User Manual
7 Commissioning
59
3.
Country selection screen will prompt.
Perform country settings with the right two
buttons. Detailed button functions can be
found in “
10.1 Description of Button
Function
”.
Press
to choose country code.
Confirm the settings by
Pressing
ENTER
.
Refer to “
10.9.2 Selecting the Country
Code” for country code explanation. If
the inverter is installed where the country code is not included, please choose
the item “Other” and manually set the protective parameters.
If the country code is not set correctly during commissioning, reset the
protective parameters as dictated in “10.9.2 Selecting the Country Code”.
There may be faults if otherwise.
4.
(Optional)
When the country
code
“
AU
”
is selected,
Press
ENTER
to
enter the “Grid Standard” interface.
Press
/
to choose the correct grid
standard.
Press
ENTER
to confirm the choice.
5.
(
Optional
) When the country code “AU” and the grid standard “Manual”
are selected,
Press
ENTER
to enter the “Pro-Stage” interface.
Press
/
to
choose the correct stage.
Press
to move cursor and
Press
to scroll up
time value. Confirm the settings by
Pressing
ENTER
. The following figure
shows the settings of single-stage protection parameters.
Countries
Country
:
[ AU ]
Grid Standard
AG
EE
EG
PN
PC
WP
Manual
Default
Pro-Stage
Single-stage
Multi-stage
Vgrid-min 210.0V
Vgrid-max 260.0V
Fgrid-min 47.00Hz
Fgrid-max 52.00Hz