5 Electrical Connection
User Manual
34
Only the current is limited for a single input and the power is not
limited.
PV Configuration Mode-Parallel Mode
For parallel mode, all PV strings with the same type, the same number of PV panels,
identical tilt and identical orientation in series can be connected to the same single
input area.
•
SG3K6TL-S/ SG4KTL-S
Connect the 2 PV strings in parallel using T-type terminals and then connect them to
inverter DC input.
Type
Total DC Input
Power Limit
Open-circuit
Voltage Limit
Short-circuit
Current Limit
SG3K6TL-S 3900
W
600V
20A
SG4KTL-S 4300
W
600V
20A
To avoid input power unbalance of the two inputs or input
load-restriction, ensure the two PV input cables are of the same model.
•
SG2KTL-S/SG2K5TL-S/ SG3KTL-S
As shown in the following diagram.