Warning
An AC breaker must be connected on the AC side of the inverter.
Any loads cannot be connected to the inverter without the AC breaker.
1. AC connector connection steps
① Take the AC connector out of the accessory bag and disassemble it, as shown in Figure
4-15:
Figure 4-15
Cable Gland
Threaded Sleeve
AC Terminal Head
Figure 4-16
Figure 4-17
③ Insert the stripped end of the five wires into the appropriate hole of the terminal head
by following the rules: yellow green wire to PE port, red or brown fire wires to L ports (no
requests for the sequence of three fire wires), and blue or black wire to the N port. Please
try to pull out the cable to make sure it is well connected. As shown in Figure 4-17:
② According to the table above, select an appropriate cable, peel the insulation sleeve
of AC cable off for 50mm, and peel off the end of 3L /PE / N wires for 8mm, as shown in
Figure 4-16:
Strip Length:8mm
50mm
Wire Diameter:13-18mm
Allen Key