4.13. PV Connection

Before connecting to PV panels, install a separate DC circuit breaker between the inverter and PV modules. 
In addition, we request users install PV junction boxes with surge protection to protect the system from a 

lightning strike.

To avoid any malfunction, do not connect any PV modules with possible current leakage to the inverter. 

 

For example, grounded PV modules will cause current leakage to the inverter. 

4.13.1. PV Module Selection

When selecting the PV modules, you should consider the following parameters:

1. 

Open-Circuit Voltage (Voc) of PV modules does not exceed the maximum PV array Voc. 

2. 

Open-Circuit Voltage (Voc) of PV modules should be higher than the minimum start voltage of the 

 

inverter.

4.13.2. PV Module Wiring

1.  Switch the Grid Supply Main Switch (AC) OFF.
2.  Switch the DC isolator OFF.
3.  Assemble PV input connector to the inverter.

 

 

  

WARNING

Please do not connect the PV array's positive and negative poles to the ground. This can seriously 
damage the inverter. 

Before connecting the inverter, please make sure the PV array open-circuit voltage is within the 
maximum limit of the inverter.

The correct steps in assembling the DC connector are explained below:

1. 

Strip 7mm of the plastic coating off the DC wire and 

disassemble the connector cap nut.

2.  Crimp metal terminals with crimping pliers.

3.  Insert the contact pin into the connector housing until it 

locks into place. Then screw the cap nut onto the connector 
housing. Torque to 2.5-3 N.m. 

Summary of Contents for SUNSYNK-3.6K-SG01LP1

Page 1: ...P3 SUNSYNK 3 6K SG02LP1 SUNSYNK 5K SG01LP1 SUNSYNK 5K SG01LP3 Global Tech China Ltd 3 Floor Wai Yip Industrial Building 171 Wai Yip Street Kwun Tong Kowloon Hong Kong Tel 852 2884 4318 Fax 8522884 481...

Page 2: ...Recommended DC Battery Protection 19 4 6 Connecting a Lithium Battery 19 4 7 Battery Temperature Sensor Connection 20 4 8 Connecting the AC 22 4 8 1 Recommended AC Surge Protector 23 4 9 Installing t...

Page 3: ...Setting Up a Lithium Battery 43 5 14 Program Charge Discharge Times 48 5 15 Grid Supply Page 50 5 16 Connecting the DRM s 51 5 17 Advanced Settings for Paralleling Inverters 52 5 18 Solar Power Genera...

Page 4: ...HYBRID INVERTER Installer Manual 4 APPENDIX D 65 APPENDIX E 65...

Page 5: ...from a physical or mental impairment that would affect their ability to follow this manual install maintain or repair this device Any untrained personnel who might get near this device while it is in...

Page 6: ...intenance or cleaning to reduce the risk of electrical shock The unit is not explosion proof so it should not be installed in an explosive atmosphere Never touch electrical components immediately afte...

Page 7: ...generators Compatible with wind turbines 220V single phase pure sine wave inverter Self consumption and feed in to the grid Auto restart while AC is recovering Auto earth bond feature Via a relay CON...

Page 8: ...ut with Two MPPT 3 Function Buttons 10 RS 485 Port 17 Battery 4 Battery Input Connectors 11 Generator Input 18 Temperature Sensor 5 BMS 485 Port 12 Load 19 Wi Fi Interface 6 BMS CAN Port 13 Grid 20 Fa...

Page 9: ...HYBRID INVERTER Installer Manual 9 2 1 Product Size Inverter Size Mounting bracket...

Page 10: ...mplete running system Generator or Utility PV modules Consult with your system integrator for other possible system architectures depending on your requirements This inverter can power all kinds of ap...

Page 11: ...wer 4680W Max PV Isc 17Ad c 17Ad c Utility Interactive AC Output Voltage L N PE 220 230Va c AC Output Frequency 50 60Hz AC Output Rated Current 16 4Aa c Max AC Output Current 18Aa c max Max AC Output...

Page 12: ...ut Frequency and Voltage 50 60Hz 220 230 240Vac single phase Current Harmonic Distortion THD 3 Linear load 1 5 Efficiency Max Efficiency 97 60 Euro Efficiency 96 50 Protection Integrated PV Input Ligh...

Page 13: ...Isc 17Ad c 17Ad c Utility Interactive AC Output Voltage L N PE 220 230Va c AC Output Frequency 50 60Hz AC Output Rated Current 22 7Aa c Max AC Output Current 25Aa c max Max AC Output Power 5500W AC Ou...

Page 14: ...NVERTER Installer Manual 14 4 INSTALLATION 4 1 Parts List Check the equipment before installation Please make sure nothing is damaged in the package You should have received the items in the following...

Page 15: ...gas to leak which contains suspended carbon fibre or flammable dust or volatile inflammable such as paint thinner or gasoline Areas where there may be gas leaks and where gas may settle around the un...

Page 16: ...ter Install this inverter at eye level to allow the LCD to be read anytime An appropriate ambient temperature is between 25 60 C to ensure optimal operation Be sure to keep other objects and surfaces...

Page 17: ...isconnect device is required between the battery and the inverter Switching devices may not be required in some applications but over current protectors are still required Refer to the typical amperag...

Page 18: ...se of children touching or insects go into the inverter Please make sure the inverter connector is fastened to a waterproof position by twisting it clockwise ON 1 2 CAUTION Reverse Polarity Before mak...

Page 19: ...ct with an inverter 1 Connect the correct cable diameter following the battery manufacture specifications and recommended safety devices 2 Connect a communication cable from the batteries to the inver...

Page 20: ...should be capable of controlling the batteries BMS Therefore you need to set the protocol of the BMS on both the battery and the inverter When using more than one battery the first battery will be the...

Page 21: ...HYBRID INVERTER Installer Manual 21 1 2 Temp sensor ON 1 2...

Page 22: ...A 2 pole 5kW 10AWG 6 1 2N m 40A 2 pole 32A 2 pole CAUTION All wiring and cable sizes must comply with your particular country s wiring regulations and Codes of Practices Ensure that suitable disconnec...

Page 23: ...HYBRID INVERTER Installer Manual 23 GRID GRID LOAD LOAD GEN PORT GEN PORT L N PE L N PE L N PE ON 1 2 4 8 1 Recommended AC Surge Protector...

Page 24: ...to the inverter If using an external meter you can extend the cable for more than 10 metres Plese consult the meter manual on distance 2 Connect the other end of the CT coil to the inverter terminals...

Page 25: ...e a permanent earth wire since this can cause faults with an RCD before the inverter Since the inverter is a true hybrid then the bond must only be made when the inverter is operating in Islanding Mod...

Page 26: ...METER 230V 5 60 A 800imp kWh 2 5 6 1 4 7 8 3 Inverter N L N L N L N L Grid Load GEN Grid AC Breaker System connection diagram for the CHNT meter 2 1 4 3 CHNT DDSU666 DDSU666 DIN RAIL METER 230V 5 60 A...

Page 27: ...d CT CT Home Loads Hybrid Inverter AC Breaker DC Breaker DC Breaker Do not connect this terminal when the neutral wire and PE wire are connected together E N Link This diagram is an example for applic...

Page 28: ...en Circuit Voltage Voc of PV modules should be higher than the minimum start voltage of the inverter 4 13 2 PV Module Wiring 1 Switch the Grid Supply Main Switch AC OFF 2 Switch the DC isolator OFF 3...

Page 29: ...rator 2 3 AC Breaker for gen port SUN 3 6K SG 40A AC breaker SUN 5K SG 40A AC breaker 2 Remotely control signal line B HM G V G S T ATS240V GV GS diesel generator startup signal relay coil open contac...

Page 30: ...N 1 2 ON 1 2 DC Breaker DC Breaker DC Breaker DC Breaker for battery SUN 3 6K SG 120A DC breaker SUN 5K SG 150A DC breaker AC Breaker for grid port AC Breaker SUN 3 6K SG 40A AC breaker SUN 5K SG 40A...

Page 31: ...Master inverter C Phase Master inverter ON 1 2 ON 1 2 ON 1 2 BMS 485 parallel_1 parallel_2RS485 BMS CAN DRMs Home load L3 L2 L1 N BAR E BAR AC Breaker AC Breaker AC Breaker DC Breaker for battery DC B...

Page 32: ...e value of a setting Enter Confirm setting change If not pressed each time the setting will not be saved 5 2 Switching ON OFF Once the inverter has been correctly installed and the batteries have been...

Page 33: ...ys Total daily power into the battery kWh Total daily power out of the battery kWh SOC State of charge of the battery Total daily solar power produced in kWh Total hourly usage of the generator Time T...

Page 34: ...necting the CT coil Inverter Column Showing inverter total power frequency L1 L2 voltage current and power Load Column Showing total load power load voltage and power on L1 and L2 Battery Column Shows...

Page 35: ...k on the gear icon on the right top of the navigation menu Serial number Software version Time Date and MCU What this page displays What you can do from this page Access the Basic Setup Page press the...

Page 36: ...t Time Clock To set time click on the BASIC icon and then on Time Time Date AM PM What this page displays Adjust set time Adjust set date Adjust set AM PM What you can do from this page How to set up...

Page 37: ...e To access the Settings click on the gear icon on the right top of the menu 0 0 kWh 0 0 kWh 0 0 kWh 0 0 kWh 0 0 kWh 0 0 kWh 85 BATTERY IN OUT MPPT GRID SOLAR TURBINE AC load Battery Grid Reset status...

Page 38: ...rating for AGM only For Lithium please refer to the battery manufacturer s documentation Note This is a global Max Discharge current for both grid tied and backup modes of operation If the current exc...

Page 39: ...ge that can be applied without overheating the battery Float V for an AGM battery is 55 20V Absorption V is for an AGM battery is 57 60V Equalization V for an AGM battery is 58 80V Equalizing charge o...

Page 40: ...ltage parameters A generator can either be connected to the Grid side or to the Gen connection When connected to the Grid Input the inverter will consider the power coming from the generator as Grid S...

Page 41: ...HYBRID INVERTER Installer Manual 41 5 12 Battery Discharge Page To configure inverter s shut down settings click on the BATTERY icon and then on Shut Down...

Page 42: ...erter to enter standby mode It does not entirely shut down the inverter Total shutdown occurs at voltages below 19V The voltage displayed on the Sunsynk Parity Inverter will vary depending on whether...

Page 43: ...ending on charger set points and decreases the current until the battery is fully charged Float The charging voltage is reduced to between 13 0 VDC and 13 8 VDC and held constant while the current is...

Page 44: ...s use others PLEASE NOTE With some types of lithium batteries the BMS cannot be controlled by the Sunsynk inverter In this case treat the battery as a lead acid type and set the charging and dischargi...

Page 45: ...00C RS485 1 Cut Line 3 6 8 FCIFP48100A RS485 1 SSIFP48100A RS485 1 UZ ENERGY UZ EB51 2 100ALL CAN 0 GenixGreen ESS 5120 RS485 6 ESS 10240 RS485 6 ESS BOX2 RS485 6 ESS BOX3 RS485 6 ESS BOX4 RS485 6 Sun...

Page 46: ...nection Single phase Hybrid Inverter Comm version is E41E Single phase Hybrid Inverter Comm version is 1001 E016 48NPFC100 RS485 16 48NPFC150 RS485 16 48NPFC200 RS485 16 Deye SUNB 5 0 C01 48 PC CAN 0...

Page 47: ...1400 72 8K HC CAN 0 CANL Pin 8 Blue Nova Rack Series BN52V 840 43 6K BR CAN 0 BlueNova BMAC Manu al v4 pdf BN52V 1120 58 2K BR CAN 0 Blue Nova Rackpower RacPower BN52 100 5 2K BP CAN 0 RacPower BN52 1...

