background image

CyberOne EC CW IOM Manual 

 

19 

 

 

 

 

4.4

 

Field Service

 

NOTE

 

Do not attempt to make repairs without the proper 
tools.

 

4.4.1

 

CW Leaks

 

A leak in a chilled water cooling system will usually form an 
obvious puddle of fluid beneath the unit. To locate the point 
of leakage, visually trace the leak up from the puddle to the 
area on the unit where fluid is seen dripping.

 

4.4.1.1  CW Leak Repair

 

When a leak is detected, properly reclaim the remaining CW 
coolant before attempting repairs. Adjacent piping must be 

thoroughly cleaned by removing all paint, dirt and oily film. 
Use a wire brush, sandcloth or sandpaper and wipe the area 
with clean,  dry  cloths.  Protect  nearby  parts  from  heat 
damage by wrapping with water-soaked cloths.

 

For copper-to-copper (piping) repairs use SILFOS Alloy. No 
flux is required with Silfos Alloy. Silver solder (Stay Silv #45) 
and flux should be used on copper-to-brass or copper-to- 
steel repairs.

 

When repairs are completed, remove all traces of flux. After 
any repair, check for leaks prior to recharging the system.

 

4.4.2

 

Humidifier    Cylinder    Replacement 

After an extended period of operation, the yellow LED on the 
humidifier cabinet will repeatedly flash four times indicating 
that the cylinder is completely used and a replacement 
cylinder must be installed. The cylinder is disposable and 
cylinder life is dependent on water supply conditions and 
humidifier usage. Use the following procedure to replace 
the cylinder.

 

CAUTION

 

 

Failure to replace the cylinder at the end of cylinder 
life may result in humidifier damage.

 

 

NOTE

 

Decrease the humidity set point below actual 
conditioned space humidity to allow the cylinder 
to cool down prior to removal.

 

 

1.

 

Turn the unit off, preferably in a manner that uses the 
controller, such as via BMS or the controller terminal.

 

2.

 

Turn off the water supply to the humidifier using the small 
manual ball valve (in the unit skid, under the compart- 
ment where the humidifier is located) that tees off the 
main water supply.

 

3.

 

Enter the cabinet section that houses the humidifier and 
drain the humidifier cylinder by toggling the ON/OFF/ 
DRAIN switch on the humidifier to DRAIN.

 

4.

 

Allow the cylinder to completely drain then turn the hu- 
midifier off by toggling the ON/OFF/DRAIN switch on 
the humidifier to OFF.

 

5.

 

Exit the cabinet  and turn off  main power using  the 
through-door disconnect switch on the door of the Unit 
Control Box.

 

6.

 

Follow the steps of the cylinder removal, drain valve 
cleaning  and  cylinder installation procedures  in  the 
humidifier installation and operation manual, which was 
provided under separate cover with your unit.

 

7.

 

Close up the cabinet and turn main power on using the 
through-door disconnect switch on the door of the Unit 
control box.

 

8.

 

Open the manual ball valve that was closed in Step 2.

 

9.

 

Turn the unit on and readjust the humidity set point.

 

If the humidifier is to be shut down for an extended period, 
follow the steps of the Extended Shutdown procedure in the 
Nortec MES2 Installation and Operation Manual. 

CAUTION

 

 

Failure to perform the recommended Extended 
Shutdown procedure before a prolonged shut- 
down period will drastically shorten cylinder life.

 

4.4.3

 

Air Filter Replacement

 

To change the air filters, open the front doors of the cabinet. 
The air filters are accessed from inside the cabinet (except for 
upflow units with rear return). For upflow units, the filters are 

located behind the air intake grilles. For downflow units, the 
filters are located at the top where the label “FILTER ACCESS” 
appears. Remove the old filters from the trays. Insert the new 
filter(s) ensuring the directional airflow arrows on the filters 
are correct, then close the front doors.

 

 

 

Summary of Contents for CyberOne EC CW

Page 1: ...CyberOne EC CW Installation Operation and Maintenance Manual Perimeter Precision Air Handlers 12 kW 35 kW 60 Hz...

Page 2: ...r Technology Systems Inc STULZ This document contains con dential and proprietary information of STULZ Distributing or photocopying this document for external distribution is in direct violation of U...

Page 3: ...erns 8 2 6 Optional Equipment Field Installed 10 2 6 1 Floor Stand 10 2 6 2 Remote Controller Terminal 10 2 6 3 Remote Temperature Humidity Sensor 10 2 6 4 Remote Water Detector 10 2 6 5 Plenum Box As...

Page 4: ...1 Typical CW Internal Layout Down ow Con guration 3 Figure 2 Typical CW Internal Layout Up ow Con guration 3 Figure 3 Recommended Installation Clearance 6 Figure 4 Down ow Con guration TypicalAir Pat...

Page 5: ...an Cooling COS CyberOne 042 060 096 120 CW Chilled Water D Downflow Air U Upflow Air EC Direct Driven single inlet two fold backward curved radial fan with electronically commutated EC motor Call Prod...

Page 6: ...understandallrelevant instructions recommendations and guidelines contained within this manual Certain maintenance orcleaning procedures maycallforthe useandhandlingofchemicals solvents orcleansers Al...

Page 7: ...nting to a wall or controlpanel An operating manual for the system controller is provided under separate cover Refer to that manual for detailed instructions on operating the system controller provide...

Page 8: ...CH NOTE 1 HOT WATER REHEAT COIL CONDENSATE PUMP FRONT SIDE RIGHT SIDE NOTES 1 SERVICE DISCONNECT SWITCH HANDLE IS MOUNTED TO FRONT DOOR OF CABINET 2 CABINET DOOR AND RIGHT SIDE ACCESS PANEL REMOVED TO...

Page 9: ...motor2 1 Upon correction of these failure conditions the motor will automatically reset 2 Upon correction of these failure conditions the motormust be manuallyreset byturning offpower for 20 seconds...

Page 10: ...Humidity T H Sensor A T H sensor may be selected as an option for use with the COS EC CW unit The sensor will be shipped loose for eld installation somewhere in the conditioned space away from the un...

Page 11: ...ner unless specified otherwise by the customer A plenum box if applicable is shipped separately Unpack and storethese itemsin asafe place unless you are using them immediately 2 2 Moving the Equipment...

Page 12: ...y air to only one room They have a compact footprint which allows the units to be placed in a corner or between cabinetry It is recommended to position the unit to obtain optimum aircirculation NOTE T...

Page 13: ...with the unit Ductwork may be connected with either pop rivets or self tapping screws 2 5 2 Up ow Con guration Air Patterns In a con gured unit the conditioned supply air has two methods of discharge...

Page 14: ...ns REAR DUCTED RETURN FRONT FREE RETURN RETURN AIR INLET RETURN AIR INLET SUPPLY AIR OUTLET TOP DUCTED DISCHARGE SUPPLY AIR OUTLET REAR DUCTED RETURN FRONT FREE RETURN RETURN AIR INLET RETURN AIR INLE...

Page 15: ...Temperature Humidity Sensor The remote temperature humidity T H sensor must be located so that it will properly sense the temperature humidity conditions to be controlled The T H sensor should not be...

Page 16: ...ws provided Holes are pre drilled in the unit and the plenum box If mounting an air distributionplenumbox the grillesmaybe removedforaccess to the mounting holes 2 7 Piping Connections Fordown owmodel...

Page 17: ...g supplied with the unit for all power and control eld wiring It is important to identify the optionsthat were purchased withthe unit in orderto con rm which eld connections arerequired NOTE If the na...

Page 18: ...orrequiresashielded cablewiththeshieldterminatedattheunitelectricbox Three control conductors are required Both the electric box and the sensorinclude aterminal stripwith box type lugsforwire connecti...

Page 19: ...rol valve and the temperature of the water has decreased as it passes through the unit 6 If a humidi er is present test humidi cation operation by creating a demand for humidi cation Use an amp metert...

Page 20: ...ked at least monthly and replaced as required NOTE Airqualityinconditionedspacesvaries Aschedule for checking air lters should be based on those conditions 4 2 2 EC Fan Periodically check the EC fan s...

Page 21: ...bable Cause Recommendation Chilled Water Valve Fails to Open or Close Temperature setpoint too high or low Adjust to correct temperature setting No control power to the chilled water valve Valve actua...

Page 22: ...heck filters and dampers Clear coil fins of debris Electric Heater Inoperable Circuit breaker tripped Check for short circuit reset circuit breaker Temperature setpoint too low Increase temperature se...

Page 23: ...ighten electrical connections Humidifier circuit breaker tripped Check for excess current draw by the humidifier electrodes Drain water from tank and refill Reset circuit breaker Defective contactor R...

Page 24: ...that uses the controller such as via BMS orthe controller terminal 2 Turnoffthewatersupplytothehumidi erusingthesmall manual ball valve in the unit skid under the compart ment where the humidi er is...

Page 25: ...e for the shipping charges If you do not have established credit with STULZ you must provide a freight carrier account number A written or faxed purchase order is required on warranty parts and must b...

Page 26: ...pan safety switch operates freely Additional Check chilled water hot water circuits for air bleed as required Coils clean and clear of obstructions Humidifier cylinder and controls operate properly Ta...

Page 27: ...l support call 888 529 1266 or email stulztechnicalsupport stulz ats com Support is available 24 7 365 Provide the model number serial number and STULZ item number from the unit nameplate This will sp...

Page 28: ...FPA National Fire Protection Agency CFM Cubic Feet Per Minute PH Phase EC Electronically Commutated PSI Pounds Per Square Inch DP Dewpoint PSIG Pounds Per Square Inch Gauge DX Direct Expansion RLA Run...

Page 29: ...ogy Systems Inc 1572 Tilco Drive Frederick MD 21704 301 620 2033 Fax 301 662 5487 info stulz ats com Technical Support 888 529 1266 www stulz usa com OCCO209A Feb 2020 STULZ Air Technology Systems Inc...

Reviews: