40
Inverter Model
Open-circuit Voltage Limit
Max. current for input connector
All models
600 V
20 A
5.6.2 Assembling the PV Connectors
High voltage may be present in the inverter!
•
Ensure all cables are voltage-free before performing electrical operations.
•
Do not connect the DC switch and AC circuit breaker before finishing electrical
connection.
To ensure IP65 protection, use only the supplied connector.
step 1 Strip the insulation from each DC cable by 7 mm–8 mm.
step 2 Assemble the cable ends with the crimping pliers.
1: Positive crimp contact
2: Negative crimp contact
step 3 Lead the cable through cable gland, and insert the crimp contact into the insulator until it
snaps into place. Gently pull the cable backward to ensure firm connection. Tighten the ca-
ble gland and the insulator (torque 2.5 N.m to 3 N.m).
User Manual