SRL Service Manual
Revision 00
July 2007
Page 32 of 56
7.3 Accessing & Modifying User Parameters
To access the User Parameters:
•
Press the
Alarm Reset & Alarm Report
buttons
simultaneously.
The display will show you are at Parameter “A1”.
To view and modify the User Parameters:
•
Press the
Up
or
Down
buttons to scroll through the parameters.
•
When you get to the parameter you want, press
Enter
to see it’s value.
•
Press the
Up
or
Down
buttons to modify it’s value
(1)
.
•
Press
Enter
to save your changes
(2)
.
•
Press
Exit
to leave the parameter
(2)
.
(1) Parameters B3, B7 & B9 are passcode protected and cannot be changed or reset without the proper
code. Contact Sullair for further information.
(2) If you press Exit without first pressing Enter to save your changes, you will exit without saving and the
parameter will revert to it’s previous value.
Note that once inside the parameters menu, the meaning of the buttons is different from the standard
operation. (See section 3.2) It is not possible to:
•
Turn the dryer On or Off
•
Reset a warning or alarm
•
Display the alarm report
•
Activate the drain valve
Once in the parameters menu, if the user does not press any button for 5 minutes, the controller will
exit the menu and return to standard operating mode.
To exit the parameter menu and return to the standard operating mode, press Exit.
When in standard operating model the display will show either:
•
“OFF” when the dryer is OFF,
•
“r.OF” with dryer is in Remote OFF mode,
•
the dew-point temperature when the dryer is ON and has no alarm, or
•
the alarm or warning code if the dryer is ON and has an alarm or warning.
&
or
or
or