The main display and the external display can both display and set the parameters,
but only one can operate at one time, if the main display is in setting mode the
remote display will
Interface Setting Code
Setting Interface
Code
Default
Range
Input battery LVS
01
11.7V
11.5V~12.5V, shut down with delay 5sec. and at fixed 11V
than with delay 0 sec.(direct)shutdown
Input battery LVS
recovery
02
12.8V
12 5V~13.5V, with delay 10sec.
Charge current
03
40A
10A 15A 20A 25A 30A 35A 40A
Battery type
04
Constant charge
voltage
05
1:AGM,CV14.6V/FV13.8V
2:WET, CV14.4V/FV13.5V
3:GEL, CV14.2V/FV13.8V
4:LifePO4, CV14.4V/Not activated
5:Custom program: CV14.2V/FV13.8V
Floating
voltage
charge
06
4:LifePO4: 0V=OFF or 13.0V~14.8V
5 Custom Program 13 0 14 0V
3. TROUBLE SHOOTING:
When the product fails, there is corresponding code showed on ’2’ (see figure (1),
of the display.
CH2
CH1
AGM
Priority
PV
ERROR
Setting 1
4:LifePO4: 12.6V~14.8V
5 Custom Program 13 8V~14 8V
12.6
BATT
v
15.8
E1
INPUT
CH3