 24 Top Vent Straight Table 16 Rear Vent One 90 Elbow Ceiling firestop spacer SV4 5VF When using Secure Flex use ceiling firestop spac...

Page 29: ...H H1 60 ft 18 3 m maximum Install the U shaped vent restrictor in any vent run with more than 6 ft of vertical rise See Page 22 for more information If 20 ft of H horizontal vent run is needed then 4...

Page 30: ...ing the vent pipe see Page 23 Figure 25 Typical Horizontal Vent Installation Support bracket spacing every 5 ft 1 52 m Firestop Spacer Vertical Vent Fireplace Vertical Rise Ceiling SV4 5E90 Elbow Supp...

Page 31: ...the terminus of the last section is within 7 178 mm to 11 1 4 286 mm inboard of the exterior surface to which the SV4 5HT termination is to be attached Figure 26 If the terminus of the last section i...

Page 32: ...stalling the Horizontal Termination NOTE To help minimize water infiltration install the firestop spacer SV4 5HF on the exterior side of the wall The firestop may be caulked with mill base caulk such...

Page 33: ...t the support straps as necessary NOTE SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used any time vent pipe passes through a combustible floor or ceiling SV4 5HF Secure Vent SF4 5HF...

Page 34: ...nge of exterior wall thicknesses If 25 ft of H horizontal vent run is needed then 5 ft minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 ft of V vertical you...

Page 35: ...estop spacer SF4 5HF Wall firestop spacer SV4 5HF Ceiling firestop spacer SV4 5VF H V H1 H2 Table 27 Top Vent Three 90 Elbows H Maximum V Minimum feet meters feet meters 5 1 524 Elbow only 5 1 524 1 0...

Page 36: ...collar to be covered by the flexible pipe and slide the flexible vent over the inner and outer adaptor collars NOTE Outer vent pipe is pulled away to show inner vent pipe details 1 3 4 44 mm flexible...

Page 37: ...rs Secure Flex vent has an longer center tube to improve ease of installation 12 Complete the Field Wiring CAUTION The ground supply lead must be connected to the wire attached to the green ground scr...

Page 38: ...te power supply wire to the outlet s common terminal 5 Connect the ground supply wire to the pigtail lead attached to the outlet s green ground screw Restrain the inlet power lead per NEC or local cod...

Page 39: ...CS ECOMODPVI Main Module On Off Brown Optional Hi Lo Blue Optional IPI Cont Pilot Yellow Learn Black Some Models Valve Safety Operator Optional Fixed Outlet Some Models MOTOR COMM 120 VAC 120 VAC POWE...

Page 40: ...s on Accessing the Control Compartment Secure all joints tightly using appropriate tools and sealing compounds ensure propane resistant compounds are used in propane applications Optionally seal aroun...

Page 41: ...S M T W T F S AM PM ROOM SET P1 A B P2 P2 AUX P2 Pilot OFF ON u PROGRAM USB MODE SET BATTERY COMPARTMENT BACK 15 Verify Proper Fireplace Operation 1 With the gas line installed inspect the system befo...

Page 42: ...LAME Zone A Flame Icon and flame setting level number is displayed Program OFF LCD Displays MODE Zone OFF ROOM TEMP Zone Measured temperature is displayed SET TEMP Zone Blank LIGHT Zone LIGHT and ligh...

Page 43: ...d by black puffs developing at the tips of very long orange flames Sooting results in black deposits forming on the logs fireplace inside surfaces and on exterior surfaces adjacent to the vent termina...

Page 44: ...e proper flame appearance is achieved 4 When satisfied that the burner flame appearance is normal reinstall the lower control compartment door then proceed to finish the installation Figure 36 Burner...

Page 45: ...it in place 22 Install the Finishing Materials 1 Complete finished interior wall NOTE To install the fireplace facing flush with the finished wall position framework to accommodate the thickness of t...

Page 46: ...o tier de la t l commande Figure B Choisissez la langue qui est principalement parl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 3 Si vous ne trouvez pas les tiquet...

Page 47: ...tal Riser Kit 36 see 750146M Cat No Model Description H6183 SV4 5HF5 Firestop Spacer 5 rigid H6184 SF4 5HF5 Firestop Spacer 5 flex H2246 SV4 5HF 10 Firestop Spacer Horizontal rigid 3 1 1 spacing 10 Pa...

Page 48: ...ex with 24 610 mm compressed flex 77L90 SFKIT36S Square Term for flex with 36 914 mm compressed flex 77L91 SFKIT48S Square Term for flex with 48 1219 mm compressed flex 91L66 SFGC4 6 Gear Clamp 4 5 11...

Page 49: ...onsable de l installation de cette trousse L installation n est pas ad quate ni compl te tant que le bon fonctionnement de l appareil converti n a pas t v rifi selon les instructions du fabricant four...

Page 50: ...ed by carbon monoxide than others including pregnant women people with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes NOTE Do not place furniture or o...

Page 51: ...n le faisant basculer de Marche Arr t et vice versa Nettoyez soigneusement la plaquedur cepteurmuralpour liminerlapoussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la p...

Page 52: ...ment Door 1 Swing the control compartment door gently up until the magnet engages the door in the closed position Removing the Control Compartment Door 1 Open the lower control compartment door see in...

Page 53: ...f extreme cold condensation may form on the glass door when the fireplace is OFF and the pilot is in intermittent mode Also with the pilot in intermittent mode the fireplace may cycle startup i e the...

Page 54: ...ion of soot and or the colorless odorless toxic gas carbon monoxide CO NOTE It is important to ensure proper log placement per the manual when installing these units Verify pilot flame is not obstruct...

Page 55: ...pper Left Rear Log 3 Upper Right Rear Log 4 Middle Left Log 5 Front Left Forked Log 6 Front Right Forked Log 7 Upper Right Forked Log 1 If necessary remove the glass door Page 57 2 Position the rear l...

Page 56: ...wn in Figure 52 One foot will rest between the 2nd and 3rd bar from the left on the grate Figure 47 Place log 4 Figure 48 Place log 5 4 5 Figure 49 Place log 6 7 The front right forked log 6 will roll...

Page 57: ...e pour r duire le risque de br lure par le hublot chaude est fournie avec l appareil et doit tre install WARNING Do not operate appliance with the glass front removed cracked or broken AVERTISSEMENT N...

Page 58: ...at the gasket seats evenly as the door draws shut Securely fasten the two 2 latches beneath the firebox floor to the door V flange 4 Install the barrier 5 Close the control compartment door Removing t...

Page 59: ...sealing of the venting system components However more frequent periodic inspections and cleanings should be performed by the homeowner NOTE Prior to the first use of the fireplace and each burn season...

Page 60: ...rush e g paint brush Reinstalling the embers and logs Carefully follow the placement instructions Pages 54 56 All logs should fit onto the corresponding pins and or log stoppers This will ensure prope...

Page 61: ...of blockage or obstruction Look for any signs of dislocation of the vent components Appliance Inspection Qualified Service Technician Perform the appropriate appliance inspection procedure detailed i...

Page 62: ...on Shroud 87L02 SV4 5HGS Termination Guard Deluxe 17M52 SV4 5HGS 1 Termination Guard Square Table 38 Termination Guard Kits Termination Guard Kits The vent termination guards may be used to minimize e...

Page 63: ...h has been under water Copreci Gas Valve Switches Electronic Pilot Assembly 3 Turn off all electric power to the appliance if service is to be performed Note The control may have a battery backup remo...

Page 64: ...REFROIDIE NE LAISSEZ JAMAIS UN ENFANT DE TOUCHER LA VITRE L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre chaude et doit tre install p...

Page 65: ...necessary d Air in the gas line Purge gas line of air call a service technician if required e Unit is not receiving power Replace unit battery backup 3 The main Burner comes on but then goes out a Gas...

Page 66: ...ce Natural Gas Rear 99K76 1 37L82 1 Orifice Liquid Propane Front 35M91 1 35M91 1 Orifice Liquid Propane Rear 19L52 1 37G00 1 On Off Jumper H8809 1 H8809 1 Superior Badge logo J8150 1 J8150 1 Fiberboar...

Page 67: ...6 5 WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury AVER...

Page 68: ...Operation 900636 01 01 2017 Innovative Hearth Products DRT4200 Series Direct Vent Gas Fireplaces 68 NOTES...

Page 69: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard...

Page 70: ...place serial number Date fireplace was Installed Type of gas fireplace uses Dealer name IHP reserves the right to make changes at any time without notice in design materials specifications prices and...

Reviews: