background image

1

Temperature Switch

Heater-On

Out1

LT Cutout

Out2

2

3

4

5

6

7

8

9

10

11

A

H

O

UL Listed

Ground Fault

Circuit Breakers

(by others)

Field Wiring

(by others)

10' long

Sensor Lead

For 120V / 277

Applications

120V Input

For 208V / 240V

Applications

Ambient

Sensor

Bulb

L

N

L1

L2

L

N

To

Heater

Circuit

To

Heater

Circuit

To Heater Cable

Ground Braid

(Typical)

Ground

Bar

Ground

Factory

Wiring

A1

A2

X1
X2

H-O-A

Switch

Enclosure

L

Heater On Indicator Lamp

Multi-Circuit All-Contactor

Digital Controller

Switches 120V/208/240/277V 30A branch circuits,

wire per example as shown

Available in 4-, 8-, and 12-circuit configurations

NEMA Type 4/12 enclosure. Short circuit current: 5kA rms symmetrical, 480V Max.

Circuit 1: 120V 10A

protected circuit

breaker to be

provided by installer

Circuits 2 - 13: 30A, 30mA

ground fault equipment

protection circuit breakers to

be provided for each circuit by

installer (typical)

A1

A2

X1A

X2

X1A

X19

X19

X19

X19

X1

X1A

X19

X2

(Typical)

A1

A2

Ground Bar

Sized as

Required

xxx

Turn off all power before servicing

panel or branch circuits

CAUTION

HIGH VOLTAGE

DANGER

Note: Locate sensor on the coldest exterior side of structure (usually
north) under the overhang and not exposed to heat sources such as
sunlight, heating vents, etc. If using extension wiring for remote
placement of sensor bulb, use copper extension wire, 300Vac rated
insulation:

16 gauge up to 60' max.

14 gauge up to 120' max.

12 gauge up to 240' max.

10 gauge up to 480' max.

Important: DO NOT exceed maximum extension wire length

versus wire gauge

!

Terminals A1, A2, X1, X2:

Torque at 4.4-7.1 lb In.

Use copper conductors only with a

temperature rating of 60° F. for

terminals rated less than 100

amperes, and a temperature rating of

75° F. for terminals rated for 100

amperes or higher

Summary of Contents for 4CDC+

Page 1: ... 120Vac to 277Vac and EverClear 812 and 822 120Vac to 277Vac self regulating heater cables by energizing multiple 4 8 or 12 individual branch circuits via adjustable control values as set on the temperature controller The Controller provides a set point for on off operation as well as a low temp cutout of the circuits The low temp cutout shuts the system off when temperatures are so cold that no s...

Page 2: ...A 4 12 rating so they may be mounted indoors or outdoors typically near the circuit breaker panel Each branch circuit must be protected by a ground fault protection device per the NEC A 120Vac protected circuit is required to energize the controller The ambient sensor is mounted outdoors in a shaded location representative of minimum ambient conditions typically on the north side of a building and...

Page 3: ...ndicator light under out2 will appear 4 Press the UP or DOWN arrow button to adjust the value Hold button to scroll 5 Press the SET button again to return to the normal operating mode will display the current sensed temperature with no decimal point Low Temp Cutout can effectively be avoided by setting its value below the lowest expected ambient temperature for example 50 0 NOTE Multi Circuit cont...

Page 4: ...2 13 30A 30mA ground fault equipment protection circuit breakers to be provided for each circuit by installer typical A1 A2 X1A X2 X1A X19 X19 X19 X19 X1 X1A X19 X2 Typical A1 A2 Ground Bar Sized as Required xxx Turn off all power before servicing panel or branch circuits CAUTION HIGH VOLTAGE DANGER Note Locate sensor on the coldest exterior side of structure usually north under the overhang and n...