Installation, Commissioning and Operating Instructions 

for Renewable Energy Storage applications

 

 

RES SOPzV 2V cells - Valve Regulated Lead Acid Batteries

 

 

Assembly and CE-marking  by:     

  Date:     

 /  

/  

 

Commissioning by: 

  

  Date:     

 /  

/  

 

Number of cells: 

  

  Type:    

 

 

 

 

Safety Instructions

 

 

 

 

Usage of the battery which does not comply with the OPERATING INSTRUCTIONS, repairs  carried out with non- 
approved spare parts or unauthorized interference with the battery will invalidate any claim for warranty. 

 
 
 
 
 
 
 

 

SYSTEMS SUNLIGHT S.A.

 

 

Headquarters 

2 Ermou & Nikis Str, Syntagma Square, 105 63 Athens, Attica, Greece 

+30 210 6245400 

+30 210 6245409 

Manufacturing Plant 

Neo Olvio, 672 00 Xanthi, Greece 

+30 25410 48100 

+30 25410 95446 

Service Department 

366 Tatoiou Street, 136 73 Acharnes, Αttica, Greece 

+30 210 6245600 

+30 210 6245619 

Summary of Contents for RES SOPzV Series

Page 1: ...ply with the OPERATING INSTRUCTIONS repairs carried out with non approved spare parts or unauthorized interference with the battery will invalidate any claim for warranty SYSTEMS SUNLIGHT S A Headquarters 2 Ermou Nikis Str Syntagma Square 105 63 Athens Attica Greece T 30 210 6245400 F 30 210 6245409 Manufacturing Plant Neo Olvio 672 00 Xanthi Greece T 30 25410 48100 F 30 25410 95446 Service Depart...

Page 2: ...tically up and equally on each of the poles Never drag or roll the battery since damage will be caused Do not apply force to the safety valve during handling The batteries are fully charged before shipment Do not short circuit Check for evidence of leakage All cells with visible defects such as cracked jars loose terminal posts or other unrecoverable problems shall be rejected 2 Installation and c...

Page 3: ... correct torque loading of 22 Nm Electrical connections to the battery and between cells on separate levels or racks should be made to minimize mechanical strain on battery terminal posts For systems where the total battery voltage is measured at the controller use oversized cables to the battery in order to minimize the voltage drop Check the battery s total voltage It should match the number of ...

Page 4: ...erature stays within the allowable limits The maximum allowable discharge per cycle Max Daily DoD MDDOD is 20 for Stand alone and 60 for Hybrid systems For discharge currents lower than 0 1 C10 the MDDOD is expressed in of the C10 value For example the cell RES 6 SOPzV 850 has C10 687Ah therefore a 60 MDDoD means 413 Ah extractable per day The maximum allowable DoD MDOD is 80 of the maximum availa...

Page 5: ...r Connect the battery to the controller and leave it for 1 2 weeks while the application load is disconnected Full charge criteria are not applicable here Use the following voltage settings On off controllers 20 to 0 C 0 to 35 C 35 C High disconnect voltage Vr 2 55V 2 45V 2 40V Low restart voltage Vrr 2 35V 2 30V 2 25V Constant Voltage controllers 20 to 0 C 0 to 35 C 35 C Regulation voltage Vr 2 4...

Page 6: ...over one month Controller type Setting 20 to 0 C 0 to 15 C 15 to 35 C 35 C Constant Voltage one step Vr 2 50V 2 45V 2 40V 2 35V Constant Voltage two steps absorption maximum 2 h per day 2 55V 2 50V 2 45V 2 40V float 2 45V 2 40V 2 35V 2 30V On off High voltage Vr 2 55V 2 50V 2 45V 2 40V Low voltage Vrr 2 35V 2 30V 2 30V 2 25V For systems with oversized PV array and low MDDOD 5 use lower settings se...

Page 7: ... the minimum system voltage In Stand alone systems it is recommended to use controllers with adjustable LVD setting to the battery temperature higher LVD for lower temperature During operation the temperature difference between individual battery cells should be below 3o K 3 5 Current limits The maximum charging current during the bulk charging is 0 2 x C10 while the battery voltage is below the g...

Page 8: ...m To avoid damage periodical equalizing charging see 3 2 1 or permanent float charging has to be made 8 Transport RES SOPzV cells are protected against short circuit If properly packed batteries are no dangerous goods according to the international regulations for dangerous goods on road and on rail ADR and RID Battery Voltage in relation to DoD as a guidance for the initial LVD settings first try...