STULZ CyberRow

variables. Three secured menu levels (Control, Service and 
Factory) will support unique passwords that must be entered 
to access the menu screens so only authorized personnel may 
perform modifications to the settings.

RESTORABLE PARAMETERS/FACTORY 
DEFAULTS

Upon initial start-up the CyberRow system shall operate using 
the setpoints programmed by the factory. The customer may 
enter new operating parameters in the Control menu and 
the system will then operate accordingly. The new setpoints 

may be stored as, "Customer Default Setpoints". The primary 

setpoints entered by the factory still remain stored in the 

controller's memory as, "Factory Setpoints". The setpoints for 

the system may be readjusted in the Control menu at any time. 
If it becomes necessary, the customer may restore the setpoints 
back to the Customer Default setpoint values or to the original 
factory (primary) setpoint values. 

A/C GROUPING pLAN OPERATION 
(OPTIONAL)

Multiple CyberRow system controllers shall be able to connect 
(grouped) to a pLAN local network, allowing the communication 
of data and information from each controller to a central control 
terminal or lead controller. The lead controller display screens 
can be used to monitor and adjust group control variables for 
the individual system controllers. Each 

 controller connected 

to the pLAN network shall be identified with its own unique 
address.
Multiple CyberRow units consisting of up to eight STULZ 
precision air conditioners equipped with like controllers may 
be controlled and monitored via the 

 series controller. With 

multiple CyberRow units each unit can selectively be configured 
as “Active” to operate as a primary A/C, “Capacity Assist” for 
staged operation, or as “Standby” to come online in case of 
a failed air conditioning unit to ensure continuous availability. 
The controller may also be configured to rotate units with 
timed duty cycling to promote equal run-time and ensure that 
each CyberRow unit within the rotating group is operationally 
exercised on a periodic timed basis.

BMS INTERFACE (OPTIONAL)

The 

 

series controller may incorporate a 10 Mbps 

communication interface port that can be field connected 
through a serial interface to a Building Management System via 
Modbus, BACnet, SNMP, or HTTP as configured by the factory. 
A controller interfaced to a network must be configured for 
BMS communication. 

18

MAIN POWER SERVICE SWITCH

The CyberRow unit shall be provided with a unit mounted 
main power service switch.

 

SERIES CONTROLLER

GENERAL

The advanced microprocessor based 

 Series controller 

shall be equipped with flexible software capable of meeting 
the specific needs of the application. The setpoints shall 
be default and their ranges shall be easily viewed and 
adjusted from the user interface display. The program and 
operating parameters shall be permanently stored on a 
non-volatile system in the event of power failure.  The 
controller shall be designed to manage temperature and 
relative humidity (RH) levels to a user defined setpoint 
via control output signals to the CyberRow unit. Control 

parameters have variable outputs from 0 to 100% of the 

full rated capacity. 
The controller shall receive inputs for measurable control 
conditions (temperature, relative humidity, and dew point) 
via return air or remote mounted supply air sensors. The 
internal logic will then determine if the conditions require 
cooling. Control setpoints shall be established to maintain 
design conditions of the installation. The controller will 
respond accordingly to changes in these conditions and 
control the output/demand for the appropriate mode of 
operation until user defined conditions are achieved.

FIELD CONFIGURABLE

The program for the 

 Series controller shall be field 

configurable, allowing the operator the capability of 
selecting control setpoints specific to the application. 
Operator interface for the 

 controller is provided 

via a door mounted user interface display panel. The 
display panel shall have a backlit LCD graphical display 
and function keys giving the user complete control and 
monitoring capability of the precision cooling system. The 
menu driven interface shall provide users the ability to 
scroll through and enter various menu screens.

PASSWORD PROTECTION

Access to the Info Menu, Alarms Log, and the ability to 
monitor room conditions shall be allowed without the 
use of a password. Modifications to the control setpoints 
shall require the use of a password. The controller shall be 
programmed to recognize predetermined security levels 
before allowing access to display screens containing critical 

PRODUCT GUIDE SPECIFICA

TIONS

Summary of Contents for STULZ CyberRow

Page 1: ...DX System STULZ CyberRow Engineering Manual Engineering Manual EM 12 33 kW Direct Expansion DX Air Water Glycol Row Based Data Center Cooling Utilizing EC Fan Technology 60 Hz Data Indoor Cooling Row...

Page 2: ...ty fast lead times and outstanding customer service make STULZ the perfect choice for all your environmental control needs ISO 9001 Quality Registered STULZ is committed to satisfying customer expecta...

Page 3: ...ature 4 Model Features 4 Model Nomenclature Specifications 5 Configurations 6 Technical Data 7 Performance Data 8 Electrical Sound Data 8 Sound Data 8 Dimensional Data 9 Product Features 10 Product Gu...

Page 4: ...ndently and infinitely adjustable EC fans ensure maximum efficiency Used in containment open architecture and hot spot reduction applications Adapts to both high and low density IT environments Wide r...

Page 5: ...ter shall be provided by a cooling tower or some other remote water source Head Pressure Control Head pressure shall be automatically controlled by factory installed 2 way or 3 way water regulating va...

Page 6: ...prevents from mixing with cool air The front of IT equipment is accessed in the external cold aisle The STULZ CyberRow draws the contained hot air from the hot aisle removes the heat and supplies coo...

Page 7: ...Standard Standard Standard Standard HUMIDITY CONTROL 5lb Electrode Canister Steam Humidifier N A N A N A Optional 9kW Electric Heat Reheat N A N A N A Optional E MICROPROCESSOR CONTROLLER A C Groupin...

Page 8: ...l R410A Type Qty Scroll 1 Scroll 1 Scroll 1 Scroll 1 Watts Input 3 830 7 540 8 700 8 700 Tot Heat of Rej MBH 64 6 124 131 8 131 8 Condenser Type Remote Air Cooled Head Pressure Control See Remote Cond...

Page 9: ...ll R410A Type Qty Watts Input 2 970 4 090 6 140 7 920 6 900 9 700 6 900 9 700 Tot Heat of Rej MBH 66 64 128 124 135 131 135 131 GPM 85 F EWT 95 F LWT 0 Glycol Solution 13 2 N A 25 6 N A 27 1 N A 27 1...

Page 10: ...9 53 48 94 101 92 Sensible 49 53 48 94 101 92 Total KW 14 15 14 27 30 27 Sensible 14 15 14 27 30 27 90 FDB 66 1 FWB Entering Air Temperature Total MBH 46 50 45 88 97 88 Sensible 46 50 45 88 87 88 Tota...

Page 11: ...99 86 Sensible 89 95 86 89 95 86 Total KW 26 29 25 26 29 25 Sensible 26 28 25 26 28 25 80 FDB 62 8 FWB Entering Air Temperature Total MBH 87 97 84 87 97 84 Sensible 84 89 94 26 89 94 Total KW 26 29 2...

Page 12: ...he component of sound intensity that is normal to a measurement surface The measurement surface is chosen to enclose the noise source s so that the sound power level can be determined Electrical Data...

Page 13: ...NNECTION POWER CONNECTION POWER CONNECTIONS PIPING CONNECTIONS CONDENSATE CONNECTION 11 6 77 8 42 1 CONDENSATE CONNECTION PIPING CONNECTION POWER CONNECTION AIROUT AIRIN AIR OUT AIR IN POWER CONNECTIO...

Page 14: ...ECTIONS PIPING CONNECTIONS Top Piping Option Bottom Piping Option Side Diverted Front Panel Option HUMIDIFIER CONNECTIONS POWER CONNECTIONS PIPING CONNECTIONS CONDENSATE CONNECTION AIR IN AIR OUT PIPI...

Page 15: ...complete operational and functional test procedure at the factory prior to shipment CABINET Side access panels shall be fabricated from 20 gauge galvannealed steel and shall be securely bolted to a 14...

Page 16: ...control capabilities The controller shall provide the user an adjustable supply air control setpoint refrigerant Each refrigeration circuit shall include as a minimum a refrigerant dryer strainer sig...

Page 17: ...600 psig Regulating Valve W G Optional The refrigerant circuit head pressure shall be controlled by a factory installed 3 way water glycol regulating valve rated for 400 psig w w p The 3 way condenser...

Page 18: ...ding Management System via Modbus BACnet SNMP or HTTP as configured by the factory A controller interfaced to a network must be configured for BMS communication 18 MAIN POWER SERVICE SWITCH The CyberR...

Page 19: ...e humidifier shall have modulating output between 20 and 100 of rated capacity Electric Heat Reheat A factory mounted and wired low watt density plated fin tubular design electric resistance heater sh...