The UMCG is equipped with DO ports. On the "DO settings" interface, you can set the
status of each DO port.
S
Se
ettttiin
ng
g M
Me
etth
ho
od
d
step 1
Click "Settings" -> "DO settings" to enter the corresponding interface.
step 2
After finishing the settings, click "Save" to save the operation.
-- -- E
En
nd
d
8.6
ADC Settings
F
Fu
un
nc
cttiio
on
n D
De
essc
crriip
pttiio
on
n
On this interface, you can set the status of analog ports of the UMCG.
S
Se
ettttiin
ng
g M
Me
etth
ho
od
d
step 1
Click "Settings" -> "ADC settings" to enter the corresponding interface.
step 2
After finishing the settings, click "Save" to save the operation.
-- -- E
En
nd
d
table 8-2
Parameter description
T
Tyyp
pe
e
Z
Ze
erro
o P
Po
oiin
ntt
S
Sllo
op
pe
e
4~20mA
0~5V
Zero point "Z" in linear
conversion formula
Slope "A" in the linear
conversion formula
The linear conversion formula is Y = A × (X-Z), where Y is the target collection quantity,
X is the input analog, Z is the zero point, and A is the slope.
E
Exxa
am
mp
plle
e
A 4– 20mA PT100 thermometer is connected, where 4mA corresponds to 0℃ and
20mA corresponds to 120℃.
The target collection quantity Y is temperature, and the input analog amount X is 4-
20mA sampling current.
It is obtained by calculation that Z=4 and A=7.5.
Thus, enter 4 and 7.5 in fields zero point and slope respectively.