2019.01 E/0                                                                                                                              www.sunportpower.com

 

3

 

other  completely  opaque  material,  or  flipping  Modules,  and 

placing the front side of Modules onto a smooth, flat surface. 

 

In  order  to  avoid  arcs  and  electrical  shock,  please  do  not 

disconnect  electrical  connections  under  load.  Faulty 

connections  can  also  result  in  arcs  and  electrical  shock.  So 

please keep connectors dry and clean, and ensure that they are 

in  proper  working  condition.  Never  insert  any  other  metal 

objects into the connector, or modify them in any way in order 

to secure an electrical connection. 

 

Do not touch or handle modules with broken glass, separated 

frames  or  damaged  back  sheet  unless  the  modules  are 

disconnected  in  advance  and  you  are  wearing  proper  PPE. 

Avoid  handling  modules  when  they  are  wet  unless  cleaning 

the modules as directed in this manual. Never touch electrical 

connections that are wet, without PPE or insulated gloves. 

Reflection  from  snow  or  water  can  increase  sunlight  and 

therefore  increase  current  and  power.  In  addition,  low 

environmental  temperature  can  also  substantially  increase 

voltage and power. 

 

4.4 Fire safety 

Consult  your  local  authority 

for  laws  and  codes;  follow 

requirements  for  building  or 

structural  fire  safety.  Sunport’s 

modules  have  been  listed  as 

Class  C  according  to  IEC 

61730-2 

standard. 

Use 

appropriate  components  such  as  fuses,  circuit  breakers, 

grounding  connectors,  and  so  on  as  regulated  by  local 

authority. 

 

Roof constructions and installations may affect the fire safety 

of  building,  it  has  to  be  covered  by  fire-proof  material  with 

appropriate class, and make sure there is adequate ventilation 

between back sheet and installation side. In order to maintain 

the  fire  class  rating,  the  distance  between  the  modules  frame 

surface and the roof surface shall be at least 100mm; modules 

are electrical generating devices that may affect the fire safety 

of a building. 

 

Electric  arc  may  happen  when  module  working  due  to  the 

wrong  installation  method  or  defective  module  part.  Please 

keep  the  combustible  liquid,  gas  and  dangerous  cargo  away 

from  the  module.  You  must  stop  using  the  module  if  there  is 

exposed combustible gas nearby. 

 

In  the  event  of  a  fire,  modules  may  continue  to  produce  a 

dangerous  DC  voltage,  even  if  they  have  been  disconnected 

from  the  inverter,  have  been  partly  or  entirely  destroyed,  or 

the system wiring has been compromised or destroyed. In the 

event of fire, inform the fire crew about the particular hazards 

from  the  PV  system,  and  stay  away  from  the  PV  system 

during  and  after  a  fire  until  the  necessary  steps  have  been 

taken to make the PV system safe. 

 

5.INSTALLATION 

5.1 Installation condition 

Sunport’s  modules  must  be  mounted  on  buildings  or  other 

structures  suitable  for  modules  installation  (e.g.  ground. 

rooftop).  Modules  must  not  be  mounted  on  moving  vehicles 

of  any  kind;  Modules  can  be  installed  in  seaside  with  a 

distance of 50m to 500m  from  sea. Corrosion  may  happen to 

joints  between  frame  and  supporter,  or  and  grounding;  Must 

use  stainless  steel  or  aluminum  metal  to  directly  contact 

modules  in  seaside  and  do  antiseptic  treatment  on  joints  to 

prevent  corrosion;  Modules  must  not  be  installed,  nor 

operated in area with strong corrosive matter, such as salt, salt 

mist,  salt-water,  active  chemical  vapors,  acid  rain,  any  other 

type of corrosive matter. In addition, Modules must not be sit 

in locations where hail, snow, sand, smoke, air pollution, soot, 

etc.  are  excessive,  this  could  affect  the  safety  and/or 

performance of the modules. 

 

The  recommended  ambient  temperature  should  be  within  –

40°C  to  40°C.  Do  not  apply  mirrored,  magnifiers  or  other 

concentrate light onto the modules. 

 

Sunport  recommends  installing  the  modules  with  a  tilt  angle 

of at least 10 degrees, making it easier for dust to be washed 

off  by  rain  and  reduce  the  time  of  cleaning;  In  addition,  this 

will  help  to  drain  the  water  out  directly  from  the  surface, 

avoid  watermarks  from  trapping  water  on  the  glass  surface 

and affect the appearance and performance of modules. 

 

Partial  or  complete  shading  of  a  module  or  modules  can 

significantly 

reduce 

system 

performance. 

Sunport 

recommends  installing  modules  in  the  place  without  shade 

throughout  the  year  to  increase  the  amount  of  energy 

produced  by  the 

modules;  Lightning  protection  is 

recommended  for  PV  systems  that  are  to  be  installed  in 

locations with high probability of lightning strikes. 

Summary of Contents for SPP M60S Series

Page 1: ...the right to make changes to its products or this manual without prior notice Sunport is not responsible for any damages caused by inappropriate installation use or maintenance of Sunport modules incl...

Page 2: ...Be cautious when setting the modules down onto a surface especially on the corner of the modules 4 2 Operating safety When unpacking the modules from the original package first remove the pallet lid a...

Page 3: ...e You must stop using the module if there is exposed combustible gas nearby In the event of a fire modules may continue to produce a dangerous DC voltage even if they have been disconnected from the i...

Page 4: ...lowest edge of the modules will not be covered by snow for long time In addition ensure that the lowest portion of the modules is placed high enough so that it will not be shaded by plants or trees or...

Page 5: ...by the coefficient of 1 25 On the basis of lowest local temperature combine with temperature coefficient of voltage in manual Voc can be calculated When modules are in series voltage to be added up w...

Page 6: ...tors are fully engaged and locked 5 3 4 Bypass diodes The junction boxes used with Sunport s modules contain bypass diodes wired in parallel with the PV cell strings In the case of partial hot spot th...

Page 7: ...The installation manual applicable module types are as follows The module types are subject to changes without prior notice due to continuous product innovation research and development XXX shows the...

Reviews: