with  dimention  of  1650mm  long  and  8~10mm  wide,  4 

columns adhesive should be applied for each module. Laying 

the modules on the treated surface (see the above picture) and 

pressing  gently  against  the  tile.  In  order  to  achieve  the  best 

bonding  performance,  it  is  required  to  install  the  modules 

within 5 minutes once the adhesive is applied on the tile. 

 

5.2.3 screw mounting 

 

Drilling 5 mounting holes on the module as shown above (the 

holes’ position could be customized as per customer required). 

 

 

Fixing  the  modules  to  the  mounting  bracket  by  screws  and 

bolts,  as  shown  above.  Screwing  up  the  module  at  all  5 

positions. 

 

5.3 Electrical installation 

The  deviations  always  exist  between  the  nominal  value  and 

test  value  in  standard  test  condition  of  Rated  electrical 

characteristics of module such as Isc, Voc and Pmax, Standard 

Test  Conditions:  1000  W/m

2

  Irradiance,  25°C  Cell 

Temperature and 1.5 Air Mass, normally, the value of current 

and  voltage  generated  from  Modules  will  be  probably  higher 

than  values  under  standard  test  condition.  When  determining 

module  voltage  ratings,  conductor  current  ratings,  fuse  sizes, 

and size of controls connected to the PV output, on the basis 

of  highest  local  temperature,  combine  with  temperature 

coefficient  of  current  in  manual,  ISC  can  be  calculated  by 

multiplying by the coefficient of 1.25; On the basis of lowest 

local  temperature,  combine  with  temperature  coefficient  of 

voltage in manual, Voc. can be calculated. When modules are 

in series, voltage to be added up; when modules are in parallel, 

current  to  be  added  up.  PV  modules  with  different  electrical 

properties  can’t  be  connected  in  series,  different  electrical 

components  of  modules  may  cause  mismatch  of  electrical 

connection,  make  sure  to  install  them  in  accordance  with 

manual provided by manufacturer.   

 

5.3.1 Connection type 

The maximum number of modules that can be connected in a 

series  string  must  be  calculated  in  according  with  applicable 

regulations in such a way that the specified maximum system 

voltage  (According  to  IEC61730  tests  and  appraisal,  the 

maximum system  voltage is 1000Vdc or 1500Vdc depending 

on  the  series  and  model.)  of  the  modules  and  all  other 

electrical DC components will not be exceeded in open circuit 

operation at the lowest temperature expected at the PV system 

location. Correction factor for the open-circuit voltage can be 

calculated 

based 

on 

the 

following 

formula: 

Voc=1-βVoc×(25-T).  T  is  the  lowest  expected  ambient 

temperature at the system location. β(%/

) is the temperature 

coefficient  of  the  selected  module  Voc  (Refer  to 

corresponding datasheet). 

 

An appropriately rated over-current protection device must be 

used  when  the  reverse  current  could  exceed  the  value  of  the 

maximum  fuse  rating  of  the  modules.  An  over-current 

protection  device  is  required  for  each  series  string  if  more 

than two series strings are connected in parallel. 

Summary of Contents for SPP M60S Series

Page 1: ...the right to make changes to its products or this manual without prior notice Sunport is not responsible for any damages caused by inappropriate installation use or maintenance of Sunport modules incl...

Page 2: ...Be cautious when setting the modules down onto a surface especially on the corner of the modules 4 2 Operating safety When unpacking the modules from the original package first remove the pallet lid a...

Page 3: ...e You must stop using the module if there is exposed combustible gas nearby In the event of a fire modules may continue to produce a dangerous DC voltage even if they have been disconnected from the i...

Page 4: ...lowest edge of the modules will not be covered by snow for long time In addition ensure that the lowest portion of the modules is placed high enough so that it will not be shaded by plants or trees or...

Page 5: ...by the coefficient of 1 25 On the basis of lowest local temperature combine with temperature coefficient of voltage in manual Voc can be calculated When modules are in series voltage to be added up w...

Page 6: ...tors are fully engaged and locked 5 3 4 Bypass diodes The junction boxes used with Sunport s modules contain bypass diodes wired in parallel with the PV cell strings In the case of partial hot spot th...

Page 7: ...The installation manual applicable module types are as follows The module types are subject to changes without prior notice due to continuous product innovation research and development XXX shows the...

Reviews: