SET-POINT AND DIFFERENTIAL

Set-point is the temperature at which the chiller temperature has to be regulated, at which 
time the compressor will go off. Differential is the temperature added after which the 
compressor restarts. For example, if  Set-point is 7

o

C and differential is 2

o

C, then 

compressor  will switch off at 7

 o

C and restart at 7+2 = 9

o

C. 

*******ALARMS*******

Incase of all alarms corresponding LCD readouts and LED signals will display,and the 
system will act accordingly. For example if there is an HP1 error, Compressor1 will trip 
and restarts with the time delay. 

PARAMETER SETTINGS :

     All  “working” parameters are protected with a hardware key to prevent any  
unauthorized access to the data. Press PRG + SEL for more than 5 seconds to enter the 
parameter mode. To change any parameter PROKEY must be inserted before entering to 
the programming mode.

Display will flash parameter “t1” . Using UP/DOWN key user can scroll all the 
parameters . By pressing “SEL” key user can view and change respective parameter 
value. Press PRG to store and exit from that particular parameter.  To End 
Programming press SEL key when LED display shows EP

If you do not press any button within 20 seconds after having entered this 

procedure, the unit will return to normal operation without storing the values of the 
modified parameters.

Setting and displaying set parameters.

Para

Probe

Set by Min Max Fac.

M.U

Variation

T1

Control Probe calibration.

It may so happen that during the course of 
time there may be a slight offset in the actual 
temperature and the temperature shown. For 
example if the actual temperature is 20

 o

and the temperature on the controller shows 
22

 o

C, set this parameter to -2

 o

C and once out

of this mode, the temperature will display 20

 

o

C (22-2

 o

C)

U

-10

10

0

o

C

0.5

T2

Antifreeze probe calibration.
Setting as in T1.

U

-10

10

0

o

C

0.5

R1

Set point for compressor1

U

R4

R3

10

o

C

0.5

R2

Set point for compressor2

U

R4

R3

7

o

C

0.5

Summary of Contents for Mega Chill-3Comp

Page 1: ...H Setting the parameters I Technical Data Introduction The MEGA CHILL 3Comp is a three compressor chiller controller This integrates all the required functions of the chiller It is very user friendly...

Page 2: ...ISPLAY LCD The Liquid Crystal Display shows the values of the controlled parameters the selected set point the alarm thresholds and all other information concerning the controlled variables DISPLAY ty...

Page 3: ...P O L1 OSS Oil Safety Switch OSS1 Single Phase Preventor Trip1 SPP1 High Pressure trip for the compressor2 HP2 Low Pressure Trip for the compressor2 LP2 Compressor Overload trip2 COMP O L2 OSS Oil Saf...

Page 4: ...ode MUTE Press this key for 1 second to disable the buzzer and alarm relay RESET Press and hold this key for 4 seconds to reset HP LPand antifreeze alarms which have been set for MANUAL RESET incase P...

Page 5: ...h parameter t1 Using UP DOWN key user can scroll all the parameters By pressing SEL key user can view and change respective parameter value Press PRG to store and exit from that particular parameter T...

Page 6: ...ill not allow the set point to go below 300 C Also if the temperature reaches 300 C the display will show Lt Low Temp indicating that the temperature has gone below the range in this parameter and at...

Page 7: ...this parameter is set at 10 seconds the system will activate the flow switch alarm only if the error persists for or more than 10 seconds In this manner a false alarm can be avoided during normal oper...

Page 8: ...N 0 Unit3Inactive 1 Unit3 Active Incase of 0 system will not activate compressor1 and all its faults F 0 1 1 Flag 1 H7 Fault in standby It Enable Disable fault sensing in standby mode 0 Disable 1 Enab...

Page 9: ...esistive All digital outputs are fused 5 Operating Temperature 5 0 C to 500 C 6 Operating Humidity max 80 non condensing 7 Mounting Panel mounting type 8 Fuse 1 5A 9 Power Source Transformer Rating In...

Reviews: