10 Operation of LCD Display
71
10.10 Running Parameter Setting
10.10.1 Main Screen of Run-param
Main Screen (Press
ENTER
)
→
Menu (Press
×
3)
→
Set-param (Press
ENTER
)
→
Enter
password (Press
ENTER
, Press
)
→
Run-param (Press
ENTER
)
On the “Run-param” screen, press
to
select one item and press
ENTER
to enter
the setting interface.
For each item,
Press
to move the
cursor and
Press
to set the appropriate
value.
Confirm settings by Pressing
ENTER
.
Tab. 10-4
Description of Running Parameters
Parameter
Description
Default
Range
P-Q
param
P-W limits
Inverter active power
limitation
110.0% 0~110%
Rate limit
Set the active power
change rate. When it is
set to [ON], user can set
the raise and decline
rate.
[OFF]
[OFF]/ [ON]
Power raise
When Rate limit is ON,
set the active power
rise rate.
100%/min 8~100%/min
Power Decline
When Rate limit is ON,
set the active power
decline rate.
6000%/min
8~6000%/min
Fault slowup
Set the power rise rate
when a fault is
removed. When it is
ON, the active power
raise rate can be set.
[ON] [OFF]/
[ON]
Slowup rate
Set the active power
raise rate.
100%/
min
8~100%/min
Save P-W Setting
Whether to save the
active power setting
[OFF] [OFF]/
[ON]
Save Q-Var
setting
Whether to save the
reactive power setting
[ON]
[Pt]/[Qt]/ [Off] /
[Q(P)] / [Q(U)]
Q-Var witch
Set the reactive power
regulation function
[OFF] [OFF]/
[ON]
PF
Inverter output power
factor
+1.000
-1.000~-0.800/
+0.800~+1.000
Q-Var limits
Inverter reactive power
limitation
0.0%
0~+100%/
0~-100%