n
A
Manual energy storage
handle
When the circuit breaker has no energy,
manually store energy through this button.
B
Circuit breaker state
indicator
Display the present state of the circuit
breaker, OPEN or CLOSED
C
Push OFF button
The breaker is switched off when this
button is pressed
D
Push ON button
The breaker is switched on when this
button is pressed
E
Energy storage state
indicator
Display the present energy storage state,
CHARGED SPRING or DISCHARGE
SPRING
The DC switch/AC circuit breakers can be used together with a micro-motor.
When there is the power supply on the AC side of the inverter, the energy can
be stored to the breaker through this motor. When there is no power supply on
the AC side of the inverter, manually store the energy through the manual
energy storage handle.
The operation steps are briefly described by taking the DC switch as an example.
•
Switch on
Press the Push ON button on the panel to switch on.
Before switching on, check if the energy storage state displayed on the panel is
CHARGED SPRING. If the state is DISCHARGED SPRING, store the energy manually by
turning the manual energy storage handle down until the breaker panel displays
CHARGED SPRING.