4.6.  Using the Grid Port 

 

It looks a little complex, but it is quite simple. A few things to keep in mind:  

You  may  choose  to  connect  the  generator  to  the  grid  port.  This  is  okay  from  my 
personal experience, but not all generators are compatible, and the system will simply 
not work. 

Remember that if you are connecting the generator to the Grid port, you must fit a CT 
coil  and  set  the  Zero  Export  feature  to  around  150W.  This  will  prevent  the  inverter 
exporting power back to the generator. 

 

 

 
 

 

 
 
 
 
 
 

 

 
If using Grid port, remember you will need to make all settings to charge 
from Grid and Grid Signal rather than generator.                             

NOTICE

Summary of Contents for Hybrid Inverter with a Generator

Page 1: ...ybrid Inverter with a Generator Global Tech China Ltd 3 Floor Wai Yip Industrial Building 171 Wai Yip Street Kwun Tong Kowloon Hong Kong Tel 852 2884 4318 Fax 8522884 4816 www sunsynk com sales global...

Page 2: ...M DIAGRAM 9 3 6 POWER UP 10 3 7 SETTING UP A LITHIUM BATTERY 10 3 8 TESTING THE GENERATOR 15 3 9 CONNECTING THE ATS TO THE INVERTER 16 3 10 SOFTWARE UPDATE 18 4 PROGRAMMING THE INVERTER TO WORK WITH A...

Page 3: ...d following these instructions 2 SAFETY Use this device only in accordance with this instruction manual as well as all applicable local and national laws and regulations Only allow this device to be i...

Page 4: ...protected by a circuit breaker and operating on all wires with a distance between contacts of at least 3mm for this unit The unit must be correctly grounded and the supply line must be equipped with a...

Page 5: ...fety devices 2 Connect communication cable from the batteries to the inverter properly following the battery manufacturer specifications The cables have two ends one to be specifically connected to th...

Page 6: ...It is recommended to utilize a suitable fuse and DC isolator see next page In some applications switching devices may not be required but overcurrent protectors are still required 3 2 Connecting the L...

Page 7: ...ximum current of the array connected to each MPPT is 18Amp Before connecting to PV modules install a separate DC circuit breaker between the inverter and PV modules To avoid any malfunction do not con...

Page 8: ...r between the inverter and PV modules To avoid any malfunction do not connect any PV modules with possible current leakage to the inverter For example grounded PV modules will cause current leakage to...

Page 9: ...9 3 5 System Diagram Ensure you have used appropriate safety devices in accordance with local wiring regulations WARNING...

Page 10: ...Battery The first thing to do after the system power up is to check that the lithium battery is communicating correctly with the inverter If it is not communicating with the inverter you need to set...

Page 11: ...11 1 On the Home Page press the gear icon on the top right corner 2 Click on the Battery icon 3 On the Battery Setup screen...

Page 12: ...tp solarmd co za inv erter compatibility solarmd sunsynk and solar md SS4074 CAN SS202 CAN Freedomwon Freedom Lite Commercial 52V and HV Models CAN www freedomwon co z a storage 2019 09 free dom lite...

Page 13: ...nershare Technology BMS48150 RS485 9 PYLON 3 0 RS485 12 Murata RS485 11 GS10000 RS485 3 BPE CAN 0 ABOET CAN 0 VISION Group CAN 13 Alpha CAN 0 Backbone B LFP51 2V 100Ah and B LFP51 2V 125Ah CAN 0 Float...

Page 14: ...below a Check if your data cable is the correct type b Check if you are plugging the cable into the correct sockets Usually RS 485 is employed but some battery manufacturers use others Some types of l...

Page 15: ...to automatic 3 Plug the generator into the inverter 4 Switch all isolators on 5 Close the switch 6 The generator should start up automatically 7 Open the switch The generator should stop It is import...

Page 16: ...tly Both GV and GS can start the generator but this depends upon the setting you select GV and GS are both dry contacts N O normally open For general operation we will use the GV Terminal If you are u...

