P5
parameter

Function: To set probe 
calibration.

To change  
the P5 
parameter, 
press the 
SET key.

Use UP/DOWN keys to set desired 
range.
In time it may be possible that the 
display may be offset by a degree 
or so.
To compensate for this error, you 
may need to add or minus the 
degrees required to achieve the 
correct temperature. Setting  range 

O

O

is from -10 C to + 10 C

O

-10 C

Min Max

Fac.

O

+10 C

O

0 C

Example:

 The temperature on 

O

the display is 28 C, whereas the 

O

actual temperature is 30 C. You will 
need to set the P5 mode to 2, 
which means that once out of the 
programming mode, the display will 
show the temperature  

O

O

O

30 C (28 C + 2 C).

5

6

LP
parameter

Function : To lock keypad.

 0 

    1 

  0 

Min

Max

Fac.

To change
the LP
parameter,
press the
SET key.

Use UP/DOWN keys to set desired 
range. 
This Parameter can lock the 
keypad so that tampering is not 
possible by by-standers.

When set to
0= keypad unlocked
1= keypad locked

When locked all parameters can 
only be viewed, but not modified.

7

 AL 
parameter

0

1

1

Function: To activate / deactivate
alarm.

To change
the AL              
parameter,  
press the  
SET key.

Use the UP/DOWN keys to set 
alarm on or off. Once set to on, the 
buzzer will come on incase the 
temperature is equal to the set 
point.

1 = Activates  Buzzer.
0 = Deactivates  Buzzer.

Note=

Alarm will be ON in probe

          fail condition irrespective of 
          AL parameter

Min

Max

Fac.

FS
Parameter

Function : To restores default
settings of the controller.

To change 
the  FS
parameter,
press the
SET key.

When set to 1 all parameters
are programmed to default
values.
Useful to debug setting related 
problems.

1

Min

Max

Fac.

8

9

EP
Parameter

Function : To end programming.

To end 
programming 
press the
SET key

Once the SET key is pressed, 
the controller goes into the 
normal mode and displays the 
temperature and all settings are 
recorded.

This key will reset the relay and 
mute the buzzer alarm.

Reset key

RST

10

Operating messages and Icon status

Parameter

Set Point

 AL , P3

Message

Description

Lt

Temperature is equal to the set point.

PP

Probe short circuit, circuit open or without

0

0

probe, or temperature >50 C or < -50 C 

Alarm (Lt or PP)

LP

Keypad locked/unlocked.

O

SP + 2 C

Compressor Relay On/Off. 

On/Off

On/Off

Flashing

Summary of Contents for SZ-7512-P

Page 1: ...he above mentioned mechanical thermostats i e relay will go off when the set point is achieved and the same can be restarted only if the differential is reached and the RST key is pressed 1 INDEX 2 Para Page Description P5 LP AL FS EP 3 4 5 6 7 8 9 10 12 13 14 To set the Set Point of the controller How to set other parameters Probe calibration Keypad lock Alarm to activate buzzer Restore factory d...

Page 2: ...eter 0 1 1 Function To activate deactivate alarm To change the AL parameter press the SET key Use the UP DOWN keys to set alarm on or off Once set to on the buzzer will come on incase the temperature is equal to the set point 1 Activates Buzzer 0 Deactivates Buzzer Note Alarm will be ON in probe fail condition irrespective of AL parameter Min Max Fac FS Parameter Function To restores default setti...

Page 3: ...RNING Improper wiring may cause irreparable damage and personal injury Kindly ensure that wiring is done by qualified personnel only Maintenance Cleaning Clean the surface of the controller with a soft moist cloth Do not use abrasive detergents petrol alcohol or solvents Notice The information in this document is subject to change in order to improve reliability design or function without prior no...

Page 4: ...ssion further manufacture other use or resale of the products whether used alone or in combination with any other products or materials ASCPL makes NO other warranty expressed or implied and makes no warranty of merchantibility or fitness for any particular purpose From time to time buyers might call to ask ASCPL for technical advice based upon limited facts disclosed to ASCPL If ASCPL furnishes t...

Reviews: