background image

8

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

* 3" (75 mm) above any horizontal/inclined vent component.
** See Page 9, Step 1 for clearance requirements to the nailing flange 

located at each side of the unit and any screw heads adjacent to it.

Wall Finishes / Surrounds / Mantels 

NOTE: Combustible wall finish materials and/or surround materials 

must not be allowed to encroach the area defined by the appliance 

front face (black sheet metal). Never allow combustible materials to 

be positioned in front of or overlapping the appliance face. See 

Figure 

and 

Figure 44 

on

 Page 26.

Noncombustible materials, such as surrounds and other appliance trim, 

may be installed on the appliance front face with these exceptions: they 

must not cover any portion of the removable glass panel.
Vertical installation clearances to combustible mantels vary according to 

the depth of the mantel (see 

Figure 5). Mantels constructed of noncom-

bustible materials may be installed at any height above the appliance. 

Minimum clearance requirements include any projections such as shelves, 

window sills, mantels, etc. above the appliance.

NOTE: We recommend the use of high temperature paint (rated 175 °F 

or higher) on the underside of the mantel.

MINIMUM CLEARANCES TO COMBUSTIBLES

Appliance And Vent Clearances

The appliance is approved with zero clearance to combustible materials 

on all sides. Refer to Table 5

 for minimum clearance values. For typical 

installations, see 

Figure 2 on Page 5.

Figure 6 - Minimum Distance to Unprotected Side Wall

Figure 5 - Minimum Mantel Clearances

INNOVATIVE HEARTH PRODUCTS  •  POWER VENT DV GAS FIREPLACES  (DRT63__TYN / DRC63__TYN)  •  INSTALLATION INSTRUCTIONS

MINIMUM CLEARANCES

*

    

 Inches (millimeters)

Sides

1/2" (13 mm)

0" (0 mm) Spacers **

Top Spacers

0" (0 mm)

Floor

0" (0 mm)

Back

1/2" (13 mm) 

0" (0 mm) Spacers

Bottom of Appliance To Ceiling

64" (1626 mm)

Vent

3" (76 mm) Top* 

1" (25.4 mm) Sides and Bottom

SERVICE CLEARANCES Feet (meters)

Front

3 feet (0.9 meters)

Table 5 

3-1/2” 

(89 mm)

Top View of 

Fireplace

Combustible materials

may project beyond

either side of the

fireplace opening as

long as they are kept

within the shaded

“Safe Zone” area. 

At 0” minimum

side wall clearance,

one combustible

wall can project to

any length.

 

45

o

Mantel Leg,

Trim, or Wall

12 (305) MANTEL

10 (254) MANTEL

8 (203) MANTEL

6 (152) MANTEL

4 (102) MANTEL

4

(102)

14

(356)

12

(305)

10

(254)

2 (51) MANTEL

TOP OF

APPLIANCE

6

(152)

8

(203)

MANTEL CLEARANCES

Inches (mm)

NOTE: Hood shown as positioned in louvered 

front model. The hood position in the flush 

faced front model is lower than shown.

Summary of Contents for DRC6345TYNDRC6340TYN

Page 1: ...E CHAUDE PEUT CAUSER DES BR LURES LAISSER REFROIDIR LA SURFACE VITR E AVANT D Y TOUCHER NE PERMETTEZ JAMAIS UN ENFANT DE TOUCHER LA SURFACE VITR E EL VIDRIO CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNC...

Page 2: ...peration Page 21 Step 9 Installing Logs Page 22 Step 10 Install Remove Glass Door Assembly Page 24 Step11 Burner Adjustments Page 24 Finishing Requirements Page 26 Step 12 Attaching Safety in Operatio...

Page 3: ...WER VENT DV GAS FIREPLACES DRT63__TYN DRC63__TYN INSTALLATION INSTRUCTIONS WARNING Improper installation adjust ment alteration service or maintenance can cause injury or property damage Refer to this...

Page 4: ...let and OUT for the manifold side see Figure 1 Orifice Sizes Sea Level To High Altitude These appliances are tested and approved for installation at elevations of 0 4500 ft 0 1370 m above sea level us...

Page 5: ...actured home in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 latest edition LOCATION In selecting the location the aesthetic and function...

Page 6: ...ead combustible projection of 2 1 2 64 mm or less see Figure 3 For projections exceeding 2 1 2 64 mm see Figure 3 For additional vent location restrictions refer to Figure 4 on Page 7 INNOVATIVE HEART...

Page 7: ...s 10 000 BTU hr 3kW and 100 000 BTU hr 30kW 36 91 cm for appliances 100 000 BTU hr 30kW 6 15 2 cm for appliances 10 000 BTU hr 3kW 9 23 cm for appliances 10 000 BTU hr 3kW and 50 000 BTU hr 15kW 12 30...

Page 8: ...rated 175 F or higher on the underside of the mantel MINIMUM CLEARANCES TO COMBUSTIBLES Appliance And Vent Clearances The appliance is approved with zero clearance to combustible materials on all sid...

Page 9: ...low for a minimum clearance to combustible framing members as shown in Table 5 on Page 8 If the appliance is to be elevated above floor level a solid continuous platform must be constructed below the...

Page 10: ...el No A B C D E F G H J 40 in in 50 5 8 37 1 4 42 7 8 25 5 16 34 37 5 8 33 3 32 29 9 32 34 3 4 mm 1286 946 1089 643 864 956 840 744 883 45 in in 56 11 16 42 1 4 47 7 8 28 3 8 40 1 8 43 5 8 38 3 32 34...

Page 11: ...8 59 1 8 41 7 8 mm 1286 2124 1502 1064 45 in in 56 3 4 89 7 8 63 1 2 44 7 8 mm 1441 2283 1613 1140 C Back wall of chase enclosure including any finishing materials D A B Figure 9 Corner Framing with...

Page 12: ...Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or Canada CAN CGA B149 1 latest edition These fireplaces are designed tested and listed for operation and installation only with Secure Vent SV4 5 and...

Page 13: ...1 0 8 4 0 4 1 1 0 0 0 1 1 1 2 9 4 1 4 1 0 1 0 0 1 2 1 5 9 9 4 5 2 6 1 4 0 0 0 1 0 1 1 1 4 0 5 2 4 1 0 0 1 0 1 2 1 5 1 1 5 5 2 6 2 4 0 0 0 0 1 1 1 1 5 0 2 5 5 7 3 3 4 0 2 0 1 1 1 4 1 1 3 5 5 2 4 4 0 2...

Page 14: ...x 1 2 screw may be used at the joint butitisnotrequiredasthepipewillsecurely lock when twisted C Attachventcomponentstoeachother Other vent sections may be added to the previously installedsectioninac...

Page 15: ...Secure Vent firestop spacer must be used anytime vent pipe passes through a combustible wall Maintain the horizontal inclined run in a straight slightly elevated plane approximately 1 4 per foot 20 mm...

Page 16: ...vent sections in horizontal inclined run as described in Step E Install support straps every three feet 1914 mm along horizontal inclined vent runs using conventional plumber s tape see Figure 16 on P...

Page 17: ...TE Centerline of Vent Piping is NOT the Same as the Centerline of the Frame Opening 6 to 48 Vent Section Telescopic vent section Elbow or Appliance Collar Base of Appliance 3 76 mm 1 25 4 mm Adaptor S...

Page 18: ...fireplace to the newly installed junction box near the termination Ensure the cable is safety plated to prevent damage from framing nails and finish drywall screws Route it into the lower control com...

Page 19: ...n it to fit within the junction box cover WARNING Crimp connectors may be used on stranded cables such as SJOT cable only Solid wire Romex must be connected per the National Electric Code NEC 70 lates...

Page 20: ...t only be replaced as a complete unit as provided by the manufacturer Do not attempt to replace broken cracked or chipped glass separately INNOVATIVE HEARTH PRODUCTS POWER VENT DV GAS FIREPLACES DRT63...

Page 21: ...ed above C When the gas lines are tested and leak free be sure to rinse off the leak testing solution D Re install the access plate making certain the gasket has not been damaged Figure 29 Fireplace R...

Page 22: ...able and attractive flame pattern Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion sooting and poor flame quality Logs get very h...

Page 23: ...e And Push It Towards The Rear 3 2 4 1 6 5 7 Log Number Description 1 Log Center 2 Log Rear 3 Log Center Left 4 Log Center Right 5 Log Rear Top 6 Log Front Left 7 Log Front Center Table 6 Log Set Alig...

Page 24: ...st be replaced prior to operating the appliance AVERTISSEMENT Tout cran ou pro tecteurretir pourpermettrel entretiende l appareil doit tre remis en place avant de mettre l appareil en marche Installin...

Page 25: ...nstallation Leave the ON REMOTE OFF wall switch in the REMOTE position and turn the remote switch OFF Use the remote to adjust the flame height as desired CAUTION Soot will be produced if the air shut...

Page 26: ...ed there are two methods of installation Combustible or noncombustible finish material may abut the front face of the fireplace and the floor panel see Figure 45 Combustible or noncombustible finish m...

Page 27: ...ipalement parl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 2 Rep rezlat l commandeetnettoyez lasoigneuse ment pour liminer la poussi re et les traces degraisseoud...

Page 28: ...Section 77L72 SV4 5L24 24 610mm Vent Section 77L73 SV4 5L36 36 914mm Vent Section 77L74 SV4 5L48 48 1219mm Vent Section 77L75 SV4 5LA Telescopic Section 77L76 SV4 5E45 45 Degree Elbow 77L77 SV4 5E90 9...

Reviews: