19
L.
Install Firestop/Spacer at exterior wall -
Install SV4.5HF Firestop/Spacer, provided
with the power vent kit, over the opening at
the
exterior
side of the framing, long side
up, with the 3" spacer clearance at the top as
shown in
Figure 18
, and nail into place. The
Firestop/Spacer may also be installed over
the opening at the interior side of the fram-
ing. The gap between the vent pipe and a
firestop can be sealed with noncombustible
caulking.
(The Firestop/Spacer may also be installed
over the opening at the interior side of the
framing).
M.
Install the Power Vent termination -
From
outside the exterior wall, slide the collars of
the termination onto the adaptor until the
termination seats against the exterior wall
surface to which it will be attached. Orient
the housing of the termination with the
arrow pointed upwards. Secure the termi-
nation to the exterior wall.
The termination
must not be recessed into the exterior wall
or siding
by more that the 1-1/4" (32 mm)
as shown in
Figure 19
.
Siding
Stucco
1-1/4” (32 mm) Maximum
Recess of the Square
Termination into Exterior
Finishing Material
Exterior Surface of
Framing
6” to 9-1/4”
(152
to 235 mm)**
Exterior Surface of Siding
Interior Surface of
Finished Wall
Maximum wall thickness
9-1/4” (235 mm)**
Power Vent
Termination
Maximum Extent of Vent Run
Sections Relative to Exterior
Surface of Framing
Last Vent Section.
Use Telescopic Vent
Section (SV4.5LA),
If Necessary
Adaptor
SV4.5RCH
*Use silicone caulking to
seal the top and sides of
the termination, up to the
underlayment, stucco, or
masonry wall surface.
Power Vent
Termination
*Caulk
*Caulk
To help minimize water infiltration
it is recommended that the Firestop/Spacer (SV4.5HF)
be installed on the exterior side of the wall.
Power Vent
Termination
7”
(178 mm)
5-1/8”
(130 mm)
12-1/8”
(308 mm)
NOTE: Centerline of Vent Piping is NOT
the Same as the Centerline of the
Frame Opening.
6” to 48” Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Base of Appliance
3”
(77 mm)
1”
(26 mm)
Adaptor
SV4.5RCH
10-1/2”
(267 mm)
The Power Vent termination has been
designed to perform in a wide range of
weather conditions. Terminations meet
or exceed industry standards.
When selecting the location of termination,
do not place the termination where water
from eaves and adjoining roof lines may
create a heavy flow of cascading water onto
the termination. If the termination must be
placed where the possibility of cascading
water exists, it is the responsibility of the
builder to direct the water away from the
termination cap by using gutters or other
means.
Carefully follow the Installation Instruc-
tions for the termination, including the
use of silicone caulking where required.
See Table 11 as an aid in venting component
selection for a particular range of exterior
wall thicknesses.
WARNING: The vent termination is hot
while in operation and for a period of
time following the use of the fireplace.
Young children should be carefully su-
pervised when in the same area as a hot
termination.
Figure 18 - Installing Power Vent Horizontal Termination
Figure 19 - Venting Connection and Exterior Wall Recessing of the Power Vent
Horizontal Termination
Venting Components Required for Various Exterior Wall Thicknesses
when Using the Power Vent Termination
Vent Components Required
Exterior Wall Thickness
Termination Kit Only
6 to 9-1/4" (152 to 235 mm)
Termination Kit and 6" Vent Section (SV4.5L6)
10-3/4 to 14" (273 to 356 mm)
Termination Kit and 12" Vent Section (SV4.5L12)
16-3/4 to 20" (426 to 508 mm)
Termination Kit and Telescopic Section (SV4.5LA)
and 6” vent section (SV4.5L6)
11-3/4 to 20" (299 to 508 mm)
Table 11
See
Figure 8
on
Page 12
for Minimum
Distance to Base of Appliance
INNOVATIVE HEARTH PRODUCTS • POWER VENT DV GAS FIREPLACES (DRC/DRT6340TYN AND DRC/DRT6345TYN) • INSTALLATION INSTRUCTIONS
**For thicknesses greater
than 9-1/4", see Table 11