E.g. If this Parameter is set to 30sec ,then 
second compressor will come on after 30sec 
delay from first compressor switch on.

F1

Fan Operating Mode

0=Fan Always On
1=Fan on with compressor 

F

0

1

0

Flag

1

F2

Starting Time of Fans

Fans will start these many seconds before the
compressor starts . 

F

0

120

20

Sec

1

A0

AFT Probe Active
To activate Antifreeze(AFT) Probe 
Function

0 = Disable AFT probe.
1 = Enable AFT probe.

F

0

1

0

Flag

1

A1

Antifreeze set point for AFT Probe

F

-30

R1

4

o

C

1

A2

Differential for AFT Probe

F

1

10

2

o

C

1

P1

Flow switch alarm delayed at power on.

System will activate the alarm only if the 
error persists for more than P1 secs at system
start up.

F

0

120

5

Sec

1

P2

Flow Switch Alarm delay during normal 
operation.

If this parameter is set at 10 seconds , the 
system will activate the flow switch alarm 
only if the error persists for or more than 10 
seconds .In this manner a false alarm can be 
avoided during normal operation.

F

0

90

5

Sec

1

P3

Low Pressure Alarm delayed during 
compressor start up

If this parameter is set at 30 seconds , the 
system will activate the low pressure switch 
alarm only if the error persists for or more 
than 30 seconds .In this manner a false alarm 
can be avoided due to low pressure at 
compressor start up.

F

0

120

40

Sec

1

P4

Reset of alarms.

0= Manual Reset for HP,OSS and AFT 
alarms
1= Auto Reset for HP,OSS and AFT alarms

F

0

1

0

Flag

1

H0

PUMP Start Logic 
PUMP with Comp

It defines Pump working logic.
0= Pump Always On.
1= Pump On/Off with Comp.

F

0

1

0

Flag

1

H1

To activate Pumpdown procedure

This parameter is used to activate or 
deactivate pumpdown procedure at every 
refrigeration cycle .
0 = Inactivate Pumpdown

    F

0

1

0

Flag

0

Summary of Contents for Mega Chill-3Comp

Page 1: ...H Setting the parameters I Technical Data Introduction The MEGA CHILL 3Comp is a three compressor chiller controller This integrates all the required functions of the chiller It is very user friendly...

Page 2: ...ISPLAY LCD The Liquid Crystal Display shows the values of the controlled parameters the selected set point the alarm thresholds and all other information concerning the controlled variables DISPLAY ty...

Page 3: ...P O L1 OSS Oil Safety Switch OSS1 Single Phase Preventor Trip1 SPP1 High Pressure trip for the compressor2 HP2 Low Pressure Trip for the compressor2 LP2 Compressor Overload trip2 COMP O L2 OSS Oil Saf...

Page 4: ...ode MUTE Press this key for 1 second to disable the buzzer and alarm relay RESET Press and hold this key for 4 seconds to reset HP LPand antifreeze alarms which have been set for MANUAL RESET incase P...

Page 5: ...h parameter t1 Using UP DOWN key user can scroll all the parameters By pressing SEL key user can view and change respective parameter value Press PRG to store and exit from that particular parameter T...

Page 6: ...ill not allow the set point to go below 300 C Also if the temperature reaches 300 C the display will show Lt Low Temp indicating that the temperature has gone below the range in this parameter and at...

Page 7: ...this parameter is set at 10 seconds the system will activate the flow switch alarm only if the error persists for or more than 10 seconds In this manner a false alarm can be avoided during normal oper...

Page 8: ...N 0 Unit3Inactive 1 Unit3 Active Incase of 0 system will not activate compressor1 and all its faults F 0 1 1 Flag 1 H7 Fault in standby It Enable Disable fault sensing in standby mode 0 Disable 1 Enab...

Page 9: ...esistive All digital outputs are fused 5 Operating Temperature 5 0 C to 500 C 6 Operating Humidity max 80 non condensing 7 Mounting Panel mounting type 8 Fuse 1 5A 9 Power Source Transformer Rating In...

Reviews: