09
10
CRC1200
CRC1200
Use UP/DOWN keys to set desired value.
0 = Compressor Continuous ON.
1 = Compressor in Time Delay.
(20Min ON / 4 Min OFF)
2 = Compressor is OFF.
To set compressor function
during room probe failure.
COMP ON PROBE FAIL
11
Function: To set Compressor function
during room probe failure.
0
2
1
Range
Min
Max
Fact. Set
EVAP TIME DELAY
14
To change Evap Fan Stop Tc
parameter, press the set key.
O
-40 C
O
35 C
EVAP FAN STOP TC
13
To change Evap Time Delay
parameter, press the set key.
0 Min
20 Min
Function: To set Evaporator Restart Time
Delay.
Use UP/DOWN keys to set desired
value.
This setting is used to limit the max.
temperature beyond which the Evap.
Fan will cut off.
Example
:
If this parameter is set to
O
O
2 C, then Evap. Fan will cut off at 2 C.
O
2 C
Function: To set Evaporator Fan Stop
Temperature.
1 Min
Example
:If this is set at 3 minutes, the
Evap. Fan relay will cut off at the temp.
set by Evap. Fan Stop TC. parameter
but the Fan will not come on for a
minimum of 3 minutes even if it’s
differential is achieved earlier.
Use UP/DOWN keys to set desired
value.
When compressor delay over Cond. Fan
will come ON first, after cond. On delay
over Comp will come ON.
CONDENSER ON DLY
To change the Condenser On
Dly parameter, press the set key.
12
Function: To Set Condensor On Delay
Timings..
0 Sec
30 Sec
15 Sec
Range
Min
Max
Fact. Set
DRIP TIME DUR
09
Function: To set drip time for defrost
water.
To change the Drip Time Dur
parameter, press the set key.
Use UP/DOWN keys to set desired
value.
During this period Compressor,
Evaporator Fan, LSV relay and Heater
will stay off so that the defrost water can
drip and drain out.
0 Min
30 Min
1 Min
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
To change the Post Drip Timing
parameter, press the set key.
POST DRIP TIMING
10
Function: To set Post Drip Timings.
Use UP/DOWN keys to set desired
value.
During this timing Compressor is ON
and Evaporator Will remain OFF also
Heater is OFF.
15 Sec
99 Sec
30 Sec
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Use UP/DOWN keys to set desired value.
0 = Evap Fan is off when compressor is
OFF.
1 = Evap fan will stay on when
compressor is OFF.
To change Evap Wn Comp Off
parameter, press the set key.
0
1
1
EVAP Wn COMP OFF
15
Function : To set Evap Fan operation
when compressor is off
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Sr.
No.
Parameter setting method
Description of parameters and functions.
Parameter
(LCD Message)
Sr.
No.
Parameter setting method
Description of parameters and functions.
Parameter
(LCD Message)
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
To change Evap Differential
parameter, press the set key.
EVAP DIFFERENTIAL
16
Function : To set Evaporator Differential.
Use UP/DOWN keys to set desired value.
Example
:If Evap Fan Stop Tc parameter
0
is set to 2 C, and if EVAP
0
DIFFERENTIAL parameter is set to 2 C,
0
then Evap. Fan will cut off at 2 C and
0
0
0
0
restart only at 0 C(2 C-2 C = 0 C).
1
O
C
O
20 C
O
2 C
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Summary of Contents for CRC 1200
Page 1: ......