P. 18

1-level Teaching

This sets the shift value to any desired value, and sets the ON level / OFF level 
(1_SL, 2_SL) by means of 1-level teaching (P-1).

 Output

(L-ON)

Time

Time

Time

Shift value

Shift value

Incident light

intensity

9,999

Incident light

intensity

9,999

Incident light

intensity

9,999

 Output

(L-ON)

 Output

(L-ON)

 Output

(L-ON)

* In this figure, the incident light intensity of 

P-1 is less than that of P-2.

TEACH : Teaching Mode

Refer to p. 18 ~ for setting procedure

When using hysteresis mode

A

1_SL

2_SL

B

C

0

P-1

1_SL

P-2

2_SL

0

ON

1_SL

2_SL

P-1

0

OFF

ON

OFF

ON

OFF

9,999

Threshold value

ON

1_SL

2_SL

OFF

P. 19

2-level Teaching

This carries out 2-level teaching (P-1, P-2) and sets the ON level / OFF level 
(1_SL, 2_SL).

P. 20 

l

3-level Teaching

This carries out 3-level teaching (P-1, P-2, P-3) and sets the ON level / OFF level 
(1_SL, 2_SL) between A and B as shown in the diagram below. 
After teaching, P-1, P-2 and P-3 are automatically assigned in ascending order to 
‘A’ ‘B’, and ‘C’.

This sets the ON / OFF levels with any of the 3 teaching methods (‘1-level 
teaching’, ‘2-level teaching’ and ‘3-level teaching’) and sets the hysteresis. 
By adjusting the hysteresis, the irregular sections of sensing objects with 
irregularities are canceled out so that stable sensing is possible.

8

Summary of Contents for LS-400 SERIES

Page 1: ...ns and Settings P 30 6 2 Display Switching Function P 32 6 3 Display Turning Function P 33 6 4 ECO Mode Function P 34 6 5 Period Holding Function P 35 6 6 Current Value Storage Function P 36 6 7 Stored Value Comparison Function P 37 7 PRO3 Mode 7 1 PRO3 Mode Functions and Settings P 38 7 2 Data Bank Load Function P 39 7 3 Data Bank Save Function P 40 8 PRO4 Mode 8 1 PRO4 Mode Functions and Setting...

Page 2: ...zing either 2 level teaching limit teaching or full auto teaching In window comparator mode and hysteresis mode the threshold value can be set by either 1 level teaching 2 level teaching or 3 level teaching whenever this indicator lights up Span adjustment can be carried out when using rising differential and trailing differential modes When this indicator lights up the output operation setting ca...

Page 3: ...nfiguration setting from the data bank Select only one amplifier to load or all amplifiers connected on the right side of the main unit to load in a single step by using optical communications Refer to p 39 Data bank load Saves configuration setting from the data bank Select only one amplifier to save or all amplifiers connected on the right side of the main unit to save in a single step by using ...

Page 4: ...ently confirmed If confirmation is not performed the new setting will not take effect Canceling operations 3 1 Precautions When Selecting Settings Confirming settings 1Select PRO mode 1Select response time change 2If the Jog switch is pressed the current mode red will be displayed The factory setting is STD standard 3If the Jog switch is turned the digital display red will blink Select the desired...

Page 5: ...set Function from PRO5 Mode on p 50 the resulting settings will be those indicated below Operation protection You can use the key lock function to protect these operations Refer to p 56 Key lock function This function can be used to prevent the operator from accidentally changing the sensor settings Automatic interference prevention function To operate the automatic interference prevention functio...

Page 6: ...he load The load has short circuited and excess current is flowing Confirm that all amplifiers are properly connected to each other Communication error has occurred at time of connection Check the sensor head connection status Disconnected sensor head wire error In case of errors attempt the following measures 5 ...

Page 7: ...eflective type Reflective type The incident light intensity display can display a maximum value of 4 000 in H SP ultra high speed mode and FAST high speed mode In STD standard mode and U LG ultra long range mode it can display up to a maximum value of 9 999 Confirmed Confirmed Automatic Automatic Automatic Turn to Turn When you turn the jog switch to or in window comparator mode or hysteresis mode...

Page 8: ...teaching P 1 P 2 and sets the threshold values 1_SL 2_SL Time ON P 1 1_SL P 2 2_SL 0 OFF Time Shift value Shift value ON 1_SL 2_SL P 1 0 OFF Incident light intensity 9 999 Incident light intensity 9 999 Output L ON Output L ON Output L ON In this figure the incident light intensity of P 1 is less than that of P 2 P 13 Full auto Teaching This method is used to set the threshold value while the sens...

Page 9: ...L 0 ON 1_SL 2_SL P 1 0 OFF ON OFF ON OFF 9 999 Threshold value ON 1_SL 2_SL OFF P 19 2 level Teaching This carries out 2 level teaching P 1 P 2 and sets the ON level OFF level 1_SL 2_SL P 20 l 3 level Teaching This carries out 3 level teaching P 1 P 2 P 3 and sets the ON level OFF level 1_SL 2_SL between A and B as shown in the diagram below After teaching P 1 P 2 and P 3 are automatically assigne...

Page 10: ... L ON the output turns ON when the incident light intensity is greater than the ON level 2_SL and the output turns OFF when the incident light intensity is less than the OFF level 2_SL For D ON the output turns OFF when the incident light intensity is greater than the OFF level 2_SL and the output turns ON when the incident light intensity is less than the ON level 1_SL When using hysteresis mode ...

Page 11: ...hods CUST CUSTOM Mode TIMER Timer Setting Mode Refer to p 23 for setting procedure Sensingcondition Beam received Beam interrupted Outputoperation Timer operation ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF Without Timer Light ON ON delay Dark ON Light ON Dark ON Light ON Dark ON Light ON Dark ON OFF delay ONE SHOT T1 T1 T1 T1 T1 T1 Timer period T1 Approx 1 ms to 9 999 ms OFF delay ON ...

Page 12: ...he Jog switch when in the status condition of sensing object is absent 7The incident light intensity red will again be displayed indicating that configuration is now complete 8By pressing the MODE key 5 times the amplifier will return to RUN mode normal sensing operation 5The digital display will again blink the incident light intensity reading red and the threshold value will be set to a value mi...

Page 13: ...m the left to the right and the threshold value will be shifted down by approx 15 to a value lower than the incident light intensity displayed high sensitivity If the switch is turned toward the direction the digital display will scroll from the right to the left and the threshold value will be shifted up by approx 15 to a value higher than the incident light intensity displayed low sensitivity Th...

Page 14: ...ity red will blink on the digital display and the threshold value will be set to a value midway between the incident light intensities when the sensing object is present and when it is absent 5The set threshold value green will indicate and the judgement on the stability of sensing will be displayed When stable sensing can be performed n The digital display will blink the word red When stable sens...

Page 15: ...the Jog switch Incident light intensity for P 1 Lower limit value 1_SL The symbol will be displayed repeatedly Press the MODE key 5 times If the shift value has been set to 500 Upper and lower limits have not been correctly set 1Select TEACH mode by pressing the MODE key once 2The current teaching method green and incident light intensity red will be displayed and the amplifier will enter the P 1 ...

Page 16: ...have been correctly set and the setting for lower limit value 1_SL green will be displayed If red is blinking the upper and lower limits have been set correctly If red is blinking the upper and lower limits have not been set correctly 5If the Jog switch is pressed while in the status condition when a sensing object is present that can be used as a standard for the upper limit then the display will...

Page 17: ...hat of sensing object A and sensing object C Incident light intensity 9 999 1Select TEACH mode by pressing the MODE key once 4The amplifier has entered the P 2 setting state and green will blink 6The amplifier has entered the P 3 setting state and green will blink 2The current teaching method green and incident light intensity red will be displayed and the amplifier will enter the P 1 settting sta...

Page 18: ... intensity of incident light the display will blink the incident light intensity reading red 8The display will indicate whether the upper and lower limits have been correctly set and the setting for lower limit value 1_SL green will be displayed If red is blinking the upper and lower limits have been set correctly If red is blinking the upper and lower limits have not been set correctly 9Then the ...

Page 19: ...tion as a standard Press the Jog switch Incident light intensity for P 1 The symbol will be displayed repeatedly Press the MODE key 5 times If the shift value has been set to 200 ON or OFF level have not been correctly set ON 0 OFF 1Select TEACH mode by pressing the MODE key once 2The current teaching method green and incident light intensity red will be displayed and the amplifier will enter the ...

Page 20: ...ght intensity red will be displayed 6The display will indicate whether the ON and OFF level have been correctly set and the setting for OFF or ON level 1_SL green will be displayed If red is blinking the ON and OFF level have been set correctly If red is blinking the ON and OFF level have not been set correctly 5If the Jog switch is pressed while in the status condition as a standard for the ON le...

Page 21: ...n A when incident light is the lowest intensity The status condition B when the incident light intensity is between lowest and greatest 1Select TEACH mode by pressing the MODE key once 2The current teaching method green and incident light intensity red will be displayed and the amplifier will enter the P 1 setting state 3If the Jog switch is pressed while in the status condition A when the inciden...

Page 22: ...light is the greatest intensity then the display will blink and indicate the incident light intensity reading red 9Then the setting for ON or OFF level 2_SL green will be displayed 0By pressing the MODE key 5 times the amplifier will return to RUN mode normal sensing operation OFF or ON level 1_SL green and incident light intensity red will be displayed 8The display will indicate whether the ON an...

Page 23: ...ent light intensity Output operation L ON D ON Window comparator mode ON level or OFF level 2_SL OFF level or ON level 1_SL 0 9 999 Press the MODE key twice Turn the Jog switch Press the Jog switch The digital display will quickly blink to confirm the setting Press the MODE key 4 times The current setting 9 999 Incident light intensity 9 999 1Press the MODE key twice to select the output operation...

Page 24: ...modes other than ONE SHOT timer cannot be used in rising trailing differential modes 5Set the timer period starting from the 1st digit Turn the Jog switch to set the timer period for the digit that is blinking The factory setting is 10 ms If you do not want to change the timer period you can press the MODE key to cancel the setting Timer operation is enabled 6When all digits have been set if the j...

Page 25: ...etting procedure M G S Function The receiving light sensitivity can be set in three steps four steps for U LG mode only Refer to p 28 for setting procedure Emission Halt Function This selects whether the laser is emitted or not Refer to p 29 for setting procedure Refer to p 27 for setting procedure The optimal limit of detection range Standard Capability of detecting sensing objects having a vibra...

Page 26: ...Jog switch Press the Jog switch Turn the Jog switch once toward the direction Select the desired response time by turning the Jog switch The digital display will quickly blink to confirm the setting Press the MODE key once Press the MODE key once 2Turn the Jog switch once toward the direction to select PRO1 mode 3Press the Jog switch to enter the response time change state 4If the Jog switch is pr...

Page 27: ...will be displayed The factory setting is H 02 standard 6If the Jog switch is turned hysteresis level red will blink on the digital display Select the desired hysteresis level 7If the Jog switch is pressed hysteresis level red will quickly blink on the digital display confirming the hysteresis level The digital display will not blink red if the setting has not been changed 4Turn the Jog switch once...

Page 28: ...de 9Press the MODE key once the amplifier will return to RUN mode normal sensing operation 5If the Jog switch is pressed the current shift amount red will be displayed The factory setting is 15 7If the Jog switch is pressed shift amount red will quickly blink on the digital display confirming the shift amount setting The digital display will not blink red if the setting has not been changed 6If th...

Page 29: ...he factory setting is level 3 If the response time is changed the maximum sensitivity for the mode being set is set 6If the Jog switch is turned receiving light sensitivity red will blink on the digital display Select the desired receiving light sensitivity level You can check the current incident light intensity at the instant the jog switch is turned Products manufactured after July 2004 Lot No ...

Page 30: ...key is pressed once the amplifier will return to PRO1 mode 9Press the MODE key once the amplifier will return to RUN mode normal sensing operation 4Turn the Jog switch 4 times toward the direction to select emission halt setting 5If the Jog switch is pressed the current laser emission state red will be displayed When the power is turned on laser emission is set to ON The setting is not stored 6If ...

Page 31: ...lue of 4 000 in H SP ultra high speed mode and FAST high speed mode In STD standard mode and U LG ultra long range mode it can display up to a maximum value of 9 999 Peak hold Bottom hold display This function displays the peak and bottom numerical value of the incident light intensity Percentage display This function displays the incident light intensity within a range of 0P 0 to 999P 999 based o...

Page 32: ...ndicates the peak value or bottom value within the graph area Display indicates the peak value or bottom value within the graph area When the period holding function in PRO2 mode is set to hold ON the peak hold value bottom hold value is displayed during the hold ON period Please note that the peak hold and bottom hold values will be resampled consecutively 2068 146 705 1820 Display Timing for Pea...

Page 33: ...ng 4If the Jog switch is pressed the current display switching setting red will be displayed The factory setting is No display switching 5If the Jog switch is turned display switching setting red will blink on the digital display Select the desired display switching setting 6If the Jog switch is pressed display switching setting red will quickly blink on the digital display and the selected displa...

Page 34: ...If the Jog switch is turned display orientation red will blink on the digital display Select the desired display orientation 7If the Jog switch is pressed display orientation red will quickly blink on the digital display and the selected display orientation will be confirmed The digital display will not blink red if the setting has not been changed 4Turn the Jog switch once toward the Ⳮ direction ...

Page 35: ...h 1Press the MODE key 5 times to select PRO mode 3Press the Jog switch to enter the display switching state 2Turn the Jog switch twice toward the Ⳮ direction to select PRO2 mode 8If the MODE key is pressed once the amplifier will return to PRO2 mode 9Press the MODE key once the amplifier will return to RUN mode normal sensing operation 4Turn the Jog switch twice toward the Ⳮ direction to enter the...

Page 36: ...n Period holding OFF Period holding ON 5If the Jog switch is pressed the current period holding setting red will be displayed The factory setting is period holding OFF 6If the Jog switch is turned period holding setting red will blink on the digital display Select from either period holding OFF or period holding ON 7If the Jog switch is pressed period holding setting red will quickly blink on the ...

Page 37: ...e current incident light intensity red will be displayed 7If the MODE key is pressed once the amplifier will return to PRO2 mode 8Press the MODE key once the amplifier will return to RUN mode normal sensing operation 6If the Jog switch is pressed incident light intensity red will quickly blink on the digital display and the data will be stored 4Turn the Jog switch 4 times toward the Ⳮ direction to...

Page 38: ...witch Press the Jog switch Press the MODE key once Press the MODE key once Press the MODE key once 1Press the MODE key 5 times to select PRO mode 3Press the Jog switch to enter the display switching state 4Turn the Jog switch 5 times toward the Ⳮ direction to enter the stored value comparison setting state 5If the Jog switch is pressed twice the incident light intensity green that was stored by th...

Page 39: ...en by the data bank save setting function Setting within the data bank will not be deleted even when a reset is performed using the 9 4 Setting Reset Function from PRO5 Mode on p 50 Optical communication When the collective data bank load save function or copy function is used via optical communication loading saving or copy of the setting can be carried out only to the amplifiers sub units connec...

Page 40: ...ill scroll twice When loading only the following one amplifier When loading all amplifiers in a single step 1Press the MODE key 5 times to select PRO mode 8If the Jog switch is pressed the letters red will blink 2Turn the Jog switch 3 times toward the Ⳮ direction to select PRO3 mode 3Press the Jog switch to enter the data bank load setting state 4If the Jog switch is pressed the current setting wi...

Page 41: ...nfirm the setting Channel 1 Channel 3 Channel 2 1Press the MODE key 5 times to select PRO mode 9If the Jog switch is pressed the letters red will blink 2Turn the Jog switch 3 times toward the Ⳮ direction to select PRO3 mode 3Press the Jog switch to enter the data bank load setting state 4Turn the Jog switch once toward the Ⳮ direction to enter the data bank save setting state 5If the Jog switch is...

Page 42: ...undefined only for the response time When the output signal is being received by a PLC or other device set the timer to the sensor response time or longer The incident light intensity at the instant teaching is recognized is set as the standard threshold value Notes 1 Pass the sensing object past the sensor once while an input signal is being input 2 After teaching is finished output operations ar...

Page 43: ... to confirm the setting The digital display will scroll twice Also displayed on amplifiers on which copy is done 1Press the MODE key 5 times to select PRO mode 3Press the Jog switch to enter the copy setting state 6If the MODE key is pressed once the amplifier will return to PRO4 mode 7Press the MODE key once the amplifier will return to RUN mode normal sensing operation 5If the Jog switch is pres...

Page 44: ...nfirm the setting Select from Lock ON Lock OFF by turning the Jog switch 1Press the MODE key 5 times to select PRO mode 3Press the Jog switch to enter the copy setting state 4Turn the Jog switch once toward the direction to enter the selection for transmission change to permit not to permit state 5If the Jog switch is pressed the current setting red will be displayed The factory setting is Lock OF...

Page 45: ...es to select PRO mode 3Press the Jog switch to enter the copy setting state 2Turn the Jog switch 4 times toward the direction to select PRO4 mode 4Turn the Jog switch twice toward the direction to enter the external input switch setting state 8If the MODE key is pressed once the amplifier will return to PRO4 mode 9Press the MODE key once the amplifier will return to RUN mode normal sensing operati...

Page 46: ...imes to select PRO mode 3Press the Jog switch to enter the copy setting state 2Turn the Jog switch 4 times toward the direction to select PRO4 mode 4Turn the Jog switch 3 times toward the direction to enter the backup setting state 8If the MODE key is pressed once the amplifier will return to PRO4 mode 9Press the MODE key once the amplifier will return to RUN mode normal sensing operation 5If the ...

Page 47: ...ettings Response time Hysteresis Output operation M G S External input mode Timer operation CUSTOM mode display etc are changed the changes will be reflected in the configuration and the numerical value of the code will be automatically updated Output operation Output 1 Output 2 Timer operation Response time CUSTOM Level 3 Level 2 Level 1 Level 4 STD H SP FAST U LG NON ON delay OFF delay ONE SHOT ...

Page 48: ...s However any settings that have been saved within the data bank will not be changed Please refer to the 3 2 Factory Settings on p 4 This selects one function that you would like to display in the navigation display in CUSTOM mode Refer to p 50 for setting procedure Refer to p 51 for setting procedure Refer to p 49 for setting procedure Refer to p 48 for setting procedure 0 Adjust Setting Function...

Page 49: ... enter the code setting state 5If the Jog switch is pressed the first green digit will blink 6Repeat the following motions select the code by turning the Jog switch then confirm each selection by pressing the Jog switch Once 8 digit have been input the digital display green and red will quickly blink confirming the code setting The digital display will not blink green and red if the setting has no...

Page 50: ... 0Press the MODE key once the amplifier will return to RUN mode normal sensing operation 4Turn the Jog switch once toward the direction to enter the 0 Adjust setting state 7When zero adjustment has been completed n The current incident light intensity will be displayed When zero adjustment has not been completed or has been cancelled n The amplifier will return to the 0 Adjust setting state 8If th...

Page 51: ...rd the direction Press the Jog switch Turn the Jog switch twice toward the direction Press the Jog switch Press the Jog switch 1Press the MODE key 5 times to select PRO mode 2Turn the Jog switch 5 times toward the direction to select PRO5 mode 3Press the Jog switch to enter the code setting state 4Turn the Jog switch twice toward the direction to enter the reset setting state 5If the Jog switch is...

Page 52: ...RO mode 3Press the Jog switch to enter the code setting state 7If the Jog switch is pressed the setting will be confirmed 2Turn the Jog switch 5 times toward the Ⳮ direction to select PRO5 mode 4Turn the Jog switch 3 times toward the Ⳮ direction to enter the CUSTOM mode display selection state 8If the MODE key is pressed once the amplifier will return to PRO5 mode 9Press the MODE key once the ampl...

Page 53: ...r Mode Rising differential Trailing differential Mode This is a sensing mode for setting a single threshold value and turning output ON or OFF This is a sensing mode for varying the hysteresis in order to cancel out minute changes in light intensity The teaching method can be selected from 1 level teaching 2 level teaching or 3 level teaching This is a sensing mode for setting two threshold values...

Page 54: ...Turn the Jog switch 6 times toward the Ⳮ direction to select PRO6 mode 6If the MODE key is pressed once the amplifier will return to PRO6 mode 7Press the MODE key once the amplifier will return to RUN mode normal sensing operation 3If the Jog switch is pressed the current setting red will be displayed The factory setting is normal mode 4If the Jog switch is turned the sensing mode red will blink o...

Page 55: ...method red will blink 0Turn the Jog switch to select the display units 1 level teaching only BTurn the Jog switch to set the shift amount 1 level teaching only CIf the Jog switch is pressed the shift amount setting value red will quickly blink confirming the setting DIf the MODE key is pressed once the amplifier will return to PRO6 mode EPress the MODE key once the amplifier will return to RUN mod...

Page 56: ...oward the Ⳮ direction 1Press the MODE key 5 times to select PRO mode 2Turn the Jog switch 6 times toward the Ⳮ direction to select PRO6 mode 5If the Jog switch is pressed sensing mode red will quickly blink on the digital display confirming the sensing mode 6If the MODE key is pressed once the amplifier will return to PRO6 mode 7Press the MODE key once the amplifier will return to RUN mode normal ...

Page 57: ...thers 11 1 Key Lock Function 11 Lock engaged Lock disengaged 1Keep the MODE key and the Jog switch pressed for 3 sec or more at the same time in RUN mode condition 5 will be displayed and the key lock function will be set to OFF 4To disengage the lock function keep the MODE key and the Jog switch pressed for 3 sec or more at the same time once again 3Key operations will be locked 2 will be display...

Reviews: