6-1
Chapter 6
Functions of Analog Input/Output
6.1 About this chapter
This chapter contains the information about the inverter setting parameters related to this product.
6.2 Terminal connection
An example of terminal connection of P1-AG is as follows.
・
Wiring the P1-AG, make sure that use the twisted pair cable with shield. In case of improper wiring, the
inverter may malfunction caused by external noise. Make sure that the shield is wired to L terminal or
Ground terminal of the inverter. Additionally, do not be multipoint ground.
・
Make sure that length of wiring to P1-AG must be 20 m or less. In case the length is more than 20 m, the
inverter may malfunction caused by external noise.
・
Make sure of wiring the FG terminal to functional ground.
Vi4
Vi5
Vi6
Vo5
Io4
So3
So4
L
Ii5
Si5
L
P1-AG terminal block
(+)
(-)
(±10V)
(0V)
Analog Input 4 voltage
Analog Input 5 voltage
Analog Input 6 voltage
Analog Input 4 switch
Analog Input 5 switch
Analog Input 4 current
Analog Input 5 current
Analog Output 3 voltage
Analog Output 3 switch
FG
Si4
L
L
Ii4
(+)
(-)
L
L
(+)
(-)
L
(+)
(-)
L
L
L
Io3
L
L
Vo4
L
Vo3
L
Analog Output 4 voltage
Analog Output 5 voltage
Analog Output 3 current
Analog Output 4 current
Analog Output 4 switch
6
Chapter 6
Function of Analog
Input/Output