8.2.3 Routine Maintenance
Item
Method
Period
Device Clean
Check the temperature and dust of
the inverter. Clean the inverter enclo-
sure if necessary.
Check if the air inlet and outlet are
normal. Clean the air inlet and outlet,
if necessary.
Six months to a year
(depend on the dust con-
tents in air)
Fans
Check whether there is fan warning
using App.
Check whether there is any abnormal
noise when the fan is turning.
Clean or replace the fans if necessary
(see the following section).
Once a year
Cable entry
Check whether the cable entry is in-
sufficiently sealed or the gap is exces-
sively large, and reseal the entry
when necessary.
Once a year
Electrical
Connection
Check whether all cable are firmly
connected in place.
Check whether a cable is damaged,
especially the part contacting the met-
al enclosure.
Six months to a year
8.2.4 Cleaning Air Inlet and Outlet
A significant amount of heat is generated when the inverter is working.
In order to maintain good ventilation, please check to make sure the air inlet and outlet are
not blocked.
Clean the air inlet and outlet with soft brush or vacuum cleaner if necessary.
8.2.5 Fan Maintenance
•
Power off the inverter and disconnect it from all power supplies before main-
taining fans.
•
After the inverter is powered off for 25 minutes, measure the voltage and cur-
rent with professional instrument. Only when there is no voltage nor current
can operators who wear protective equipment operate and maintain the inverter.
•
Fan maintenance must be performed by professionals.