Page 48: ...d next figures 1 Tick this box to not export power back to the grid the CT coil will detect power flowing back to the grid and will reduce the power of the inverter only to supply the local load 2 Tic...

Page 49: ...ery SOC drops to 50 IMPORTANT When charging the batteries from the Grid or Generator please ensure you have set the correct battery charging settings on the battery charge as shown in Section 4 10 Bat...

Page 50: ...e solar PV is prioritised to supply the Load first and then subsequently charge the battery 5 15 Grid Supply Page In the Settings menu click on the GRID icon What this page displays Grid frequency set...

Page 51: ...nstaller Manual 51 5 16 Connecting the DRM s This can be selected under advance settings This can be selected under advance settings 1 DRM 1 5 2 DRM 2 6 3 DRM 3 7 4 RDRM 4 8 5 Ref 0 6 D Ground 7 Net J...

Page 52: ...gle phase utility grid is 16 and the maximum number that can be paralleled in a three phase utility grid is 15 A A master single phase inverter is capable to operate with other 15 slaves inverters Thu...

Page 53: ...lel system must have their own isolating load breaker before it goes to the parallel breaker to ensure while programming that the load outputs are isolated from each other Only once confirmed all inve...

Page 54: ...ing one inverter in a parallel mode It can damage the inverter Q4 What are the consequences of having more than one Master Inverter or having no inverter set as Master It can damage the inverter There...

Page 55: ...nthly yearly and total solar power produced Access this page by clicking on the Solar Turbine icon on the Home Page 5 19 Grid Power This page shows the Daily Monthly Yearly and total grid power export...

Page 56: ...the maximum current depending on the voltage of the wind turbine PLEASE NOTE DO NOT use a wind turbine that exceeds 400V Use a self breaking wind turbine Once the batteries are fully charged and the i...

Page 57: ...the output Most wind turbines are three phase PM type Therefore either a wind turbine controller or a direct connec tion to the MPPT via a simple protection circuit will be required 5 21 Advanced Set...

Page 58: ...4kW Zero Export Tick this box to stop exporting power produced by the Aux Load Gen Peak Shaving Tick this box to use peak power shaving 5 22 Advanced Settings for Peak Shaving To configure Peak Power...

Page 59: ...e and indicator status displayed on the LCD with as much detail as possible 5 Owner s contact information Error Code Description Solutions F13 Working Mode Change Inverter work mode changed 1 Reset th...

Page 60: ...d to adjust the frequency on the grid set up page F48 DC bus bar voltage is too low Battery low voltage 1 Check if the battery voltage is too low 2 If the battery voltage is too low use the PV or grid...

Page 61: ...ltHigh_Fault F24 DC_Insulation_Fault F56 DC_VoltLow_Fault F25 DC_Feedback_Fault F57 AC_BackFeed_Fault F26 BusUnbalance_Fault F58 AC_U_GridCurr_High_Fault F27 DC_Insulation_ISO_Fault F59 AC_V_GridCurr_...

Page 62: ...ked that the solar panel Voc voltage does not exceed 480V and checked the battery voltage Power ON Sequence 1 Switch on AC 2 Press Start Button 3 Switch on Battery and battery breaker 4 Switch on the...

Page 63: ...ters in 3 Phase check you phase rotation before switching on the AC Load in 3 Phase the output voltage will increase across phase to 400V If using a wind turbine please ensure you have the correct lim...

Page 64: ...8 RS485B Pin 4 5 NC RS232 Pin 3 BMS transmit Computer receiver Pin 4 BMS receiver Computer transmit Pin 5 GND Pin 1 2 6 NC The following table is the connection on inverter side Protocol Description C...

Page 65: ...r We recommend the use of an RCD on all circuits and sub circuits connected to the Sunsynk Inverter Below is the specifications for a Residual Current Breaker with Overcurrent Protection RCBO Earth le...

Page 66: ...Ltd wered by Po...

Reviews: