background image

Installation 

900948-00C, 06/2019 

Innovative Hearth Products
DRT2000-C Series Direct-Vent Gas Fireplaces

36

Vertical or Horizontal Venting Using Secure Flex

®

 Kits and Components

When Secure Flex

® 

kits are used in a rear flue, horizontal termination installation, at least 1 ft of vertical rise is required.

Secure Flex venting kits and components may be used in any other vent installation where rigid Secure Vent

®

 (SV4.5) 

direct-vent components can be used. All restrictions, clearances and allowances pertaining to rigid vent also apply to 

flexible vent. Do NOT modify Secure Flex kits . Also, do NOT join separate sections of flex vent together. Secure Flex 

kits can be installed on the end of a Secure Vent (SV4.5) rigid vent run, provided that doing so does not violate any 

of the venting length, height, routing, horizontal to vertical ratio requirements, or clearance considerations detailed in 

this manual. When combined, a rigid vent should not be installed between two flexible vents.
Secure Flex kits come with an included adaptor that can be installed on the fireplace collar or the inclined channel 

end of the last Secure Vent (SV4.5) vent section in a rigid system in the exact same fashion as any other Secure Vent 

section. Align the dimpled end of the adaptor over the previously installed section or fireplace collar, adjusting the 

radial alignment until the four locking dimples of the adaptor are aligned with the inlets of the four incline channels of 

the last vent section or collar. Push on the adaptor until it is fully engaged, then twist the adaptor clockwise running 

the dimples down and along the incline channels until they seat at the end of the channels.

Figure 27A - Flexible Vent Adaptor

Figure 27B - Flexible Vent

Apply ONLY MIL-PAC BLACK 

HIGH TEMPERATURE 

SEALANT (P/N 10K81) to 

the outside surface of both 

collars of the adaptor (fill the 

grooves of the outer collar to 

be covered by the flexible pipe) 

and slide the flexible vent over 

the inner and outer adaptor 

collars

NOTE: 

Outer vent pipe is pulled away 

to show inner vent pipe details.

Adaptor (SV4.5RF)

Attach adaptor to vent collar or Secure Vent sections

1-3/4” (44 mm) flexible 

vent and adaptor inner 

collar overlap

Securing screws 

in three (3) places 

through perforation 

and into the pipe

Gear clamps

Flexible vent

Flexible vent section

5” (127 mm) 

radius minimum

Shown here: 36” Flex Connector Kit 

(H7748) 

36” of flex with two adaptors for 

mating two rigid sections of vent 

together.

1. 

Install the Inner Flex Pipe. 

a. 

Install the small gear clamp loosely around the inner flexible vent, then push it back out of the way.

b. 

Apply a bead of Mill-Pac Black (700 °F) high temperature sealant (P/N 10K81) to the inner adaptor collar, 

approximately 1/2” from the end.

c. 

Pull and extend the inner flexible vent. 

d. 

Slide the inner flex vent over the adaptor collar at least 1-3/4”.

NOTE: 

Ensure the flex vent is free from damage or tears. 

e. 

Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor inner collar 

approximately 3/4” from the end of the flex.

f. 

Install three (3) sheet metal screws 120° apart through the flexible vent and into the adaptor collar just below 

the gear clamp to provide additional security to the connection.

2. 

Install the outer Flex Pipe. 

a. 

Install the large gear clamp loosely around the outer flexible vent pipe, then push it back out of the way.

b. 

Apply a bead of Mill-Pac Black (700 °F) high temperature sealant (P/N 10K81) to the outer adaptor collar. 

Cover to the grooves of the collar that extend approximately 1” from the end and to the flat surface, 

approximately 1 3/8” from the end.

c. 

Pull and extend the outer flexible vent.

d. 

Slide the outer flexible vent over the adaptor collar. Ensure the flexible vent completely engages the adaptor collar 

1-3/4” from the end, and that it is free from damage or tears.

e. 

Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor outer collar 

approximately 3/4” from the end of the flexible vent.

1-3/4” (44 mm) flexible 

vent and adaptor outer 

collar overlap

Securing screws 

in three (3) places 

through perforation 

and into the pipe

Summary of Contents for DRT2000-C Series

Page 1: ...sseur de gaz appelez le service des incindies L installationetl entretiendoivent treassur spar un installateur ou un service d entretien qualifi ou par le fournisseur de gaz INSTALLER Leave this manua...

Page 2: ...pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre chaude et doit tre install pour la protection Des enfants et Des personnes risques Vea el vol...

Page 3: ...si se toca Mantenga a los ni os alejados de la chimenea en funcionamiento Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el...

Page 4: ...irements 12 Location 12 Vent Termination Clearances 13 Minimum Clearances to Combustibles 15 Wall Finishes Surrounds Mantels 16 Installation Preparation 16 Installation Installation Sequence 17 Constr...

Page 5: ...t subir des br lures s ils viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou u...

Page 6: ...dangerous Improper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning CARBON MONOXIDE POISONING Early signs of carbon monoxi...

Page 7: ...te accessibility clearance for service and proper operation Never obstruct the front openings of the appliance These appliances are designed as supplemental heaters Therefore it is advisable to have a...

Page 8: ...re l objet d une inspection par un technicien professionnel avant d tre utilis et au moins une fois l an par la suite Des nettoyages plus fr quents peuvent tre n cessaires si les tapis la literie et c...

Page 9: ...1 Figure 1A Millivolt Gas Valve Figure 1B Electronic Gas Valve Propane tanks are at pressures that will cause damage to valve components Verify that the tanks have step down regulators to reduce the...

Page 10: ...0 1372 m Model Natural Gas drill size Propane drill size 35 Models 0 0745 Cat No F3940 56 0 046 Cat No 62L37 40 Models 45 0 082 Cat No 39L66 0 049 Cat No F3941 45 Models 44 0 086 Cat No 60J80 55 0 05...

Page 11: ...n monoxide detector must comply with NFPA 720 be ANSI UL 2034 listed and be ISA certified A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minim...

Page 12: ...are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace Utility shelves like these are commonly used for locating television sets and decorative plants...

Page 13: ...22 m 12 12 to 14 12 5 0 ft 1 52 m 14 12 to 16 12 6 0 ft 1 83 m 16 12 to 18 12 7 0 ft 2 13 m 18 12 to 20 12 7 5 ft 2 29 m 20 12 to 21 12 8 0 ft 2 44 m 12 X Roof pitch is X 12 2 ft minimum 2 ft minimum...

Page 14: ...to nonmechanical air supply inlet to building or the combustion air inlet to any other fireplace 6 150 mm for fireplaces 10 000 Btu h 3 kW 9 230 mm for fireplaces 10 000 Btu h 3 kW and 50 000 Btu h 1...

Page 15: ...only and does not have to conform to standard hearth extension installation requirements Shelf Height To provide for the lowest possible shelf surface use the rear vent model For top vent models the v...

Page 16: ...ve the fireplace NOTE To avoid heat related finish damage we recommend the use of high temperature paint rated 175 F or higher on the underside of the mantel INSTALLATION PREPARATION The fireplace is...

Page 17: ...g Page 37 Gas Connection 12 Connect the Gas Line Page 39 13 Verify Proper Fireplace Operation Page 40 Finishing 14 Optional Accessory see Page 68 for ordering information Install the Firebox Liners Pa...

Page 18: ...inimum height of rear vent installations Minimum opening size additional 1 8 per side is recommended NOTE Framing specifications do NOT apply for flexible venting When using flexible venting refer to...

Page 19: ...line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code NFPA 54 latest edition USA or CAN CGA B149 1 latest edition Ca...

Page 20: ...g the vent pipe If you require a rear vented unit remove the round outer rear flue cover 2 screws Figure 9A and the inner flue cover plate 4 screws Figure 9B If you require a top vented unit remove th...

Page 21: ...nd identify the exterior termination location The following sections describe vertical roof and horizontal exterior wall vent applications Use only approved vent components See Pages 28 29 vertical an...

Page 22: ...ons When horizontally terminating a vent system with a vertical vent run up to 4 ft through an exterior wall no vent restrictor is required If installing more than 6 ft of vertical venting install the...

Page 23: ...opic vent section SV4 5LA may be used to provide the installer with an option to install in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesir...

Page 24: ...3 465 38 75 0 0 0 0 10 10 69 5 75 0 0 0 2 0 2 475 5 39 625 0 1 0 0 10 11 73 5 6 125 1 0 0 2 0 3 480 40 1 1 0 0 10 12 79 5 6 625 0 1 0 2 0 3 492 41 1 0 1 0 10 12 81 6 75 0 0 0 1 1 2 499 5 41 625 0 0 0...

Page 25: ...figures Secure Flex pipe may also be used A table summarizes each configuration s minimum and maximum vertical and horizontal length parameters for a variety of applications 1 Refer to Figure 23 and...

Page 26: ...there is living space above the ceiling level the firestop spacer must be installed on the bottom side of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the t...

Page 27: ...eal the top and both sides of the flashing with waterproof caulking The flashing must overlap the roofing material along the bottom 11 Install the storm collar Install the storm collar supplied with t...

Page 28: ...ARNING Do NOT join separate sections of concentric flexible vent pipe Figure 23 Top Vent Straight Table 16 Rear Vent One 90 Elbow Ceiling firestop spacer SV4 5VF When using Secure Flex use ceiling fir...

Page 29: ...1 H Ceiling firestop spacer SV4 5VF H1 H 8 ft 2 4 m maximum H H1 20 ft 6 1 m maximum V V1 H H1 60 ft 18 3 m maximum Install the U shaped vent restrictor in any vent run with more than 6 ft of vertical...

Page 30: ...and determine the number of vent sections and elbows required See Effective Vent Length on Pages 23 24 for more information Plan the venting so that a joint does not occur in the ceiling or roof joist...

Page 31: ...Attach the termination adaptor Attach the adaptor SV4 5RCH provided with the termination to the vent section or telescoping vent section elbow or fireplace collar Figure 25 12 Install the firestop sp...

Page 32: ...mill base caulk such as 10K81 or high temperature silicone Figure 26 Venting Connection and Exterior Wall Recessing of the Horizontal Termination Use silicone caulking to seal the top and sides of the...

Page 33: ...Secure Vent SF4 5HF Secure Flex firestop spacer must be used any time vent pipe passes through a combustible wall WARNING Do not join separate sections of concentric flexible vent together Table 21 Re...

Page 34: ...is needed then 5 ft minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 ft of V vertical you are allowed 5 ft of H horizontal run up to a maximum horizontal ru...

Page 35: ...wall firestop spacer SF4 5HF Wall firestop spacer SV4 5HF Ceiling firestop spacer SV4 5VF H V H1 H2 Table 27 Top Vent Three 90 Elbows H Maximum V Minimum feet meters feet meters 5 1 524 Elbow only 5...

Page 36: ...the inner and outer adaptor collars NOTE Outer vent pipe is pulled away to show inner vent pipe details Adaptor SV4 5RF Attach adaptor to vent collar or Secure Vent sections 1 3 4 44 mm flexible vent...

Page 37: ...ations or Secure Vent adaptor for Secure Flex components Secure Flex termination and adaptor collars are a different circumference than Secure Vent collars Secure Flex vent has an longer center tube t...

Page 38: ...hermostat mount it in a convenient location on a wall near the fireplace 2 Wire the control switch within the millivolt control circuit using the 15 ft of 2 conductor wire supplied with the unit Figur...

Page 39: ...B B B R B B SIT Electronic Gas Valve See the Operation section on Page 51 for more details NOTE Electronic models must be connected to the main power supply 1 Route a 3 wire 120 Vac 60 Hz 1 ph power s...

Page 40: ...Flare shutoff valve 3 8 Flex tubing Gas stub 1 2 x 3 8 Reducer These fireplaces are equipped with a gas flex line for use where permitted in connecting the unit to the gas line A gas flex line is pro...

Page 41: ...3 74 NOTE When lighting the fireplace for the first time it will take a few minutes for the gas line to purge itself of air When purged the pilot and burner will light and operate as indicated Subsequ...

Page 42: ...f the air shutter opening is closed too far sooting may develop Sooting is indicated by black puffs developing at the tips of very long orange flames Sooting results in black deposits forming on the l...

Page 43: ...ition by pulling rod down especially on LP gas 1 Move the adjustment rod down to increase air flow and up to decrease it The rod is located in the lower control compartment Position the air shutter to...

Page 44: ...djustment It is suggested that the center screw should be installed first and the ends last 1 Attach hood using three screws as shown here WARNING Reinstall any barrier removed before operating the fi...

Page 45: ...the Barrier Support Bracket Installation see Figures 36A and 36B 1 Slide barrier into upper trim panel NOTE This panel will rotate for ease of installation BARRIER INSTALLATION FOR D2000C SERIES 2 Low...

Page 46: ...ch the Safety in Operation Warning Labels 1 Attach the furnished safety instruction labels at all fireplace operation and control points Page 47 NOTE The installer MUST ensure these warnings are prope...

Page 47: ...huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl e dans la r...

Page 48: ...id Cat No Model Description The following flashing comes packaged with a storm collar 77L78 SV4 5F Flat Roof Flashing 77L79 SV4 5FA 1 12 to 7 12 Adjustable Flashing 77L80 SV4 5FB 7 12 to 12 12 Adjusta...

Page 49: ...x with 12 305 mm of compressed flex vent see 750204M 94L05 SFKIT18SS Small Square Termination for flex with 18 457 mm of compressed flex vent see 750204M 94L06 SFKIT24SS Small Square Termination for f...

Page 50: ...selon les instructions du fabricant fournies avec la trousse Le fournisseur de service qualifi ayant r alis l installation assume les responsabilit s li es la conversion In Canada The conversion shall...

Page 51: ...ted by carbon monoxide than others including pregnant women people with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes NOTE Do not place furniture or...

Page 52: ...rruptor opera la chimenea encendi ndola y apag ndola Limpiebienlaplacadelinterruptoroeltermostatode paredparaquitarelpolvoyaceite Peguelaetiqueta enlasuperficiedelaplacadelinterruptorquecontrola la ch...

Page 53: ...front during the first few fires as part of the burn in period The glass should be kept clean during the burn in period to prevent the film from baking on making it very difficult to remove Cleaning...

Page 54: ...you local distributor or dealer Readthisinstructionsheetinitsentiretybeforebeginningtheinstallation ALL WARNINGS AND PRECAUTIONS IN THE INSTALLATION AND OPERA TION MANUAL PROVIDED WITH THE APPLIANCE...

Page 55: ...Direct Vent Gas Fireplaces 55 Figure 39D Figure 39E Showing Lintel Figure 39C Insert Bent Bracket Bracket Insert Top Leg Of Bracket Between Lintel And Top Panel Example of Pre Bent Bracket Before Ins...

Page 56: ...in incomplete combustion sooting and poor flame quality Logs get very hot and remain hot for up to one hour after the gas supply is turned OFF Handle the logs only when cool This appliance is not desi...

Page 57: ...ges 63 64 Locate the placement tabs Figure 40 2 Bend up the log placement tabs Figure 40 3 Install the front left log 1 Figure 41 Figure 40 Locate the log placement tabs Figure 41 Place front left log...

Page 58: ...gure 44 Place back right log 4 Figure 45 Place twig log 5 Bottom View Bottom View Top View Top View Figure 46 Place glowing embers rockwool Do NOT place embers on or close to large ports or the pilot...

Page 59: ...Pages 63 64 Locate the placement tabs Figure 47 2 Bend up the log placement tabs Figure 47 3 Install the front left log 1 Figure 48 Figure 47 Locate the log placement tabs Figure 48 Place front left l...

Page 60: ...tinued Figure 51 Back Right Log 4 Figure 52 Place Twig Log 5 Bottom View Bottom View Top View Top View Figure 53 Place glowing embers rockwool Do NOT place embers on or close to large ports or the pil...

Page 61: ...ent tabs Figure 54 3 Install the front left log 1 Figure 55 Figure 54 Locate the log placement tabs Figure 55 Place front left log 1 4 Install front right log 2 on two tabs Figure 56 5 Install back le...

Page 62: ...59 Place Twig Log 5 Bottom View Bottom View Top View Top View Figure 60 Place glowing embers rockwool Do NOT place embers on or close to large ports or the pilot area NOTE Enough glowing ember materia...

Page 63: ...e installed AVERTISSEMENT Une barri re con ue pour r duire le risque de br lure par le hublot chaude est fournie avec l appareil et doit tre install WARNING Do not operate appliance with the glass fro...

Page 64: ...lace in order to close If it does remove the door and inspect the door gasket to ensure it is even and not rolled up at the top SEE WARNING IN FIGURE 61 4 Install the barrier 5 Close the control compa...

Page 65: ...venting system components However more frequent periodic inspections and cleanings should be performed by the homeowner NOTE Prior to the first use of the fireplace and each burn season and periodica...

Page 66: ...g paint brush Reinstalling the embers and logs Carefully follow the placement instructions Pages 56 62 All logs should fit onto the corresponding pins and or log stoppers This will ensure proper flame...

Page 67: ...or signs of blockage or obstruction Look for any signs of dislocation of the vent components Appliance Inspection Qualified Service Technician Perform the appropriate appliance inspection procedure de...

Page 68: ...able speed forced air circulation The FBK 250 offers variable speed control and a heat activated switch perfect for fireplaces controlled thermostatically Touch Up Paint Kits Repair minor scratches an...

Page 69: ...y indicator Batteries included Wall Control 4 button timer with 30 60 120 OFF minutes Wall surface mounted Connects to wall switch wire Perfect for rental and resort applications Wall Switch Countdown...

Page 70: ...__________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________...

Page 71: ...mediately call your service technician or gas supplier LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE If the pilot will not stay lit after several tries turn the gas control knob to OFF and call y...

Page 72: ...m diatement un technicien qualifi ou le fournisseur de gaz Si la veilleuse ne reste pas allum e apr s plusieurs tentatives r glez la manette d admission du gaz la position OFF et appelez un technicien...

Page 73: ...y gas control which has been under water Electronic Gas Control Valve SIT Electronic Pilot Assembly 3 Turn off all electric power to the appliance if service is to be performed Note The control may ha...

Page 74: ...ur peut avoir une batterie de secours installer les batteries au besoin 8 Placez l interrupteur du r cepteur en position REMOTE ou l interrupteur mural en position ON 9 Si applicable Appuyez sur le bo...

Page 75: ...lighting instructions a Defective pilot generator thermocouple Check pilot flame it must impinge on thermocouple Clean and or adjust pilot for maximum flame impingement on thermocouple Ensure that th...

Page 76: ...45DEN C 45 DV Top Rear Elec F3890 DRT2045DEP C 45 DV Top Rear Elec F3887 DRT2045DMN C 45 DV Top Rear MV F3888 DRT2045DMP C 45 DV Top Rear MV Cat No Fireplace Models Description F3877 DRT2035REN C 35 D...

Page 77: ...embly H8601 1 H8601 1 H8601 1 Electronic DFC Ignition Board J7906 1 J7906 1 J7906 1 Electronic Power Transformer H8006 1 H8006 1 H8006 1 6 Electronic Battery Holder for backup batteries H8803 1 H8803...

Page 78: ...__________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________...

Page 79: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard...

Page 80: ...number Date fireplace was Installed Type of gas fireplace uses Dealer name Innovative Hearth Products IHP reserves the right to make changes at any time without notice in design materials specificati...

Reviews: