5. ASSIGNMENT ON COMPUTER
Computer I/O
address
(hexadecimal)
Assignment
Bank change-over response register
(HML)
0
00 (Initial value)
01
02
03
Data
to
Area
(HML)
F
S-LINK input/output units
Address where Error 4
occurs
S-LINK unit connection
address
Control board product
information
(version etc.)
(HML
㧗
1) 0
Flag
(HML
㧗
1) 1
Under normal condition: number of connected S-LINK I/O units
When Error 4 occurs: first address of units where Error 4 occurs
(HML
㧗
1) 2
I/O setup of S-LINK
(HML
㧗
1) 3
Unused (=00)
(HML
㧗
1) 4
Bank change-over request register (Computer
→
Control board)
(HML
㧗
1) 5
Bank change-over response register (Control board
→
Computer)
(HML
㧗
1) 6
System set
(HML
㧗
1) 7
Frame check
Status
Area
(HML
㧗
1) 8
Number of S-LINK I/O units where Error 4 occurs
(HML
㧗
1) 9
Number of connected S-LINK I/O units
(HML
㧗
1) A
System address length
(HML
㧗
1) B
Address of SL-BS1A where operation stops
(HML
㧗
1) C
Address of connected SL-BS1A
(HML
㧗
1) D
Unused (=00)
(HML
㧗
1) E
(HML
㧗
1) F
System reserved (impossible to write in)
(HML
㧗
2) 0
Board select number
(HML
㧗
2) 1
to
(HML
㧗
3) F
System reserved (impossible to write in)
Notes: 1) For (HML) 0 to (HML) F, the contents of the assignment vary depending on the contents of the bank change-over
request register and the bank change-over response register.
2) Reading out/Writing in (HML) 0 to (HML) F must be done after the contents of the bank change-over request register
and those of the bank change-over response register match.
3) Do not write into ‘Unused’ or ‘System reserved’ locations.
6