BEEP Beeper fault warning
When system has fault (temperature sensor fault, no flow etc), beeper sends out warning
Menu Structure
Main
menu
Sub
menu
1
Subm
enu
2
Factor
y set
Adjustable
range
Step
per
adjust
Description
AUX
Auxiliary functions
TIME
OFF
ON/OFF
Timer function
t 1O
00:00
00:00-23:59
Start time of the first time section
t 1F
00:00
00:00-23:59
Close time of the first time section
t 2O
00:00
00:00-23:59
Start time of the second time section
t 2F
00:00
00:00-23:59
Close time of the second time
section
t 3O
00:00
00:00-23:59
Start time of the third time section
t 3F
00:00
00:00-23:59
Close time of the third time section
AH
OFF
ON/OFF
Thermostat function
AHS
S3
S2/S3/S5
Allocated sensor for thermostat
function (S3 for T3, S2 for T2,
S5 for
T5)
AHO
40
℃
0.0-95
℃
0.5
℃
Switch-on temperature
AHF
45
℃
0.0-94.5
℃
0.5
℃
Switch-off temperature
t A1O
00:00
00:00-23:59
Start time of the first time section
t A1F
23:59
00:00-23:59
Close time of the first time section