DEZ
S
ERIES
1000
I
NSTALLATION
,
O
PERATION AND
M
AINTENANCE
M
ANUAL
B-2
NOTE:
Process air outlet
temperatures as shown are
maximum values at standard
full rated heater output. The
actual process outlet
temperature will be lower
when the heater output is
below full rated output. This
condition will occur during
heater modulation cycles
due to partial loading of the
dehumidifier.
Performance for DEZ-300-40
Grains Per Pound (GPP)
1. Find the correct “Process Entering Moisture” (humidity) value in
grains per pound (GPP) on the x-axis of the Moisture Removal
Capacity graph.
2. Move vertically in a straight line to intersect the curve closest to the
entering air temperature. Interpolate as required.
3.
Move horizontally to the left and intersect the scale marked “Process
Leaving Air Moisture”. The value at this point represents the process
air moisture (humidity) leaving the dehumidifier in GPP
Leaving Temperature
1. Find the correct “Process Entering Moisture” (humidity) value in
grains per pound (GPP) on the x-axis of the Process Leaving Air
Temperature graph.
2. Move vertically in a straight line to intersect the curve closest to the
entering air temperature. Interpolate as required.
3. Move horizontally to the left and intersect the scale marked “Process
leaving Air Temperature”. The value at this point represents the air
temperature leaving the dehumidifier in
F.