C300 series of non-sensor current vector-control inverter manual
5. PARAMETERS LIST
means that this parameter can not be changed during operation.
★
▲
means that this parameter is related to the inverter’s model.
Parameters’
Types
Function Code
Name
Setting range
Minimum
Setting
Manufacture
Setting
Modify
Limit
F0. 0
Control methods
0
:
V/F method
;
1
:
Vector control
1
1
★
F0. 1
Frequency input channel
/ mode selection
0
:
Frequency setting by operation panel
1
:
UP/DW
Acc and Dec control
2
:
RS485 interface
3
:
Panel potentiometer
4
:
External voltage signal VC
(
0V~10V
)
5
:
External current signal CC
(
0~20mA
)
6
:
Combination setting
7
:
External terminals
1 0
F0. 2
Frequency digital setting
0.00 ~ the upper limit frequency
0.01
0
F0. 3
Auxiliary control
of freq. digital
setting
The first part of LED(form right to left)
:
0
:
Setting freq. will save after power
down
1
:
Setting freq. will not save after power
down
The second part of LED
:
0
:
Setting freq. is keep when stopping
1
:
Setting freq. will save in F0.2 when
stopping
2
:
Setting freq. isclear when stopping
The third and fourth part of LED(form
right to left)
:
Reserved
1 0000
B
a
sic
o
p
er
at
io
n p
a
ram
e
te
r
uni
t
F0. 4
Operation
Channel selection
The first part of LED (form right to left):
0
:
Panel control
1
:
External terminals
2
:
RS485 interface
The second part ofLED
:
Function of key
STOP
0
:
It is valid for panel control.
1
:
It is valid for all kinds of control
method.
The third and fourth part of LED(form
right to left)
:
Reserved
1 0000