Page 17: ...17 If you are using the 8 8kW inverter then this connection would be terminals 7 8...

Page 18: ...you have it updated You can update the software in three ways 1 Wi Fi data logger 2 GSM data logger 3 Hand held programmer The easiest method is to use a GSM data logger which is simply plugged into...

Page 19: ...e data logger number and the update can be done remotely When carrying out an update please be patient as it can take some time For very experienced engineers then the update can be done using a handh...

Page 20: ...mmunicating properly 2 The inverter starts up correctly 3 The generator A T S is functioning correctly 4 The inverter s software is updated Now that you have performed all the connections and all of t...

Page 21: ...t time and date 1 On the Settings Page press the Basic icon 2 The Basic Setup page will show up on the screen 3 Touch the screen on the variable that you want to change 4 Change the number up and down...

Page 22: ...51 5 Hz or higher b Lower frequency limit 47 5 Hz or Lower c Lower voltage limit 185V d Higher voltage limit 265V The inverter will lock into the generator If the generator frequency or voltages are o...

Page 23: ...23 4 3 Setting Up the Batteries To set up your batteries click on the Battery icon on the settings page From here you can configure many settings a Select battery size if not auto set...

Page 24: ...24 b Max charge and discharge of the batteries c On the Batt Charge sub page select Gen Charge and Gen Signal...

Page 25: ...charging current This cannot exceed the maximum power of the inverter otherwise it will shut down Also you need to be aware of a C rating of the battery charge and discharge b Battery cables normally...

Page 26: ...the C Rating may only be 0 1 much lower The second step is to check if the inverter can withstand these values a 3 kW Max 50 Amp b 5 5 kW Max 80 Amp c 8 8 kW max 100 Amp e Set up generator run time a...

Page 27: ...l cause the inverter will switch o the grid but not shut down completely b Low Battery is battery warning beep c Reset is the battery level the battery needs to reach before the battery will start the...

Page 28: ...28 1 On this page you need to program the Aux port as a generator port as in the figure below 2 Then select the start stop value for the generator we suggest Start at 35 and Stop at 95...

Page 29: ...mit power to supply only the loads connected to LOAD port with Limit to Load only What you can do from this page Define a real time to charge or discharge the battery Choose to charge the battery from...

Page 30: ...30 1 Select the maxiumum power of the inverter a 3 6kW inverter maximum power 3 6kW b 5 5kW inverter maximum power 6kW c 8 8kW inverter maximum power 9kW 2 Select Zero Export and Limit to Load Only...

Page 31: ...ou are working off grid then you should prioritise the battery b If you are on grid and the generator is just a backup then prioritise the load 4 Select Use Timer This is the real time in which the in...

Page 32: ...nction will be activated Power this is the maximum power this function will control SOC this is the SOC the battery must reach Grid charge from the grid Gen charge the batteries from the generator Tic...

Page 33: ...t not all generators are compatible and the system will simply not work Remember that if you are connecting the generator to the Grid port you must fit a CT coil and set the Zero Export feature to aro...

Page 34: ...inverter c Switch off battery isolator 2 Ensure that a all cable glands are tightened b the inverter cooling system is not obscured c you have completed all mandatory cable tests do not carry out any...

Page 35: ...erters in parallel then one of the inverters can be used as a charger and another as a discharger To discharge the inverter that is used as a charger it cannot be connected to the parallel circuit Thi...

Page 36: ...36 You can watch the video for this manual in the link below https www youtube com watch v aYw2 9z0lPM Follow us on social media Sunsynk https www sunsynk org sunsynkofficial energysolutions...

Page 37: ...ing 171 Wai Yip Street Kwun Tong Kowloon Hong Kong Tel HK 852 2884 4318 Fax 852 2884 4816 Tel UK 44 151 528 9945 Tel SA 27 1108 39837 sales globaltech china com Audio Training manuals on Apple Pod Cas...

Reviews: