Table 4-4: Parameters
Type
Enable
Default
Min
Max
Display Text
Comment
Setup
Always
1
0
2
Press Tran
200,250,500, 750
Setup
X200
135
50
225
P1 Max
250psi transducer
Setup
X250
135
50
195
P1 Max
200psi transducer
Setup
X500
250
150
495
P1 Max
500psi transducer
Setup
X750
400
300
560
P1 Max
750psi transducer
Setup
Always
0
0
1
Water Switch
Water pressure switch enable for water
cooled machines
Setup
Flooded
0
0
1
OilSwitch
Oil switch enable for flooded screw
machines
Setup
Always
65
20
200
Min Load Psi
Minimum acceptable Loaded P1 value
Setup
Always
0
0
30
Stop Timer
If not 0, run unloaded for this time before
stopping
Setup
Always
0
0
30
Lube Cycle
Prelube/Postlube time
Setup
Always
0
0
2
K8 Option
Disable, Lube Pump, Master Control
Setup
Always
0
0
100000
Load Hours
Hours machine has been loaded
Setup
Always
0
0
100000
Run Hours
Hours machine has been running
Setup
Always
0
0
100000
Load Cycles
Number of load cycles
Setup
Always
0
0
100000
Starts
Number of starts
Setup
Always
0
0
10000
Capacity
Used by monitor to determine system load
Cal
Always
0
-7
7
P1
Cal
Always
0
-7
7
P2
Cal
Always
-20
10
dP1
Cal
Always
0
-7
7
P3
Cal
Always
0
-7
7
P4
Cal
Always
0
0
1
Fault on Warn
Force shutdown on warning
User
X200
110
30
220
Unload
250psi transducer unload pressure
User
X250
110
30
185
Unload
200psi transducer unload pressure
Summary of Contents for SUPERVISOR CONTROLLER
Page 8: ...NOTES 6...
Page 15: ...13 NOTES...
Page 16: ...SUPERVISOR CONTROLLER USER MANUAL SECTION 2 14 Table 2 1 Supervisor Controller Menu Tree...
Page 18: ...16 NOTES...
Page 30: ...28 NOTES...
Page 31: ...Section 5 29 SUPERVISOR CONTROLLER USER MANUAL WIRING DIAGRAMS...
Page 51: ...NOTES...