background image

3

The filter frame shall be installed on the side of the cabinet selected for the return 

air to enter the furnace; either side  or bottom. NOT IN BACK OF CABINET.

Four knockouts are provided on each of the two sides and bottom of the furnace 

to locate R/A opening.

 

FEATURES

All models are completely pre - wired.

All  “  field  “  wiring  shall  be  completed  by  the  Installer  to  the  terminal  block 

provided on the main control board in the furnace.

 

INSTALLATION CLEARANCES FURNACE

As shipped the ALPHA series furnaces are Certified for “ZERO” clearance.

To  facilitate  servicing  the  unit,  the  “Front”  clearance  should  be  a  minimum 

of 24”.

OPERATING SEQUENCE

HEATING 

The  thermostat  closes  the  R-W1/W2  circuit,  -  activating  the  controller  and 

elements one by one. The blower starts at low speed at the same time as the first 

two elements come on.

Blower speed increases as the other elements turn on.

Furnace is factory set in modulation mode.

If modulation has been selected at the controller, the blower speed with adjust 

automatically to maintain the factory set discharge air temperature.

If  modulation  has  not  been  selected,  the  blower  will  run  at  the  factory  set 

heating speed.

When  the  thermostat  is  satisfied,  all  elements  turn  off  at  once  and  the  blower 

continues to run until either the preset discharge  temperature is met or 1 minute, 

which ever occurs first.

Refer to fig.2 to select modulation.

Position 1 on switch SW2 turns heating modulation on and off.

COOLING 

The thermostat closes the R-Y/G circuit,

thereby activating compressor relay. The blower starts at cooling speed. 

Furnace is factory set in modulation mode.

If modulation is selected at the controller, the cooling  sequence starts first at high  

speed  blower  for  approximately  7  minutes  (sensible  mode)  followed  by 

approximately 7 minutes of lower speed blower (latent mode). This sequence repeats.

If modulation is deselected, cooling speed is fixed at high speed.

Refer to fig.2, SW2 position 2 to turn modulation ON or OFF.

Summary of Contents for ALPHA

Page 1: ...installer and where required by law a licenced technician FOR SERVICE CALL INSTALLATION INFORMATION _________________ _________________ Qualified Contractor Telephone Number _________________ _________________ Unit Model Number Unit Serial Number _________________ Date of Installation MANUFACTURED BY SUMMERAIRE MANUFACTURING EXCLUSIVELY FOR IMPACT DISTRIBUTION ...

Page 2: ...the requirements Canadian or U S A National Codes These electric furnaces require 120 240 vac 1 phase 60 Hz 3 wire power supply C W neutral LOCATION The furnace shall be centrally located in relation to the outlet registers with suitably sized warm air ducts for improved heat distribution MULTI POSITION Alpha series electric warm air furnaces can be installed for vertical horizontal or down flow op...

Page 3: ...ace is factory set in modulation mode If modulation has been selected at the controller the blower speed with adjust automatically to maintain the factory set discharge air temperature If modulation has not been selected the blower will run at the factory set heating speed When the thermostat is satisfied all elements turn off at once and the blower continues to run until either the preset discharg...

Page 4: ... to control the electric elements of the second stage Also the wire jumper on the main control positions W1 W2 must be removed The CONTINOUS FAN switch turns the blower on to continuous LOW speed This feature will filter the air and provide for better distribution in the building CAUTION It is important to check airflow and make sure that the furnace does not operate above the temperatures specified ...

Page 5: ...s etc Follow the instructions that are supplied with the thermostat 1 stage electric heating only 2 stage electric heating only 1 stage thermostat with outdoor control for 2 stage function electric heating only 2 stage thermostat electric heating and air conditioning 1 Stage Thermostat Electric Heating Only When a digital thermostat is used set this function to Gas or Oil Furnace ELEMENT RELAY SUB...

Page 6: ...ic clip provided Refer to fig 6 A C COIL INSTALLED UPSTREAM OF FURNACE OPTIONAL RETURN AIR SENSOR Recommended for Heat Pump applications The following must be observed when the A C coil is installed upstream of the furnace Locate air filter upstream of A C coil The return air temperature must be monitored to permit the controller to function To do this the return air sensor must be installed in the ...

Page 7: ...nabled SW2 positions 1 and 2 labeled MOD will select modulation options DO NOT CHANGESWITCH POSITIONS 3 to 6 In the tables below a switch ON is represented by a value 1 while a switch OFF is represented by a value 0 The following tables highlight valid selection for each furnace size Switch Old New Position Relay Relay Two Element Furnace 0100 1 3 1100 1 4 0010 1 5 1010 1 6 0110 2 3 1110 2 4 0001 ...

Page 8: ...110 2 4 0001 2 5 1001 2 6 0101 3 4 1101 3 5 0011 3 6 1011 4 5 0111 4 Switch Old New Position Relay Relay Four Element Furnace 0010 1 5 1010 1 6 0001 2 5 1001 2 6 1101 3 5 0011 3 6 1011 4 5 0111 4 6 Switch Old New Position Relay Relay Five Element Furnace 1010 1 6 1001 2 6 0011 3 6 0111 4 6 ...

Page 9: ...9 Fig 2 MAIN CONTROL BOARD ...

Page 10: ...LED the front control cover must be removed This sequence should only be performed by a qualified contractor WARNING HIGH VOLTAGE IS PRESENT IN THE CONTROL COMPARTMENT SERIOUS INJURY OR DEATH MAY RESULT IF PROPER PRECAUTIONS ARE NOT FOLLOWED Fault Number Element LED Resulting Condition Flashes Flashes Controller Action Excessive fan 1 none All outputs turned off motor amp draw Alarm relay on Alarm ...

Page 11: ...11 Fig 4 ...

Page 12: ...ng contractor so as to be of sufficient strength to support furnace and accessory fittings and materials Non combustible base required Return air knock out NOTE Field selected suspension materials must be sized by the installing contractor and be of sufficient strength to support air handler weight of 100 lbs and connected accessory fittings and materials Minimum 1 x 1 x 1 8 angle Horizontal Installat...

Page 13: ...t using nylon strap included Air Filter A C Coil drain must be trapped Discharge sensor lead and low voltage lead wires shall be isolated from high voltage leads and routed through knockouts provided Discharge sensor lead and low voltage lead wires shall be isolated from high voltage leads and routed through knockouts provided Drill 3 8 dia hole in warm air duct a minimum of 15 upstream of plenum ...

Page 14: ...FULL AMP DRAW AT FULL POWER 6 CANCEL CALL FOR HEAT ELEMENT LEDS TURN OFF APPROXIMATELY 1 MINUTE LATER FAN TURNS OFF PROVIDED THAT CONTINUOUS FAN HAS NOT BEEN SELECTED 7 INTERRUPT POWER TO OUTDOOR CONDENSOR INITIATE CALL FOR COOLING ONCE FURNACE FAN IS RUNNING CONFIRM 24 VOLT OUTPUT AT Y AND C AT COMP RELAY RECONNECT POWER TO CONDENSOR IF TEST SUCCESSFUL NOTE MAIN CONTROL DELAY INTERVAL BETWEEN COO...

Page 15: ... BOARDSE6 5 ELEMENT PLATE 2 ELMPLTE 6 ELEMENT 2 ELEMENT3 2 ELEMENT4 2 ELEMENT5 7 LED PANEL 2 PANLED 8 SELECTOR SWITCH 2 SWITCHRCKR 9 FAN MOTOR 2 MTRDDO25 1 3HP 2 MOTOR5845A 10 MOTOR CAPACITOR 2 CAP370V5MF 1 3HP 2 CAP370V15MF 3 4HP 11 BLOWER 2 BLOWER10208 2 BLOWERGT1210 CAPACITOR BOOT not shown 2 CAPBOOT CIRCUIT BREAKER not shown 2 BRKR16A ...

Page 16: ... CIRCUIT AMPS 60 85 100 110 125 150 BREAKER SIZE AMPS 60 90 100 125 125 150 MOTOR H P SPEEDS 1 3 HP 3 SPEED 3 4 HP 3 SPEED BLOWER AIRDEX 1020 800 5 DELHI GT12 10 GENERAL INFORMATION DIMENSIONS WIDTH x DEPTH x HEIGHT 20 W x 21 D x 36 H RETURN AIR PLENUM 18 1 2 x 18 1 2 WARM AIR PLENUM 15 x 18 AIR FILTER 1 REQUIRED 20 x 20 x 1 SHIPPING WEIGHT 48 KG 105 Lbs AIR CONDITIONING UP TO 3 TONS UP TO 5 TONS ...

Page 17: ...17 MANUFACTURED BY SUMMERAIRE MANUFACTURING EXCLUSIVELY FOR IMPACT DISTRIBUTION Revised 09_18_07 ...

Reviews: