32
The external protective grounding terminal must meet at least one of the following
requirements.
•
The cross-sectional area of the grounding cable is not less than 10 mm
2
for cop-
per wire or 16 mm
2
for aluminum wire. It is recommended that both the external
protective grounding terminal and the AC side grounding terminal be reliably
grounded.
•
If the cross-sectional area of the grounding cable is less than 10 mm
2
for copper
wire or 16 mm
2
for aluminum wire, ensure that both the external protective
grounding terminal and the AC side grounding terminal are reliably grounded.
The external protective grounding point provides a reliable ground connection. Do
not use an improper grounding conductor for grounding, Otherwise, it may cause
product damage or personal injury.
The grounding connection can be made by other means if they are in accordance
with the local standards and regulations, and SUNGROW shall not be held liable
for the possible consequences.
5.4.1 External Protective Grounding Requirements
All non-current carrying metal parts and device enclosures in the PV power system should
be grounded, for example, brackets of PV modules and inverter enclosure.
When there is only one inverter in the PV system, connect the external protective grounding
cable to a nearby grounding point.
When there are multiple inverters in the PV system, connect the external protective ground-
ing terminals of all inverters and the grounding points of the PV module brackets to ensure
equipotential connections to ground cables (according to the onsite conditions).
5.4.2 Connection Procedure
External grounding cable and OT/DT terminal are prepared by customers.
step 1 Prepare the cable and OT/DT terminal.
User Manual
Summary of Contents for SG2.0RS-S
Page 2: ......
Page 6: ......
Page 10: ......
Page 36: ...26 End 4 Mechanical Mounting User Manual...
Page 117: ...www sungrowpower com Sungrow Power Supply Co Ltd...