background image

   

Summit Ice Melt Systems

PO Box 6928, Tahoe City, CA 96145
Ph: 530-583-8888 

summiticemelt.com

Multi-Circuit Ambient Temp Sensing Digital Controllers

Operation

The Multi-Circuit Controller uses a thermistor to sense ambient temperatures. When the
temperature drops below the Heater-On set-point, the system is energized. When the
temperature rises above the Heater-On set-point, the system is de-energized. 

If the temperature drops below the low-temp cutoff, the system is de-energized. When
the temperature rises above the low-temp cutoff, the system is energized. 

The 3-position rocker switch allows the operator to set the system in Automatic,
Manual, or Off mode (center position). When the rocker switch is set to the MANUAL
position, heaters are energized, regardless of ambient conditions.

Installation

The Multi-Circuit Controller enclosures vary in size to accommodate the number of
circuits controlled. The enclosures are NEMA 4/12 rating so they may be mounted
indoors or outdoors, typically near the circuit breaker panel. Each branch circuit must be
protected by a ground fault protection device per the NEC. A 120Vac protected circuit is
required to energize the controller.  

The ambient sensor is mounted outdoors in a shaded location representative of
minimum ambient conditions (typically on the north side of a building), and away from
any heat source, such as direct sunlight or a utility room exhaust vent, so that the
temperature sensor gives an accurate reading of the air temperature reflective of actual
ambient conditions. The ambient sensor comes with a standard 10 ft lead, but its range
can be extended up to hundreds of feet using ordinary stranded copper wire. See
schematic diagram for details.

Pre-Season Testing

The heater circuits may be energized and tested for proper functionality prior to the cold
weather season by simply setting the 3-position rocker switch to Manual. Amperage
readings may then be taken on each branch circuit.  Amperage will depend on ambient
temperature and time. Follow heater manufacturer test procedures.

Summary of Contents for 4CDC+

Page 1: ... 120Vac to 277Vac and EverClear 812 and 822 120Vac to 277Vac self regulating heater cables by energizing multiple 4 8 or 12 individual branch circuits via adjustable control values as set on the temperature controller The Controller provides a set point for on off operation as well as a low temp cutout of the circuits The low temp cutout shuts the system off when temperatures are so cold that no s...

Page 2: ...A 4 12 rating so they may be mounted indoors or outdoors typically near the circuit breaker panel Each branch circuit must be protected by a ground fault protection device per the NEC A 120Vac protected circuit is required to energize the controller The ambient sensor is mounted outdoors in a shaded location representative of minimum ambient conditions typically on the north side of a building and...

Page 3: ...ndicator light under out2 will appear 4 Press the UP or DOWN arrow button to adjust the value Hold button to scroll 5 Press the SET button again to return to the normal operating mode will display the current sensed temperature with no decimal point Low Temp Cutout can effectively be avoided by setting its value below the lowest expected ambient temperature for example 50 0 NOTE Multi Circuit cont...

Page 4: ...2 13 30A 30mA ground fault equipment protection circuit breakers to be provided for each circuit by installer typical A1 A2 X1A X2 X1A X19 X19 X19 X19 X1 X1A X19 X2 Typical A1 A2 Ground Bar Sized as Required xxx Turn off all power before servicing panel or branch circuits CAUTION HIGH VOLTAGE DANGER Note Locate sensor on the coldest exterior side of structure usually north under the overhang and n...

Reviews: