SUNFAR C300 43
C300 series of non-sensor current vector-control inverter manual
FWD-GND
[F0.6]
Direction
OFF
# # 1 #
FWD
ON
# # 1 #
FWD
OFF
# # 0 0
FWD
OFF
# # 0 1
REV
ON
# # 0 0
REV
ON
# # 0 1
FWD
When setting freq. is lower than lower limit freq., the inverter will run in lower limit
freq. But the parameters F4.8 and F4.9 are priority over F0.7 and F0.8.
Acc time 1 is the time of output frequency accelerating from 0.0 Hz to 50.00Hz.
Dec time 1 is the time of output frequency decelerating from 50.00 Hz to 0.00Hz.
Units of Acc and Dec are set by parameter F0.12.
The first part of LED(form right to left)
:
It is used for setting curve type when
inverter is accelerating or decelerating, shown as fig6-3.
0
:
Beeline
Output freq. of inverter will increase or decrease according to fixed rate.
1
:
S curve
Output freq. of inverter will increase or decrease according to graded rate.
Characteristics of S curve are set by parameter F0.13 and F0.14.
The second part of LED
:
To set Acc/Dec method
0
:
Output freq. will be modified according to Acc/Dec time.
1
:
Output freq. will be automatically modified according to lode.
The third part of LED
:
It is used for setting unit of Acc/Dec time, namely unit of
parameters F0.10, F0.11, F4.17, F4.18, F4.19, F4.20, F4.21 and F4.22.
0
:
Sec. 1
:
Minute
The fourth part of LED
:
Reserved.
F0.9 Reserved
F0.7 The lower limit frequency
Setting range
:
0.0 ~ [F0.8] Hz
F0.8 The upper limit frequency
Setting range
:
[F0.7] ~ 400.00Hz
F0.10 Acc time 1
Setting range
:
0.1 ~ 6000 Sec/Min
F0.11 Dec time 1
Setting range
:
0.1 ~ 6000 Sec/Min
F0.12 character parameter of Acc and Dec Setting range
:
0000 ~ 0111