15

DX System

STULZ CyberRow

12 - 33 kW Row-Based

Precision Control Air Conditioners 

Direct Expansion - Air, Water, Glycol

SUMMARY

This specification describes requirements for a precision 
environmental control system. The STULZ CyberRow is a row-based 
cooling system that shall provide precision temperature control 
for computer rooms, or rooms containing telecommunications 
or other highly sensitive heat load equipment, where continuous 

24  hours  a  day  365  days  a  year  air  conditioning  is  required. 

Designed with both front and rear access, CyberRow systems 
require minimum floor space. The supplied system shall be 
provided with ETL Certification. The CyberRow model number 
shall be, CRS - _ _ _ - _ .

DESIGN REQUIREMENTS

The environmental control system shall be a STULZ CyberRow 
Direct Expansion (DX) factory-assembled unit. The unit shall be 
designed for a row-based installation with removable front and 
rear access panels. No allowance for side service access shall 
be required, however removable side access panels shall be 
provided for additional access. 

CyberRow units are especially adapted for both raised and 
non-raised floors. The air handling system shall be specifically 
designed for high sensible heat ratio. Each system shall be 
capable of handling ___CFM. The unit shall have the cooling 
capacity of ___BTU/H, and the sensible cooling capacity of ___
BTU/H based on entering air condition of ___°F dry bulb and 
___°F (°C) wet bulb. The main fan motors shall be ___HP. The 
unit shall have a power supply of ___volts.

QUALITY ASSURANCE

The manufacturer shall maintain a set of international standards 
of quality management to ensure product quality. Each system 
shall be subjected to a complete operational and functional test 
procedure at the factory prior to shipment. 

CABINET

Side access panels shall be fabricated from 20 gauge 
galvannealed steel and shall be securely bolted to a 

14 gauge base and the top plate. The top plate, front 

and rear panels shall be  fabricated from 16 gauge 
galvannealed steel. The cabinet shall be powder coated 
with a satin black finish to provide durability, and to 
protect from corrosion. Armaflex elastomeric thermal 
insulation shall be used to insulate the cabinet, block 
noise and prevent damage from vibration. Casters and 
leveling feet shall be included to ease the installation 
and level the equipment with existing IT solutions.

AIRFLOW PATTERNS

All units shall be designed using a front discharge with 
a rear return airflow pattern. An optional plenum with a 
front diverted discharge pattern is available.

AIR FILTRATION

All units shall be equipped with removable, washable 
filters. These filters shall consist of an open cell 
structured polyurethane foam with a roll formed 3000 
series aluminum frame. Filters shall meet both UL 900 

and UL 94 HF-1 standards.

MECHANICAL COMPONENTS

BACKWARD INCLINED, PLENUM STYLE 
FAN, WITH AN EC MOTOR

The blowers shall be backward inclined plenum style 
fans with an Electronically Commutated (EC) motor, 
for maintenance free operation. The motor shall 
include: integrated electronic control board and direct 
microprocessor control signaling for fan speed control, 
soft-starting capabilities, and integrated current 
limitations. Each fan shall be low noise, low vibration 
manufactured with an anti-corrosive aluminum impeller. 
Each fan impeller shall be dynamically and statically 
balanced in two planes to minimize vibration during 
operation.

REFRIGERATION SYSTEM

All piping and components contained within the 

refrigeration system shall be rated for use with R410A 

PRODUCT GUIDE SPECIFICA

TIONS

Summary of Contents for STULZ CyberRow

Page 1: ...DX System STULZ CyberRow Engineering Manual Engineering Manual EM 12 33 kW Direct Expansion DX Air Water Glycol Row Based Data Center Cooling Utilizing EC Fan Technology 60 Hz Data Indoor Cooling Row...

Page 2: ...ty fast lead times and outstanding customer service make STULZ the perfect choice for all your environmental control needs ISO 9001 Quality Registered STULZ is committed to satisfying customer expecta...

Page 3: ...ature 4 Model Features 4 Model Nomenclature Specifications 5 Configurations 6 Technical Data 7 Performance Data 8 Electrical Sound Data 8 Sound Data 8 Dimensional Data 9 Product Features 10 Product Gu...

Page 4: ...ndently and infinitely adjustable EC fans ensure maximum efficiency Used in containment open architecture and hot spot reduction applications Adapts to both high and low density IT environments Wide r...

Page 5: ...ter shall be provided by a cooling tower or some other remote water source Head Pressure Control Head pressure shall be automatically controlled by factory installed 2 way or 3 way water regulating va...

Page 6: ...prevents from mixing with cool air The front of IT equipment is accessed in the external cold aisle The STULZ CyberRow draws the contained hot air from the hot aisle removes the heat and supplies coo...

Page 7: ...Standard Standard Standard Standard HUMIDITY CONTROL 5lb Electrode Canister Steam Humidifier N A N A N A Optional 9kW Electric Heat Reheat N A N A N A Optional E MICROPROCESSOR CONTROLLER A C Groupin...

Page 8: ...l R410A Type Qty Scroll 1 Scroll 1 Scroll 1 Scroll 1 Watts Input 3 830 7 540 8 700 8 700 Tot Heat of Rej MBH 64 6 124 131 8 131 8 Condenser Type Remote Air Cooled Head Pressure Control See Remote Cond...

Page 9: ...ll R410A Type Qty Watts Input 2 970 4 090 6 140 7 920 6 900 9 700 6 900 9 700 Tot Heat of Rej MBH 66 64 128 124 135 131 135 131 GPM 85 F EWT 95 F LWT 0 Glycol Solution 13 2 N A 25 6 N A 27 1 N A 27 1...

Page 10: ...9 53 48 94 101 92 Sensible 49 53 48 94 101 92 Total KW 14 15 14 27 30 27 Sensible 14 15 14 27 30 27 90 FDB 66 1 FWB Entering Air Temperature Total MBH 46 50 45 88 97 88 Sensible 46 50 45 88 87 88 Tota...

Page 11: ...99 86 Sensible 89 95 86 89 95 86 Total KW 26 29 25 26 29 25 Sensible 26 28 25 26 28 25 80 FDB 62 8 FWB Entering Air Temperature Total MBH 87 97 84 87 97 84 Sensible 84 89 94 26 89 94 Total KW 26 29 2...

Page 12: ...he component of sound intensity that is normal to a measurement surface The measurement surface is chosen to enclose the noise source s so that the sound power level can be determined Electrical Data...

Page 13: ...NNECTION POWER CONNECTION POWER CONNECTIONS PIPING CONNECTIONS CONDENSATE CONNECTION 11 6 77 8 42 1 CONDENSATE CONNECTION PIPING CONNECTION POWER CONNECTION AIROUT AIRIN AIR OUT AIR IN POWER CONNECTIO...

Page 14: ...ECTIONS PIPING CONNECTIONS Top Piping Option Bottom Piping Option Side Diverted Front Panel Option HUMIDIFIER CONNECTIONS POWER CONNECTIONS PIPING CONNECTIONS CONDENSATE CONNECTION AIR IN AIR OUT PIPI...

Page 15: ...complete operational and functional test procedure at the factory prior to shipment CABINET Side access panels shall be fabricated from 20 gauge galvannealed steel and shall be securely bolted to a 14...

Page 16: ...control capabilities The controller shall provide the user an adjustable supply air control setpoint refrigerant Each refrigeration circuit shall include as a minimum a refrigerant dryer strainer sig...

Page 17: ...600 psig Regulating Valve W G Optional The refrigerant circuit head pressure shall be controlled by a factory installed 3 way water glycol regulating valve rated for 400 psig w w p The 3 way condenser...

Page 18: ...ding Management System via Modbus BACnet SNMP or HTTP as configured by the factory A controller interfaced to a network must be configured for BMS communication 18 MAIN POWER SERVICE SWITCH The CyberR...

Page 19: ...e humidifier shall have modulating output between 20 and 100 of rated capacity Electric Heat Reheat A factory mounted and wired low watt density plated fin tubular design electric resistance heater sh...