12
6 Electrical Connection
6.1 General Safety Regulations
Incorrect cable connections could damage the local controller or even
injure operators.
All cables must be undamaged, well insulated, appropriately sized, and
securely connected.
6.2 Terminal Introduction
A
B
C
D E
G
H
I
L
J
F
K
M N O
P
ETH2
ETH1
USB
SD
Debug
RST
0V 1 2 3 4 5
6 7 8 9 10 11 12 13 14 1516 0V
DIN
1 2 3
DO1
1
3
DO2
1
3
DO3
1
3
DO4
2
2
2
A1 B1 A2 B2
A3 B3 A4 B4
A5 B5 A6 B6
+ -
GND
PT1
+ -
GND
PT2
+ -
AI1
+ -
AI2
+ -
AI3
+ -
AI4
H L
CAN
+ -
24V
AC(L) AC(N)
GPS/BDS
RF
L1
L2
DO
1
2
3
NO
NC
COM
Tab. 6-1
Terminal description
Item
Remark
Name
Description
A
ETH1/ETH2
Ethernet port
ETH2 can be connected to local
controller via the switch, router, and
other devices; and ETH1 is used for
lower-layer
devices
(can
be
connected to BCP, PCS, and the
like)
B
DIN
Digital input
Node input port
DIN1: Not assigned
DIN2: Emergency stop node
DIN3-DIN5: Not assigned
DIN6-DIN13: Optional
DIN14-DIN16: Not assigned
C
USB-HOST
USB interface
Software upgrade interface
Summary of Contents for EMS200
Page 1: ...EMS200 V12 UEN Ver11 201812 EMS200 Local Controller User Manual...
Page 2: ......