No. of
Parameter
Name of
Parameter
Setting
Option
Description
14
Battery
undervoltage
alarm point
[14] 44V
default
So as to battery undervoltage alarm point, when the
battery voltage is lower than the judgement point,
an undervoltage alarm is given out and no turnoff is
output. 40V~52V setting range at 0.4V step is valid
in case of a self-defined and lithium battery.
15
Battery
discharge
limiting
voltage
[15] 40V
default
So as to battery discharge limiting voltage, when the
battery voltage is lower than the judgement point,
the output is turned off immediately. 40V~52V
setting range at 0.4V step is valid in case of a self-
defined and lithium battery.
16
Equalizing
charge
[16] DIS
No equalizing charge is permitted.
[16] ENA
default
When equalizing charge is enabled, only vented
lead-acid battery and sealed lead-acid are valid.
17
Equalizing
charge
voltage
[17] 58.4V
default
So as to equalizing charge voltage, 48V~58.4V
setting range at 0.4V step is valid in case of a vented
lead-acid battery and sealed lead-acid battery.
18
Equalizing
charge time
[18] 120
default
So as to equalizing charge time, 5min~900min
setting range at 5min step is valid in case of a
vented lead-acid battery and sealed lead-acid
battery.
19
Equalizing
charge delay
[19] 120
default
For equalizing charge delay, 5min~900min setting
range at 5min step is valid in case of a vented lead-
acid battery and sealed lead-acid battery.
20
Equalizing
charge
derating time
[20] 30
default
For equalizing charge derating time, 0~30days
setting range at 1-day step is valid in case of a
vented lead-acid battery and sealed lead-acid
battery.
21
Equalizing
charge
enabling
[21] ENA
Start equalizing charge immediately.
[21] DIS
default
Stop equalizing charge immediatel.
22
Energysaving
mode
[22] DIS
default
No energy-saving mode
[22] ENA
After enabling the energy-saving mode, in case of
empty or small load, the output is turned off after
output delaying of inverter for a certain period of
time. After the rocker switch is pressed to
“
OFF
”
state and then to
“
ON
”
state, the inverter restore
the output.
23
Automatic
restart after
overload
[23] DIS
When the automatic restart after overload is
disabled, if the output is turned off upon overload,
the machine shall not restore turnon.